ABB XT2N160 TMA 160 3p F F
رقم الطلب: 1SDA061805R1 (1SDA067020R1)
Full Model: XT2N 160 TMA 160-1600 3p F F
مسلسل: ABB Tmax XT Series Molded Case Circuit Breaker
- Core Parameters Summary
| فئة المعلمة | المواصفات التفصيلية | ملحوظات |
| المعلومات الأساسية | • Frame size: XT2 | For low-voltage power distribution in industry and buildings |
| • Frame current: 160أ | ||
| • Rated current In: 160أ | ||
| • Poles: 3ص | ||
| • Breaking capacity: اكتب ن (36كا @ 415 فولت و) | ||
| • Rated operating voltage Ue: 690الخامس و, 500V DC | ||
| • Standards: اللجنة الانتخابية المستقلة 60947-2, GB 14048.2 | ||
| Trip System | • Trip type: TMA thermal-magnetic (الزائد + حماية ماس كهربائى) | Not suitable for earth fault protection; additional accessories required |
| • Overload protection (و): قابل للتعديل, 160أ | ||
| • Short-circuit protection (I3): قابل للتعديل, 800~1600A | ||
| • Instantaneous short-circuit protection: Fixed at 10In (1600أ) | ||
| • Protection curve: يتوافق مع اللجنة الانتخابية المستقلة 60947-2 | ||
| Mounting & Connection | • Mounting type: مُثَبَّت (ف) | Standard DIN rail or screw mounting |
| • Connection: Front connection (ف) | ||
| • Operation: Direct handle operation | ||
| • Dimensions: 90mm×130mm×82.5mm | ||
| • Weight: تقريبا. 1.574كجم | ||
| • Protection degree: IP20 | ||
| الخصائص الكهربائية | • Rated insulation voltage Ui: 800V | Suitable for AC-1, AC-2, ايه سي-3, AC-4 duties |
| • Rated impulse withstand voltage Uimp: 8كيلو فولت | ||
| • Rated short-time withstand current Icw: 16كا / 1 ثانية | ||
| • Rated frequency: 50/60هرتز | ||
| • Wiring capacity: الأعلى. 95mm² copper, الأعلى. 70mm² aluminum |
- Detailed Protection Characteristics
2.1 حماية الزائد (Thermal)
مميزة: Inverse time curve per IEC 60947-2
Adjustable range: 160أ (fixed)
Trip time:
1.05في: No trip for long duration
1.3في: Trip within ≤1 hour
6في: Trip within 2~10 seconds
2.2 Short-Circuit Protection (Magnetic)
Instantaneous trip: 800~1600A adjustable (I3)
Short-time delay: Not available (TMA has no short-time delay; TMD or electronic trip required)
Instantaneous short-circuit protection: Fixed at 10In (1600أ), non-adjustable
- Mounting Dimensions & Physical Characteristics
| Dimension | قيمة | Unit |
| Width | 90 | مم |
| Height | 130 | مم |
| Depth | 82.5 | مم |
| Mounting hole spacing | 75 | مم |
| Terminal spacing | معيار | مم |
| وزن | 1.574 | كجم |
| Package size | 145*130*208 | مم |
| Package weight | 1.2 | كجم |
Mounting Requirements:
35mm standard DIN rail (في 60715) مُستَحسَن
Ambient temperature: -25°C ~ +70°C
ارتفاع: ≤2000m (derating required above)
حماية: IP20 (front); must be installed in enclosure with IP30 or higher
- Replacement & Extended Models in the Same Series
4.1 Direct Replacement Models
| نموذج | اختلاف | Application |
| XT2N160 TMA 160 3P F F | Identical specifications | Direct replacement, no modification needed |
| XT2N160 TMA 160 3P P F | Plug-in mounting (ص) | Frequent replacement or maintenance |
| XT2N160 TMA 160 3P F W | Rear connection (دبليو) | Limited cabinet space |
