ويشات: +86-13184948252 واتس اب: 0086-13811255435 بريد إلكتروني: كينت@bestcontactor.com

عن اتصال |

A9L40600 Schneider surge protection - المقاولين,قاطع الدائرة,العاكس للطاقة الشمسية,عداد كهرباء,البطاريات الشمسية

كهربائي/

A9L40600 Schneider surge protection

Model A9L40600 SchneiderModel Analysis and Technical Parameters A9L40600 is the complete order number of a low-voltage surge protection product (Surge Arrester) under Schneider Electric‘s Acti9 Series. It belongs to the iPRD40 modular surge arrester series and is mainly used for Type 2 surge protection in power distribution systems. Model Segment Analysis Code Segment ...

  • تفاصيل المنتج

Model A9L40600 SchneiderModel Analysis and Technical Parameters

A9L40600 is the complete order number of a low-voltage surge protection product (Surge Arrester) under شنايدر إلكتريك‘s Acti9 Series. It belongs to the iPRD40 modular surge arrester series and is mainly used for Type 2 surge protection in power distribution systems.

  1. Model Segment Analysis
Code SegmentوصفCorresponding Product Attribute
A9Schneider Acti9 Series IdentifierA standardized low-voltage component series for terminal power distribution, including circuit breakers, surge arresters, إلخ.
L40Product Type Sub-codeRepresents the iPRD40 series modular surge arrester. “ل” generally indicates surge protection products, و “40” corresponds to the 40kA maximum discharge current rating.
600Structural Feature and Configuration CodeCorresponding to 3P+N (three-phase + neutral) pole configuration, 350V rated voltage, and equipped with a pluggable trip module
  1. Summary of Core Product Attributes
ItemSpecification Parameter
Brand and SeriesSchneider Acti9 iPRD40 Series
Product TypeType 2 modular surge arrester (with pluggable trip unit)
Pole Configuration3ف + ن (three-phase + neutral)
الجهد المقنن (Uc)350الخامس و (suitable for domestic 400V three-phase systems)
Maximum Discharge Current (Imax)40ال (8/20μs waveform)
فئة الحمايةType 2 (secondary surge protection for power distribution systems)
Technical PrincipleCombined technology of MOV (Metal Oxide Varistor) + GDT (Gas Discharge Tube)
Applicable Earthing SystemTN-S, TT systems (not applicable to TN-C, IT systems)
  1. Detailed Technical Parameter Table
Parameter CategorySpecific ValueRemarks
المعلمات الكهربائية
تصنيف جهد التشغيل350الخامس و50/60هرتز
Maximum Discharge Current40ال (8/20μs)Core indicator of surge protection
Nominal Discharge Current20ال (8/20μs)
Voltage Protection Level (Up)≤ 1.5kVMeasured at In=10kA
Response Time≤ 25nsMOV+GDT combined technology ensures fast response
Mechanical and Installation Parameters
Module Width4 modules (72مم)Suitable for 35mm DIN standard rail
أبعاد85مم (H) × 72mm (W) × 69mm (د)
TerminalSuitable for 2.5~35mm² copper conductorsRecommended torque: 8~10N·m
فئة الحمايةIP20Suitable for installation inside power distribution cabinets
Environmental and Service Life Parameters
درجة حرارة التشغيل-25°C ~ +60°C
درجة حرارة التخزين-40°C ~ +85°C
عمر الخدمة الميكانيكية≥ 10,000 مرات (plug-in operation)
عمر الخدمة الكهربائيةComplies with IEC 61643-11 معيارThe pluggable module can be replaced when surge protection components age
Certification and Standards
Compliant Standardsاللجنة الانتخابية المستقلة 61643-11, GB 18802.1Certified with CE and CCC
  1. Core Functions and Working Principle
  2. Surge Suppression Mechanism: Adopts MOV+GDT hybrid technology. MOV is responsible for fast response (≤25ns) to suppress most surges, while GDT provides higher surge withstand capacity and lower leakage current.
  3. Fault Indication Function: The pluggable module is equipped with a visual status indicator (green = normal, red = fault) for quick identification of protection status.
  4. Thermal Trip Protection: Built-in thermal trip device automatically trips when surge energy is excessive or components age, preventing overheating damage to the arrester.
  5. Replaceable Design: Only the pluggable trip module needs to be replaced after a fault, eliminating the need for overall replacement and reducing maintenance costs.
  6. سيناريوهات التطبيق النموذجية
Application FieldSpecific Application ScenarioProtection Target
Commercial BuildingsMain/distribution power cabinets in office buildings, shopping malls, hotelsProtect critical loads such as air conditioners, elevators, and lighting systems
Industrial PlantsProduction line control circuits, PLC systems, front-end of frequency convertersPrevent damage to precision electronic equipment caused by lightning strikes or grid fluctuations
Data CentersUPS input/output terminals, front-end of server cabinet PDUsEnsure continuous and stable operation of IT equipment and avoid data loss
InfrastructureCritical power distribution circuits in hospitals and transportation hubsProtect life-safety related equipment and control systems
Photovoltaic SystemsAC side output terminals of invertersSuppress surges generated by photovoltaic systems and grid feedback surges
  1. Installation and Operation Precautions
  2. موقع التثبيت:

As Type 2 حماية, it should be installed in the main or distribution power cabinet, after the main circuit breaker.

Recommended to be installed close to the protected equipment, with the line length not exceeding 10 متر.

  1. متطلبات الأسلاك:

Phase lines (L1/L2/L3) and neutral line (ن) must be wired correctly according to the markings.

The protective earthing (بي) wire should be as short and thick as possible. It is recommended to use ≥16mm² copper conductors with a length not exceeding 50cm.

All terminals must be tightened to the recommended torque (8~10N·m) to prevent overheating due to poor contact.

  1. Matching Requirements:

A 16A~32A miniature circuit breaker or fuse must be installed upstream as overcurrent protection to prevent short circuits caused by surge arrester faults.

Not applicable to IT and TN-C earthing systems, only suitable for TN-S and TT systems.

  1. Maintenance Points:

Regularly check the status indicator (green = normal, red = fault).

Replace the pluggable trip module in a timely manner after a fault; do not perform plug-in operations with power on.

It is recommended to conduct a surge protection performance test every 2 سنين.

  1. Reference of Related Models in the Same Series
Modelرقم القطبMaximum Discharge Currentالجهد المقننApplication Scenario
A9L402001ف + ن40ال350الخامسType 2 surge protection for single-phase power distribution systems
A9L404002ف + ن40ال350الخامسTwo-phase power distribution systems (على سبيل المثال, lighting systems)
A9L406003ف + ن40ال350الخامسThree-phase power distribution systems (mainstream model)
A9L156003ف + ن15ال350الخامسPlaces with low surge risk

 

السابق:

ترك الرد

ترك رسالة