ويشات: +86-13184948252 واتس اب: 0086-13811255435 بريد إلكتروني: كينت@bestcontactor.com

عن اتصال |

Delta DVP16SP11T Digital I/O Expansion Module - المقاولين,قاطع الدائرة,العاكس للطاقة الشمسية,عداد كهرباء,البطاريات الشمسية

عداد الكهرباء/كهربائي/

Delta DVP16SP11T Digital I/O Expansion Module

DVP16SP11T is a 16‑point slim digital mixed I/O expansion module of Delta DVP‑S series, configured as 8 من (Digital Input) + 8 يفعل (الإخراج الرقمي, NPN sinking transistor). It is specially designed for expanding I/O points of Delta DVP‑S series PLC main units, suitable for small automation systems with limited space, and supports high‑speed pulse ...

  • تفاصيل المنتج

DVP16SP11T is a 16‑point slim digital mixed I/O expansion module of Delta DVP‑S series, configured as 8 من (Digital Input) + 8 يفعل (الإخراج الرقمي, NPN sinking transistor).

It is specially designed for expanding I/O points of Delta DVP‑S series PLC main units, suitable for small automation systems with limited space, and supports high‑speed pulse output and counting functions.

  1. شرح النموذج & Basic Positioning
Part of Modelمعنى
DVPDelta PLC product series code
16Total I/O points: 16 نقاط (8 مدخل + 8 الإخراج)
SPMixed I/O type (S = Slim, P = Mixed input/output)
11Version code, النوع القياسي
TOutput type: Transistor output (NPN sinking)

تحديد موضع المنتج:

Compact I/O expansion module for DVP‑S series PLC, used to expand the digital control capability of the main unit.

Especially suitable for space‑limited applications such as small mechanical equipment, automated production lines, and building control systems.

It can be seamlessly connected with DVP‑S series main units (DVP12SA11T, DVP16SA11T, إلخ.).

  1. المعلمات التقنية الرئيسية
غرضمواصفة
Input Characteristics
Input points8 نقاط (من)
Input typeSinking / sourcing selectable (default sinking)
Rated input voltage24VDC (±10%)
Input current7mA per point (ON state)
Response time1آنسة (معيار), configurable to 0.1ms (high‑speed mode)
Input impedanceتقريبا. 3.3
Output Characteristics
Output points8 نقاط (يفعل)
Output typeTransistor (NPN sinking)
Rated output voltage24VDC (±10%)
Rated current per point0.5أ (continuous), 1أ (peak, 0.5ق)
الأعلى. total current4أ (all outputs active)
High‑speed pulse output2 points up to 10kHz (specific channels)
Electrical & Physical Characteristics
Power requirement24VDC, module power consumption approx. 80أماه
Insulation resistance≥100MΩ (500VDC)
Dielectric strength2kV AC (between input/output/power, 1 min)
درجة حرارة التشغيل0℃ ~ +55℃
Storage temperature-25درجه مئوية ~ +70 درجه مئوية
أبعاد25mm × 76mm × 102mm (تصميم نحيف, saves cabinet space)
تصاعد35mm standard DIN rail mounting
  1. سمات & Structural Advantages
  2. Ultra‑Slim Compact Design

Only 25mm wide, saves about 50% installation space compared with traditional modules, ideal for high‑density I/O control panels.

Gapless side‑by‑side assembly for maximum space utilization.

Clip‑on connection, no screws required, easy installation.

  1. Flexible I/O Configuration

8 مدخل + 8 output mixed design to meet I/O requirements of most small control systems.

Input supports sinking/sourcing switching, compatible with NPN/PNP sensors.

Fast transistor response (≤10μs), suitable for high‑frequency switching control.

  1. High‑Speed Control Capability

2 high‑speed pulse outputs up to 10kHz for simple positioning (على سبيل المثال, stepper motor drive).

4 high‑speed counter inputs up to 20kHz for speed measurement, part counting, إلخ.

Supports interrupt input for fast response to external emergency signals.

  1. Reliable Electrical Performance

Enhanced anti‑interference design, complies with industrial EMC standards (EN 61000‑6‑2 / EN 61000‑6‑4).

Output short‑circuit protection to prevent module damage.

Built‑in surge suppression circuit to protect output devices from back EMF of inductive loads.