4.2 Function-Extended Models
| نموذج | Functional Upgrade | Order No. |
| XT2N160 Ekip LSI 160 3P F F | Electronic trip, LSI protection | 1SDA067071R1 |
| XT2N160 Ekip LSIG 160 3P F F | Electronic trip, LSIG protection (including earth fault) | 1SDA067072R1 |
| XT2N160 TMD 160 3P F F | Thermal-magnetic with short-time delay | 1SDA067035R1 |
4.3 Pole-Extended Models
4P version: XT2N160 TMA 160 4p F F (رقم الطلب: 1SDA061806R1 / 1SDA067041R1)
Neutral pole rated current: 50% or 100% of phase current optional
4.4 Cross-Brand Reference
شنايدر: NSX160N TMD160 3P F
سيمنز: 3VT8116-1AA03-0AA0
شينت: NM1-160S/3300 160A
- Recommended Accessories
| Accessory Type | نموذج | وصف |
| Auxiliary contact | XT2-AS11 | 1لا + 1نورث كارولاينا, for status indication |
| Alarm contact | XT2-AL11 | 1لا + 1نورث كارولاينا, for fault alarm |
| Shunt trip | XT2-SHT | Remote tripping, التيار المتناوب/تيار مستمر 220 فولت |
| Undervoltage release | XT2-UVT | حماية الجهد المنخفض, AC 220V |
| Rotary handle | XT2-CR | Door-mounted operation, improved safety |
| Extended rotary handle | XT2-CRE | For deep panels |
| Terminal cover | XT2-TC | Protect terminals, prevent electric shock |
| Label holder | XT2-LB | For marking breaker parameters |
- Applications & Selection Notes
6.1 التطبيقات النموذجية
Industrial plants: Motor protection (≤160A), distribution feeder protection
Commercial buildings: التدفئة والتهوية وتكييف الهواء, إضاءة, pump control
بنية تحتية: Small substations, مراكز البيانات, PV systems
Others: معدات تصنيع المعدات الأصلية, agricultural machinery, marine systems
6.2 Selection Guide
| Requirement | مُستَحسَن | Not Recommended |
| Motor protection | ✓ (with proper setting) | المحركات الصغيرة (<10أ); use MCB instead |
| Distribution protection | ✓ (sub-circuits) | Main incomer (use XT3/XT4 series) |
| Earth fault protection | ✗ (needs accessories) | ✓ (choose Ekip LSIG) |
| Frequent operation | ✗ (MCCB not suitable) | ✓ (قواطع + relay) |
| Isolation function | ✓ (اللجنة الانتخابية المستقلة 60947-3) | – |
6.3 Selection Cautions
- Ensure rated current In matches load
- Breaking capacity must meet system short-circuit current (ن: 36kA @ 415V)
- Mounting (fixed/plug-in) and connection (front/rear) must match panel design
- Auxiliaries, shunt/undervoltage trips ordered separately
- Not for DC short-circuit protection (use DC-rated model)
- استكشاف الأخطاء وإصلاحها & Maintenance
7.1 الأخطاء الشائعة & الحلول
| Symptom | الأسباب المحتملة | الحلول |
| التعثر المتكرر | 1. الزائد | 1. Check load |
| 2. Short circuit | 2. Locate short circuit | |
| 3. Incorrect trip setting | 3. Reset settings | |
| 4. High ambient temperature | 4. Improve ventilation | |
| Cannot close | 1. No power to undervoltage trip | 1. Check control power |
| 2. Shunt trip not reset | 2. Reset shunt trip | |
| 3. Mechanism fault | 3. Contact ABB service | |
| 4. Line fault | 4. Clear fault | |
| No output after closing | 1. Main contacts damaged | 1. Inspect/replace contacts |
| 2. الأسلاك فضفاضة | 2. Tighten terminals | |
| 3. Trip unit fault | 3. Replace trip unit | |
