CHINT NBHLE-40Y-1PC32 is a 1P+N two-pole residual current circuit breaker (RCCB) specially designed for household and small-to-medium engineering applications. It integrates overload, short-circuit, and leakage protection functions, suitable for AC 50Hz/60Hz circuits with a rated voltage of 230V. Below is its core information and application guidelines:
- Core Technical Parameters
- تصنيف الخصائص الحالية والرحلة
التصنيف الحالي: 32أ, suitable for conventional loads such as lighting, مآخذ, and small air conditioners, supporting up to approximately 7kW single-phase devices (على سبيل المثال, instantaneous water heaters).
Default Type C trip characteristic (instantaneous trip at 5-10 times rated current), ideal for resistive loads (على سبيل المثال, مصابيح, electric heaters); for inductive loads like motors, النوع د (instantaneous trip at 10-14 مرات) is available.
- Leakage Protection and Breaking Capacity
30mA leakage action current, rapidly cutting off faulty circuits within 0.1 ثواني, متوافق مع IEC 61009-1 and GB/T 16917.1 standards to prevent electric shock and fire risks.
كسر القدرة: 6ال, capable of handling common household short-circuit currents (typically 2-4kA) to ensure safe power disconnection.
- Electrical Performance and Certifications
– الجهد المقنن: 230V, operating temperature range: -5°C to +70°C, IP20 protection grade, resistant to moisture and dust.
– Certified by CCC and compliant with CE standards, ensuring reliable quality.
- سيناريوهات التطبيق النموذجية
- Household Power Distribution Systems
Branch Circuit Protection: Socket circuits in humid areas like kitchens and bathrooms to prevent safety accidents from leakage. على سبيل المثال, electric water heaters (3-8KW) can directly use a 32A circuit breaker with 30mA leakage protection for dual-layer safety.
Whole-House Leakage Protection: If the distribution box lacks a main RCCB, NBHLE-40Y-1PC32 can serve as the main switch to monitor leakage across all circuits.
- Commercial and Light Industrial Use
Small Office Equipment: Centralized power supply circuits for printers, projectors, water dispensers, إلخ., to avoid overload and leakage risks.
Store Lighting Systems: LED strips and display cabinet circuits in clothing stores, cafes, إلخ., providing stable protection.
- New Energy Equipment Adaptation
AC Charging Pile Protection: A 7kW charging pile (32أ) can directly use this circuit breaker as the main switch, paired with NXB series circuit breakers for hierarchical control.
PV Inverter Branch: Protection for the AC side of small household PV systems to prevent damage from backflow current.
ثالثا. Installation and Selection Recommendations
- Installation Specifications
تركيب السكك الحديدية: Compatible with TH35-7.5mm standard rails, wiring terminals support 2.5-10mm² conductors, and vertical installation is required for optimal heat dissipation.
المتطلبات البيئية: Avoid installation in high-temperature (>70°C), high-humidity, or flammable environments; distribution boxes must have reserved heat dissipation space (≥30cm from the wall).
- Selection Logic
Load Matching: Equipment total power (W) ÷ voltage (230V) = current (أ). The circuit breaker’s rated current should be ≥1.2 times the calculated value. على سبيل المثال, a 6kW load corresponds to 26.1A, making a 32A circuit breaker compliant.
Leakage Protection Hierarchy: If the main switch already has an RCCB, use ordinary circuit breakers (على سبيل المثال, NXB63-2P/32A) for branches; if not, prioritize NBHLE series for whole-house protection.
- Accessory Expansion
Auxiliary Functions: Can be paired with AX-X1 auxiliary contacts (indicate on/off status), AL-X1 alarm contacts (trigger signals during faults), or shunt trip coils (remote tripping control).
System Compatibility: Compatible with NXB series circuit breakers, rail sockets, and surge protectors (على سبيل المثال, NXU) to build modular power distribution systems.
- Maintenance and Safety Tips
- عمليات التفتيش المنتظمة
Monthly Testing: Press the test button (امتحان) to verify the leakage protection function. Replace immediately if it fails to trip.
Annual Check: Use an infrared thermometer to detect contact temperatures (≤60°C) and prevent increased contact resistance due to oxidation.
- استكشاف الأخطاء وإصلاحها
التعثر المتكرر: If overload or short circuit is ruled out, aging insulation may be the cause, requiring professional electrical inspection.
Leakage Indicator Protrusion: Indicates a past leakage fault; identify and fix the cause before resetting.
- Pricing and Purchase Channels
سعر السوق: Reference price per unit is approximately 150-200 CNY (subject to local dealers).
Purchase Advice: Procure through CHINT’s official channels (على سبيل المثال, Tmall flagship store, authorized dealers) to ensure product quality and after-sales service.
- Typical Configuration Schemes
| سيناريو | Circuit Breaker Configuration | Complementary Equipment | Cable Specification |
| Household Kitchen Branch | NBHLE-40Y-1PC32 (النوع ج) | Induction cooker, microwave, fridge | 4mm copper wire |
| 7kW Charging Pile Main | NBHLE-40Y-1PC32 (النوع ج) | NXB63-2P/32A branch circuit breaker | 6mm copper wire |
| Commercial Lighting | NBHLE-40Y-1PC32 (النوع ج) | LED strips, smart switches | 2.5mm copper wire |
| PV Inverter AC Side | NBHLE-40Y-1PC32 (النوع ج) | Self-resetting over/under voltage protector | 6mm copper wire |
With high reliability and flexible adaptability, CHINT NBHLE-40Y-1PC32 is the ideal choice for leakage protection in household and small-to-medium engineering projects. Users can select trip characteristics based on load types and strictly follow installation guidelines to ensure electrical safety.