  1. مجالات التطبيق
Fieldالتطبيقات النموذجيةAdvantages
Small MachineryPackaging machines, labeling machines, small machine toolsSlim size, high‑speed I/O for precise control
Automated Linesالناقلون, sorting systems, assembly stationsMixed I/O for various sensors & actuators
Building AutomationLighting control, access control, التدفئة والتهوية وتكييف الهواءLow power, suitable for long‑time operation
Smart AgricultureIrrigation, greenhouse control, feed processingStrong anti‑interference, adapts to harsh environments
New Energy EquipmentSmall PV inverters, energy storage systemsFast response, supports high‑frequency switching
  1. Comparison of Similar Modules in DVP‑S Series
نموذجI/O ConfigurationOutput Typeالميزات الرئيسيةطلب
DVP16SP11T8من + 8يفعلTransistor (NPN)16‑point mixed, high‑speed pulse outputFull control of small equipment
DVP16SP11R8من + 8يفعلتتابع16‑point mixed, AC/DC compatibleContactors, solenoids, inductive loads
DVP08SP11T4من + 4يفعلTransistor (NPN)8‑point mixed, smaller sizeMicro‑equipment control
DVP08SP11R4من + 4يفعلتتابع8‑point mixed, economicalSimple control circuits
DVP08SN11T0من + 8يفعلTransistor (NPN)Output only expansionAdditional output points only
DVP08SM11N8من + 0يفعلDigital InputInput only expansionAdditional input points only
  1. Connection & ملاحظات العملية
  2. System Connection

Connect to DVP‑S series main unit via left expansion port; up to 8 modules can be expanded.

Modules connected by dedicated expansion cable, no extra configuration needed.

الأعلى. I/O points after expansion: main unit points + expansion points (الأعلى. 128 نقاط).

  1. Wiring Rules

Input wiring: 24VDC supply, COM to 0V, signal terminal to sensor signal.

Output wiring: 24VDC supply, COM to +24V, signal terminal to load negative (sinking output).

4 outputs share one COM terminal; 2 COM groups (4 points each) for grouped control.

  1. High‑Speed Function Configuration

High‑speed pulse output: Y0/Y1 up to 10kHz for stepper or servo motors.

High‑speed counter: X0–X3 up to 20kHz, 1‑phase / 2‑phase configurable.

Configured via programming software (DVPSoft), no extra hardware required.

  1. Protection Measures

Surge suppressor on input side to resist external interference.

Freewheeling diode for inductive loads to protect transistors.

Avoid output short‑circuit; الأعلى. 0.5A continuous per output.

  1. اختيار & استبدال
  2. Selection Guidelines

Output type: Transistor for high‑frequency, low inductance; Relay for AC/DC, قوة عالية.

I/O points: Choose 8‑point or 16‑point based on controlled devices.

Space: Slim modules preferred for narrow control cabinets.

High‑speed functions: Select T‑type for pulse output or high‑speed counting.

  1. Replacement Options
RequirementRecommended ReplacementAdvantage
Relay output neededDVP16SP11RAC/DC load compatible, long contact life
Fewer I/O pointsDVP08SP11TSmaller size, تكلفة أقل
Higher pulse frequencyBuilt‑in high‑speed channels of DVP‑S main unit (up to 100kHz)Higher precision positioning
Cross‑series replacementDVP‑ES2 series expansion (DVP08SP11T‑ES2)Compatible with DVP‑ES2, richer functions
  1. Typical Application Examples
  2. Small Packaging Machine:

8 inputs (material position, product detection, safety door),

8 outputs (feeding motor, sealer, cutter, conveyor),

high‑speed pulse for feeding positioning.

  1. Automated Assembly Line:

Inputs (part position, fixture status),

Outputs (cylinders, المحركات, indicators),

high‑speed counting for production statistics.

  1. Building Lighting Control:

Inputs (motion sensor, light sensor, manual switch),

Outputs (lighting circuits, HVAC fans),

energy‑saving control.

Packing Specification: 1 pc/box, 10 pcs/carton

الاختلافات الأساسية: Delta DVP16SP11T vs. Similar Modules

At a Glance:

Delta DVP16SP11T features ultra‑slim 25mm width, cost‑effective, seamless compatibility with DVP‑S series.

سيمنز / ميتسوبيشي / Omron excel in industrial ecosystem and high‑end functions.

Xinje focuses on cost‑effective domestic replacement.

  1. Main Competitors & Basic Comparison
غرضDelta DVP16SP11TSiemens S7‑200 SMART EM AT02Mitsubishi FX5U‑16EYT/ESOmron CP1W‑16ETXinje XC3‑16EYT
PositioningDVP‑S slim mixed I/OS7‑200 SMART compact expansionFX5U/iQ‑F high‑performanceCP1H/CP1L general expansionXC3 domestic compact
I/O Config8من + 8يفعل16من + 16يفعل16من + 16يفعل16من + 16يفعل16من + 16يفعل
OutputTransistor NPN sinkingTransistor (sink/source selectable)Transistor (sink/source selectable)Transistor (sink/source selectable)Transistor sinking
Input Voltage24VDC (±10%)24VDC24VDC24VDC24VDC
Width25مم (thinnest)تقريبا. 30ممتقريبا. 28ممتقريبا. 27ممتقريبا. 26مم
Compatible CPUDVP‑S series onlyS7‑200 SMART onlyFX5U / FX3U seriesCP1H / CP1L / CP1EXC3 / XC2 series only
الأعلى. ExpansionUp to 8 modulesUp to 8 modulesUp to 16 modulesUp to 8 modulesUp to 7 modules
Package1 pc/box, 10 pcs/carton1 pc/box1 pc/box1 pc/box1 pc/box
  1. Key Functional & Performance Differences