| Aux contact no signal | 1. Auxiliary contact defective | 1. Replace auxiliary contact |
| 2. Wrong wiring | 2. Check wiring | |
| 3. Improper switching | 3. Adjust contact position |
7.2 Maintenance Recommendations
Inspection: كل 6 months – check wiring and mechanism
Cleaning: كل 12 months – remove dust to maintain insulation
Operation test: Once per year – 3~5 manual ON/OFF cycles
Trip test: Once every 2 years – simulate overload and short circuit
Service life: عادة 10 سنين, depending on duty and environment
- Ordering & Packaging
Standard package: 1 unit/box, including installation manual and certificate
MOQ: 1 unit
Warranty: 18 months from commissioning, or 24 months from delivery (whichever comes first)
Order code: 1SDA061805R1 (or 1SDA067020R1, varies by region)
Complete Model Guide for ABB Tmax XT2 Series (160A Frame)
Frame size: XT2 (160أ)
الجهد المقنن: 690الخامس و, 500V DC
البولنديين: 3ص / 4ص
Breaking classes: ن(36ال), س(50ال), ح(70ال), ل(100ال)
- Model Naming Convention
XT2 [Breaking Class] [Frame Current] [Trip Type] [النطاق الحالي] [البولنديين] [Mounting] [Connection]
Breaking class:
ن: 36kA @ 415V (معيار)
س: 50kA @ 415V (enhanced)
ح: 70kA @ 415V (high performance)
ل: 100kA @ 415V (ultimate)
Frame current: 160 (fixed)
Trip type:
TMA: الحرارية المغناطيسية (الزائد + instantaneous, no short-time delay)
TMD: الحرارية المغناطيسية (الزائد + short-time delay + instantaneous)
Ekip LSI: Electronic (الزائد + short-time delay + instantaneous)
Ekip LSIG: Electronic (الزائد + short-time delay + instantaneous + earth fault)
Ekip I: Electronic (instantaneous only)
النطاق الحالي: على سبيل المثال, 160-1600 (TMA 160A)
البولنديين: 3ص / 4ص
Mounting: ف (مُثَبَّت) / ص (البرنامج المساعد)
Connection: ف (Front) / دبليو (Rear)
- XT2 Series Model List (by Breaking Class)
2.1 Standard Breaking (ن, 36ال)
| Model Prefix | Trip Type | Typical Model | النطاق الحالي | Application |
| XT2N160 | TMA | XT2N160 TMA 160-1600 3P F F | 160أ | General distribution, motors |
| TMD | XT2N160 TMD 100-1000 4P F W | 100أ | Systems requiring short-time delay | |
| Ekip LSI | XT2N160 Ekip LSI R125 3P P F | 125أ | Electronic protection, المراقبة عن بعد | |
| Ekip LSIG | XT2N160 Ekip LSIG R80 4P F F | 80أ | Earth fault protection required |
Example Order No.: 1SDA061805R1 (XT2N160 TMA 160 3P F F)
2.2 Enhanced Breaking (س, 50ال)
| Model Prefix | Trip Type | Typical Model | النطاق الحالي | Application |
| XT2S160 | TMA | XT2S160 TMA 63-630 3P F F | 63أ | Industry, heavy-duty equipment |
| TMD | XT2S160 TMD 40-400 4P P W | 40أ | Frequently started motors | |
| Ekip LSI | XT2S160 Ekip C Dip LSI R100 3P F F | 100أ | Complex commercial distribution | |
| Ekip LSIG | XT2S160 Ekip LSIG R50 4P F F | 50أ | مراكز البيانات, medical facilities |
Example Order No.: 1SDA067021R1 (XT2S160 TMA 160 3P F F)
2.3 High Performance Breaking (ح, 70ال)
| Model Prefix | Trip Type | Typical Model | النطاق الحالي | Application |
| XT2H160 | TMA | XT2H160 TMA 32-320 3P F F | 32أ | Industrial systems with high short-circuit current |
