Carlo Gavazzi DPA51CM44

Three-Phase Phase Sequence & Phase Loss Monitoring Relay The DPA51CM44 is a three‑phase power monitoring relay from the DPA51 series manufactured by Carlo Gavazzi, specifically designed to detect phase sequence errors and phase loss faults in three‑phase power supplies, protecting motors and other three‑phase equipment from damage. Model Code Explanation Part of Model Description DPA ...

  • تفاصيل المنتج

Three-Phase Phase Sequence & Phase Loss Monitoring Relay

The DPA51CM44 is a three‑phase power monitoring relay from the DPA51 series manufactured by Carlo Gavazzi, specifically designed to detect phase sequence errors and phase loss faults in three‑phase power supplies, protecting motors and other three‑phase equipment from damage.

  1. Model Code Explanation
Part of Modelوصف
DPAسلسلة المنتجات (three‑phase monitoring relay)
51Product type (تسلسل المرحلة & phase loss monitoring)
جFunction type (standard version, monitors phase sequence and phase loss)
M44Supply and output specification (208–480 VAC, SPDT output)
  1. Key Technical Specifications
المعلمةمواصفة
وظيفةThree‑phase phase sequence monitoring, phase loss monitoring
Supply Voltage208–480 VAC (±15%), self‑powered from the monitored supply
Measuring Range177–550 VAC (phase‑to‑phase)
نطاق التردد50/60 هرتز (±5%)
الإخراج1 SPDT relay, 5 أ / 250 بطالة, energized in normal condition
Regenerative Voltage DetectionDetects regenerative voltage up to 85% من الجهد المقنن
تصاعدتركيب السكك الحديدية DIN (compliant with DIN/EN 50022)
أبعاد17.5 × 81 × 67.2 مم (ultra‑slim design)
فئة الحمايةIP20
درجة حرارة التشغيل-25 °C to +55 درجة مئوية
درجة حرارة التخزين-40 °C to +85 درجة مئوية
  1. Operating Principle & سمات
  2. Operating Principle

Monitors the phase relationship of the three‑phase supply. When all three phases are present and the phase sequence is correct, the relay remains energized. If phase loss or incorrect phase sequence occurs, the relay de‑energizes immediately to trigger protection.

  1. الميزات الرئيسية

True RMS measurement ensures accurate detection even under non‑sinusoidal conditions

Regenerative voltage detection enables phase loss detection even when motor is rotating

مدمج 17.5 mm width saves control cabinet space

LED status indicator for quick fault diagnosis

No external power supply required; powered directly from the monitored three‑phase lines

  1. التطبيقات

Suitable for all types of equipment and systems requiring three‑phase power protection, مشتمل:

Motor control circuits (prevents reverse rotation and phase‑loss burnout)

Elevators and lifting equipment

Air conditioning and refrigeration systems

Pumps and fan systems

Industrial automation production lines

Any electrical equipment requiring three‑phase power monitoring

  1. تثبيت & الأسلاك
  2. تثبيت

Mount on standard 35 مم DIN السكك الحديدية

Ensure adequate ventilation; avoid installation near heat sources

  1. الأسلاك

Connect L1, L2, L3 to the three‑phase power supply

Connect NO (مفتوح عادة), نورث كارولاينا (Normally Closed), COM (Common) to the control circuit

  1. استبدال & Extended Models
استبدال / Extended ModelFunctional Difference
DPA51CM48208–480 VAC, 2 SPDT outputs
DPA51CM54480–690 VAC, 1 SPDT output
DPA51CM58480–690 VAC, 2 SPDT outputs
DPA71 SeriesSimilar to DPA51, 35.5 عرض ملم, extended functions
Chinese Brand EquivalentsGOLDAIR DPA51 series, Shanghai Fuji Electric DPA51CM44, إلخ.
  1. طلب المعلومات
ManufacturerCarlo Gavazzi
نموذجDPA51CM44
Standard Pack1 unit / box

Operating Principle of DPA51CM44

The DPA51CM44 is a self‑powered three‑phase phase sequence & phase loss monitoring relay. Its core function is to continuously monitor voltages on L1/L2/L3, determine whether phase loss has occurred and whether phase sequence is correct, and output a protection signal via the internal relay.

