Codeمعنى
NM1Chint NM1 series molded case circuit breaker
800Frame current 800A
حHigh breaking capacity grade (Grade H, typically 50kA at 400V AC)
33003 أقطاب, combined tripper (thermomagnetic tripping), no accessories
800أRated current 800A

  • تفاصيل المنتج

Chint NM1-800H/3300-800A is a 3-pole, 800أ قاطع دائرة الحالة المصبوب (مكب) of the NM1 series, featuring H-grade breaking capacity and thermomagnetic tripping. It is designed for overload and short-circuit protection of power distribution lines, and suitable for industrial and large commercial power distribution trunk lines.

Codeمعنى
NM1Chint NM1 series molded case circuit breaker
800Frame current 800A
حHigh breaking capacity grade (Grade H, typically 50kA at 400V AC)
33003 أقطاب, combined tripper (thermomagnetic tripping), no accessories
800أRated current 800A

المعلمات الأساسية

المعلمةقيمة
Rated operating voltageAC 690V, 50هرتز
تصنيف الجهد العزل800V
التصنيف الحالي800أ
كسر القدرةGrade H: 50ال (400الخامس و)
Pole number
Tripper typeThermomagnetic (overload long-time delay + short-circuit instantaneous protection)
Mounting methodFixed type, vertical/horizontal mounting available
Wiring methodFront wiring (rear wiring and plug-in type optional)
Operation methodDirect handle operation
Executive standardGB 14048.2, اللجنة الانتخابية المستقلة 60947-2, شهادة سي سي سي

سيناريوهات التطبيق

Overload and short-circuit protection for industrial power distribution trunks and power circuits in large workshops.

Protection for power distribution main trunks in commercial buildings (shopping malls, مباني المكاتب).

Protection for large motor circuits with infrequent starting.

نقاط التثبيت والتشغيل الرئيسية

  1. Installation shall comply with specifications; both vertical and horizontal mounting are acceptable, with secure fastening and good heat dissipation ensured.
  2. Check the specification of wiring terminals before wiring to match cables/bus bars for 800A current.
  3. Regularly inspect the action accuracy of the tripper to avoid the impact of ambient temperature on protection performance.

Cross-brand Replacement Reference

شنايدر: NSX 800N/3P 800A (Verify breaking capacity and tripping curve).

ايه بي بي: Tmax T6N 800/3P 800A (Pay attention to mounting dimensions and accessory compatibility).

The core difference between Chint NM1-800H/3300-800A and NM1-800H/3200-800A lies in the tripper type and protection function; other basic parameters (frame current, كسر القدرة, رقم القطب, إلخ.) are completely consistent.

  1. Core Difference: Meaning of “3300” و “3200” in the Model
Model PartDigital Meaningوظيفة الحماية
33001st digit 3 = 3 أقطاب; 2nd digit 3 = combined tripper (thermomagnetic tripping); last two digits 00 = no accessoriesOverload long-time delay protection + short-circuit instantaneous protection
32001st digit 3 = 3 أقطاب; 2nd digit 2 = magnetic tripper (magnetic tripping only); last two digits 00 = no accessoriesShort-circuit instantaneous protection only, no overload protection

This is the fundamental difference between the two circuit breakers, which directly determines their application scenarios and protection capabilities.

  1. Complete Parameter Comparison Table
المعلمةNM1-800H/3300-800ANM1-800H/3200-800Aملاحظات
Tripper typeThermomagnetic combined trippingMagnetic trippingCore difference
حماية الزائد Available (long-time delay)Unavailableال 3300 model achieves overload delay protection through the thermal bending of bimetallic strips
حماية ماس كهربائىAvailable (instantaneous)Available (instantaneous)Both realize short-circuit instantaneous tripping through electromagnetic coils
Frame current800أ800أConsistent
التصنيف الحالي800أ800أConsistent
كسر القدرةGrade H (50kA@400V AC)Grade H (50kA@400V AC)Consistent
Pole numberConsistent
الجهد المقننAC 690V, 50هرتزAC 690V, 50هرتزConsistent
تصنيف الجهد العزل800V800VConsistent
Mounting methodFixed type (vertical/horizontal)Fixed type (vertical/horizontal)Consistent
Wiring methodFront wiring (rear wiring, plug-in type optional)Front wiring (rear wiring, plug-in type optional)Consistent
Executive standardGB 14048.2, اللجنة الانتخابية المستقلة 60947-2GB 14048.2, اللجنة الانتخابية المستقلة 60947-2Consistent

ثالثا. Application Scenario Differences

نموذجالسيناريوهات القابلة للتطبيقInapplicable Scenarios
3300• Industrial/commercial power distribution trunks (requiring both overload and short-circuit protection)• Special occasions requiring only short-circuit protection
• Large motor circuits (infrequent starting)• Dedicated circuits for fire-fighting equipment (3300 model with shunt trip is usually required for fire-fighting equipment)
• General lighting and power hybrid distribution systems
3200• Used as an isolating switch (needing short-circuit protection but no overload protection)• Used alone as power distribution line protection (lack of overload protection will cause line overheating and damage)
• Occasions matched with other overload protection devices (على سبيل المثال, المرحلات الحرارية الزائدة)• Direct protection for motors (unable to prevent motor burnout due to overload)
• Special short-circuit protection for specific industrial equipment
  1. اقتراحات الاختيار
  2. Prioritize the 3300 model: Most power distribution scenarios require both overload and short-circuit protection; ال 3300 model provides more comprehensive protection to avoid line overheating, equipment damage and other problems caused by overload.
  3. Select the 3200 model only under specific conditions: When the system is already equipped with other overload protection devices (على سبيل المثال, المرحلات الحرارية الزائدة, overload alarms), ال 3200 model can be used as a dedicated short-circuit protection circuit breaker to reduce costs.
  4. ملحوظة: ال 3200 model cannot be used alone for power distribution lines requiring overload protection due to the lack of overload protection, otherwise potential safety hazards may be caused.