2.1 High‑Speed Control (Core Difference)

غرضDelta DVP16SP11TSiemens EM AT02Mitsubishi FX5U‑16EYTOmron CP1W‑16ETXinje XC3‑16EYT
Pulse Output2 points @10kHz2 points @≈2kHz4 axes @200kHz (built‑in)4 points @100kHz2 points @10kHz
High‑Speed Counter4 points @20kHz6 points @100kHz6 points @200kHz4 points @200kHz4 points @10kHz
Input Response0.1آنسة (high‑speed)1آنسة0.2آنسة0.1آنسة0.5آنسة
StrengthBasic high‑speed, small positioningStable, low‑speed logicUltra‑high frequency, precision positioningStrong counting, high anti‑interferenceLowest cost, basic control

2.2 تثبيت & Wiring

غرضDelta DVP16SP11TSiemens EM AT02Mitsubishi FX5U‑16EYTOmron CP1W‑16ETXinje XC3‑16EYT
تصاعدClip‑on DIN rail, gaplessScrew + DIN railTerminal block, plug‑inDIN rail + screwClip‑on DIN rail
صالةSpring clamp, tool‑freeScrew terminalSpring clampScrew terminalSpring clamp
SpaceUltra‑compactStandard compactStandard compactStandard compactStandard compact

2.3 Software & تواصل

غرضDelta DVP16SP11TSiemens EM AT02Mitsubishi FX5U‑16EYTOmron CP1W‑16ETXinje XC3‑16EYT
SoftwareDVPSoft (easy to use)TIA Portal (powerful)GX Works3 (FX compatible)CX‑Programmer (stable)XCPPro (user‑friendly)
تواصلMODBUS RTU/TCP, يمكنفتحPROFINET, MODBUS TCPCC‑Link, إيثرنت/IP, MODBUSMODBUS RTU/TCP, HostLinkMODBUS RTU/TCP
EcosystemSeamless with Delta servo/HMIFull Siemens integrationPerfect with Mitsubishi servo/inverterHigh compatibility with Omron devicesGood with domestic equipment
DiagnosisأساسيComprehensiveDetailed, المراقبة عن بعدPrecise, fast fault locationأساسي
  1. Application‑Based Selection Suggestions
  2. Best for Delta DVP16SP11T

Extremely limited space: 25mm ultra‑slim for compact panels.

DVP‑S series system: Direct expansion without adaptation.

Cost‑effective + basic high‑speed: 10kHz pulse / 20kHz counter for small packaging, labeling, الناقلات.

Fast delivery: DVPSoft is easy to learn, short commissioning time for OEMs.

  1. Best for Siemens S7‑200 SMART EM AT02

Large/complex lines: PROFINET, full diagnosis, multi‑device coordination.

Siemens ecosystem: بلك, servo, HMI unified.

موثوقية عالية: Automotive, chemical, water treatment.

  1. Best for Mitsubishi FX5U‑16EYT/ES

Precision positioning: 200kHz pulse, multi‑axis interpolation for CNC, precision assembly.

Mid‑to‑high automation: Built‑in Ethernet, analog, CC‑Link.

Long‑term support: Mature FX ecosystem.

  1. Best for Omron CP1W‑16ET

Harsh environments: Strong anti‑interference, dust, electromagnetic noise.

Counting & inspection: High‑speed counting for packaging, sorting.

Omron sensor/HMI system.

  1. Best for Xinje XC3‑16EYT

Domestic replacement / tight budget: Lower cost than Delta.

Beginner development: XCPPro easy to use.

Domestic equipment matching: High cost‑performance.

  1. Cross‑Brand Replacement Notes
  2. I/O point match: Delta is 8DI+8DO; Siemens/Mitsubishi/Omron are 16DI+16DO per module. Adjust I/O layout.
  3. Output polarity: Delta is NPN sinking; others often support sink/source. Confirm COM wiring.
  4. High‑speed downgrade: If replacing from Mitsubishi/Siemens to Delta, reduce pulse/counter speed and reprogram.
  5. تواصل: Delta uses mainly MODBUS; Siemens/Mitsubishi support industrial Ethernet. Adjust protocol settings.

السابق:

ترك الرد

ترك رسالة