  1. Power Supply Method

It does not require a separate external control power supply; it operates directly from the monitored three‑phase supply L1, L2, L3.

  1. Detection Logic

Internal circuitry continuously monitors between the three phases:

Presence of voltage (phase loss detection)

Correct 120° phase difference sequence (phase sequence detection)

  1. أوضاع التشغيل
  2. Normal Condition (all three phases present + correct phase sequence)

Internal detection circuit confirms normal condition → output relay energizes

→ NO contact closes, NC contact opens, equipment runs normally.

  1. Single‑phase or two‑phase loss

Voltage loss detected → relay immediately de‑energizes

→ control circuit is interrupted, providing protection.

  1. Reversed phase sequence (incorrect L1/L2/L3 order)

Abnormal phase relationship → relay de‑energizes

→ protection is triggered to prevent motor reverse rotation.

  1. Additional Features

True RMS measurement ensures accurate judgment under harmonic and non‑sinusoidal conditions.

Built‑in regenerative voltage detection identifies back EMF from motor inertia to avoid misoperation.

LED indicator: ON in normal condition, OFF in fault condition for on‑site troubleshooting.

The DPA51CM44 is a three‑phase phase sequence and phase loss protection relay suitable for 208-480 بطالة. It can be used in any application using three‑phase AC power where reverse rotation or phase‑loss burnout must be avoided. Typical applications include:

  1. Motor Equipment (الأكثر شيوعًا)

المشجعين, مضخات المياه, مضخات النفط, circulation pumps

ضواغط الهواء, vacuum pumps, الضواغط

Machine tool spindle motors, conveyor motors

Prevents winding burnout due to phase loss and motor reverse rotation caused by reversed phase sequence.

  1. التدفئة والتهوية وتكييف الهواء & Refrigeration Equipment

Central air conditioning units, water chillers

Cooling tower fans, air‑source heat pumps

Industrial refrigeration units

Prevents damage to compressors and fans from reversed phase sequence.

  1. Lifting & Lifting Equipment

Elevators, freight elevators, lifting platforms

Cranes, winches, hoists

Reversed phase sequence causes immediate reverse operation, creating severe safety hazards, so monitoring is essential.

  1. Water Supply, Drainage & Fire Protection Systems

Fire pumps, sprinkler pumps, sewage pumps

Booster pumps, industrial circulation water systems

Ensures pumps do not reverse and shuts down promptly on phase loss.

  1. خطوط الإنتاج الآلي & Equipment

Belt conveyors, roller lines, assembly lines

ماكينات التعبئة والتغليف, food machinery, textile machinery

Injection molding machines, extruders, die‑casting machines

Maintains stable three‑phase power and avoids unexpected line stoppages or damage.

  1. بناء & Power Distribution Projects

Temporary three‑phase power on construction sites

Power monitoring in distribution cabinets and power boxes

Power distribution circuits in shopping malls and factories

Quickly detects abnormal incoming three‑phase power to prevent collective failure of downstream equipment.

Almost all electromechanical equipment powered by approximately three‑phase 380 V that must not reverse or run under phase loss can use the DPA51CM44 for power protection.

Carlo Gavazzi DPA Series Three‑Phase Monitoring Relay Model List

The Carlo Gavazzi DPA series focuses on three‑phase phase sequence and phase loss monitoring, with some models offering extended functions. Below is a complete list sorted by sub‑series, including key parameters and feature descriptions.

  1. Model Naming Convention
Partوصف
DPAرمز السلسلة (three‑phase phase sequence / phase loss monitoring)
العشرينSub‑series number (01, 51, 52, 55, 71, إلخ.)
ج/دFunction type (C = standard, D = special)
MXXSupply & output specification
M44 = 208–480 VAC, 1 SPDT
M48 = 208–480 VAC, 2 SPDT
M54 = 480–690 VAC, 1 SPDT
M58 = 480–690 VAC, 2 SPDT
M23 = 24 VDC, 1 SPDT
التدفئة والتهوية وتكييف الهواءSpecial version for A2L/A3 flammable refrigerant systems
  1. Complete Model List by Sub‑Series