| TMD | XT2H160 TMD 3.2-32 4P F F | 3.2أ | Precision equipment, control circuits | |
| Ekip LSI | XT2H160 Ekip Dip LSI R63 3P P F | 63أ | Generators, substations | |
| Ekip LSIG | XT2H160 Ekip LSIG R25 4P F F | 25أ | PV, renewable energy |
Example Order No.: 1SDA067587R1 (XT2H160 TMD 3.2-32 3P F F)
2.4 Ultimate Breaking (ل, 100ال)
| Model Prefix | Trip Type | Typical Model | النطاق الحالي | Application |
| XT2L160 | TMA | XT2L160 TMA 100-1000 4P F F | 100أ | Heavy industry with very high fault level |
| TMD | XT2L160 TMD 160-1600 3P F W | 160أ | Large motor control centers | |
| Ekip LSI | XT2L160 Ekip LSI R160 3P P F | 160أ | Metallurgy, chemical, hazardous areas | |
| Ekip LSIG | XT2L160 Ekip LSIG R125 4P F F | 125أ | Petrochemical, mining |
Example Order No.: 1SDA067667R1 (XT2L160 TMA 100-1000 4P F F)
- Trip Unit Comparison
| Trip Type | حماية | Adjustable Parameters | Typical Load | Price Level |
| TMA | الزائد + لحظية | و, I3 | المحركات, general distribution | اقتصاد |
| TMD | الزائد + Short-time + لحظية | و, ISD, tsd, I3 | Transformers, capacitors | واسطة |
| Ekip LSI | الزائد + Short-time + لحظية | Full range, communication | Critical distribution | Medium-High |
| Ekip LSIG | الزائد + Short-time + لحظية + Earth Fault | Full range, communication, logging | Sensitive loads, safety | عالي |
| Ekip I | Instantaneous only | I3 | Short-circuit intensive devices | اقتصاد |
- Special Models & Options
4.1 4P Neutral Configurations
معيار: Neutral = 50% مرحلة (general distribution)
Heavy: Neutral = 100% مرحلة (non-linear loads: VFD, يو بي إس)
Example: XT2N160 TMA 160 4P F F (100% neutral)
4.2 Plug-in Mounting (ص)
Fast replacement, suitable for critical equipment
Example: XT2S160 TMD 80 3P P F
4.3 Rear Connection (دبليو)
Saves cabinet space, compact panels
Example: XT2H160 Ekip LSI R63 3P F W
4.4 توافق الملحقات (Full Series)
| ملحق | نموذج | وصف |
| Auxiliary contact | XT2-AS11 | 1NO+1NC, status indication |
| Alarm contact | XT2-AL11 | 1NO+1NC, إنذار خطأ |
| Shunt trip | XT2-SHT | Remote tripping, التيار المتناوب/تيار مستمر 220 فولت |
| Undervoltage release | XT2-UVT | حماية الجهد المنخفض, AC 220V |
| Rotary handle | XT2-CR | Door operation, safety |
- Quick Selection Table
| Application | Recommended Class | Trip Type | البولنديين | Mount/Conn |
| General industrial | N/S | TMA/TMD | 3ص | F/F |
| Motor protection | N/S | TMA | 3ص | F/F |
| Commercial lighting | ن | TMA | 3ف/4ف | F/F |
| Data center | H/L | Ekip LSIG | 4ص | F/W |
| PV system | H/L | Ekip LSIG | 4ص | F/F |
| Frequent maintenance | Any | Any | 3ف/4ف | P/F |
- Replacement & Upgrade Path
6.1 Same-Frame Upgrade
كسر القدرة: XT2N → XT2S → XT2H → XT2L (dimensions unchanged)
Trip unit: TMA → TMD → Ekip LSI → Ekip LSIG
Mount/connection: F/F → P/F or F/W
6.2 Cross-Frame Upgrade
XT2 (160أ) → XT3 (250أ) → XT4 (250A enhanced) → XT5 (630أ)
Note dimension and parameter changes
All XT2 series models comply with IEC 60947-2 و غيغابايت 14048.2.
Fixed dimensions: 90mm × 130mm × 82.5mm for easy system expansion and maintenance.