2.1 DPA01 / PPA01 Series (wide voltage range, including plug‑in PPA01)

نموذجSupply Voltageالإخراجتصاعدسمات
DPA01CM44208–480 VAC1 SPDTDIN railمعيار, تسلسل المرحلة + خسارة المرحلة
DPA01CM60208–600 VAC1 SPDTDIN railWide voltage range
DPA01CM69208–690 VAC1 SPDTDIN railUltra‑wide voltage range
DPA01DM2324 VDC1 SPDTDIN railDC supply version
DPA01DM48208–480 VAC2 SPDTDIN railDual output
PPA01CM44208–480 VAC1 SPDTPlug‑inمعيار, plug‑in mounting
PPA01CM48208–480 VAC2 SPDTPlug‑inDual output
PPA01DM48208–480 VAC2 SPDTPlug‑inDual output special version

2.2 DPA51 / DPA71 Series (مدمج, 17.5 عرض ملم)

نموذجSupply Voltageالإخراجتصاعدسمات
DPA51CM44208–480 VAC1 SPDTDIN railمعيار, ultra‑slim 17.5 مم
DPA51CM44HVAC208–480 VAC1 SPDTDIN railFor flammable refrigerant HVAC systems
DPA51CM48208–480 VAC2 SPDTDIN railDual output
DPA51CM54480–690 VAC1 SPDTDIN railHigh‑voltage version
DPA51CM58480–690 VAC2 SPDTDIN railHigh‑voltage dual output
DPA71CM44208–480 VAC1 SPDTDIN rail35.5 عرض ملم, extended functions
DPA71CM48208–480 VAC2 SPDTDIN rail35.5 عرض ملم, dual output

2.3 DPA52 Series (switching power supply, wide input range)

نموذجSupply Voltageالإخراجتصاعدسمات
DPA52CM44125–624 VAC1 SPDTDIN railSwitching power supply, wide input
DPA52CM44HVAC125–624 VAC1 SPDTDIN railFor flammable refrigerant HVAC
DPA52CM48125–624 VAC2 SPDTDIN railDual output
DPA52CM54480–690 VAC1 SPDTDIN railHigh‑voltage version
DPA52CM58480–690 VAC2 SPDTDIN railHigh‑voltage dual output

2.4 DPA55 Series (with voltage monitoring)

نموذجSupply Voltageالإخراجتصاعدسمات
DPA55CM44208–480 VAC1 SPDTDIN railPhase sequence + خسارة المرحلة + voltage monitoring (±10% / ±15%)
DPA55CM48208–480 VAC2 SPDTDIN railDual output with voltage monitoring
DPA55CM54480–690 VAC1 SPDTDIN railHigh‑voltage with voltage monitoring
DPA55CM58480–690 VAC2 SPDTDIN railHigh‑voltage dual output with voltage monitoring

2.5 Other DPA Series Models

نموذجمسلسلسمات
DPA03CM44DPA03Three‑phase phase sequence / خسارة المرحلة, extended functions
DPA03CM48DPA03Dual output, extended functions
DPA03CM69DPA03Ultra‑wide voltage range, extended functions
  1. Key Feature Comparison
مسلسلWidthمزود الطاقةالوظيفة الأساسيةSuitable Voltage
DPA5117.5 ممSelf‑powered (monitored supply)Phase sequence + خسارة المرحلة208–480 VAC
DPA7135.5 ممSelf‑powered (monitored supply)Phase sequence + خسارة المرحلة208–480 VAC
DPA0135.5 ممSelf‑powered (monitored supply)Phase sequence + خسارة المرحلة208–690 VAC
DPA5235.5 ممSwitching power supplyPhase sequence + خسارة المرحلة125–624 VAC
DPA5535.5 ممSelf‑powered (monitored supply)Phase sequence + خسارة المرحلة + voltage monitoring208–690 VAC
  1. دليل الاختيار
  2. Space requirement: Choose DPA51 (17.5 مم) to save control cabinet space
  3. Voltage range:

208-480 بطالة: select models with suffix CM44 / CM48

480-690 بطالة: select models with suffix CM54 / CM58

Ultra‑wide range: select CM60 / CM69 from DPA01 series

  1. Output requirement:

Single control loop: 1 SPDT (CM44 / CM54)

Dual control loops: 2 SPDT (CM48 / CM58)

  1. Special applications:

Flammable refrigerant HVAC systems: select models marked HVAC

Voltage monitoring required: select DPA55 series

السابق:

التالي:

ترك الرد