NM1-630S-3300-630A قاطع الدائرة المقولب - المقاولين,قاطع الدائرة,العاكس للطاقة الشمسية,عداد كهرباء,البطاريات الشمسية

قاطع الدائرة/

NM1-630S-3300-630A قاطع الدائرة المقولب

الجزء النموذجيوصف
NM1Product series code; CHINT Electric NM1 series molded case circuit breaker, suitable for power distribution protection and motor protection scenarios
630Frame size rated current; the maximum current rating that this series of circuit breakers can carry is 630A
سكسر فئة القدرة; Type S indicates standard breaking capacity, usually 35kA (refer to the product manual for details), suitable for conventional power distribution environments. Other classes in the same series include H (higher breaking capacity) and L (lower breaking capacity)
3300Pole number + trip unit type + accessory code
First two digits "33": 3-قاطع الدائرة القطبية, suitable for three-phase three-wire power distribution systems
Last two digits "00": no accessories (such as auxiliary contacts, undervoltage release, shunt release, إلخ.)
630أالتصنيف الحالي; the rated operating current set for this circuit breaker is 630A

  • تفاصيل المنتج
  1. تفسير النموذج
الجزء النموذجيوصف
NM1Product series code; CHINT Electric NM1 series molded case circuit breaker, suitable for power distribution protection and motor protection scenarios
630Frame size rated current; the maximum current rating that this series of circuit breakers can carry is 630A
سكسر فئة القدرة; Type S indicates standard breaking capacity, usually 35kA (refer to the product manual for details), suitable for conventional power distribution environments. Other classes in the same series include H (higher breaking capacity) and L (lower breaking capacity)
3300Pole number + trip unit type + accessory code
First two digits “33”: 3-قاطع الدائرة القطبية, suitable for three-phase three-wire power distribution systems
Last two digits “00”: no accessories (such as auxiliary contacts, undervoltage release, shunt release, إلخ.)
630أالتصنيف الحالي; the rated operating current set for this circuit breaker is 630A
  1. المعلمات التقنية الأساسية
فئة المعلمةSpecific Index
تصنيف جهد التشغيل (إي)Three-phase AC 400V (50هرتز), suitable for low-voltage power distribution systems
التصنيف الحالي (في)630أ
Frame Current (Iu)630أ
كسر القدرة (وحدة العناية المركزة)Class S: 35ال (at AC 400V)
Trip Unit TypeThermal-magnetic trip unit (overload long-time delay protection + short-circuit instantaneous protection)
Overload Protection CharacteristicsLong-time delay inverse-time characteristic; setting current Ir = 1.0In (630أ). It can withstand 1.05In for long-term operation and will not trip within 1 hour under 1.3In
Short-Circuit Protection CharacteristicsInstantaneous trip setting current Ii = 10In (6300أ); it trips instantaneously when the short-circuit current reaches this value
فئة الحمايةIP20 (enclosure protection, preventing finger access)
طريقة التركيبFixed type/draw-out type (confirm specific model; fixed type is standard)
طريقة الأسلاكFront-panel wiring (معيار); rear-panel wiring is optional

ثالثا. الميزات الوظيفية

  1. Dual Protection Function: Integrates overload long-time delay protection and short-circuit instantaneous protection, which can effectively cut off overload and short-circuit fault currents to protect power distribution lines and equipment.
  2. Standard Breaking Capacity: The 35kA breaking capacity meets the short-circuit protection requirements of most industrial plants, commercial buildings, and civil power distribution scenarios.
  3. تصميم وحدات: Supports the installation of accessories such as auxiliary contacts, shunt releases, and undervoltage releases to expand functions like remote control and fault signal feedback.
  4. Easy Operation: Adopts a manual energy storage operating mechanism with clear closing/opening actions, and is equipped with a transparent observation window for intuitive inspection of contact status.
  5. Long Electrical and Mechanical Service Life: Electrical service life ≥ 10,000 مرات; mechanical service life ≥ 20,000 مرات, suitable for power distribution scenarios with frequent switching.
  6. Application Scope
  7. Main Switch of Power Distribution System: Suitable for incoming line and bus section switches in 400V three-phase low-voltage power distribution systems, protecting the secondary side of transformers and outgoing circuits of power distribution cabinets.
  8. Industrial Equipment Protection: Can be used as the power-side protection switch for high-power motors (مثل المشجعين, مضخات المياه, compressors with power ≤ 315kW).
  9. Building Power Distribution Scenarios: Protection of power distribution trunk lines in shopping malls, مباني المكاتب, factory workshops, إلخ., suitable for environments with conventional short-circuit current levels.
  10. Not Suitable For: Power distribution systems with high short-circuit current (> 35ال), precision equipment circuits requiring selective protection, and DC power distribution scenarios.
  11. اقتراحات الاختيار
  12. Match Load Current: The rated load current should be ≤ 630A. If the load is a motor, the motor starting current must be considered (it is recommended that the instantaneous setting current of the trip unit be ≥ 8 times the rated motor current).
  13. Verify Breaking Capacity: The calculated on-site short-circuit current should be ≤ 35kA. If the short-circuit current exceeds 35kA, upgrade to the NM1-630H type (higher breaking capacity, usually 50kA/65kA).
  14. Accessory Selection:

For remote opening: Install a shunt release (code 3310).

For undervoltage protection: Install an undervoltage release (code 3320).

For fault signal feedback: Install auxiliary contacts (code 3308).

  1. Brand Replacement Reference:
ماركةReplacement Modelالاختلافات الأساسية
شنايدرNSX630N 3P 630AHigher breaking capacity (50ال) and higher price
سيمنز3VL630 3P 630ARicher modular accessories, suitable for Siemens power distribution systems
لذيذCDM1-630S 3300 630أDomestic brand of the same grade with consistent parameters and high cost performance
  1. استكشاف الأخطاء وإصلاحها
Common Faultsالأسباب المحتملةالحلول
Trips immediately after closing1. Short-circuit fault exists in the line1. Troubleshoot the short-circuit point of the line and close after repair
2. Leakage on the load side (not applicable if no leakage accessory is installed)2. Check the insulation condition of the load
3. The instantaneous trip current setting is too small3. Confirm whether the trip unit setting current matches the load
Does not trip during overload1. Thermal trip unit failure1. Replace the thermal trip unit
2. The trip unit setting current is adjusted too high2. Re-adjust the setting current to the rated value
3. Circuit breaker contact adhesion3. Disassemble and inspect the contacts; replace the circuit breaker if necessary
Cannot close1. Undervoltage release is not powered on (if installed)1. Check whether the power supply of the undervoltage release is normal
2. Mechanical mechanism jamming2. Manually reset the mechanical mechanism and clean internal foreign objects
3. Line fault not eliminated3. Troubleshoot and eliminate line faults
Abnormal heating during operation1. Loose wiring terminals1. Tighten the wiring terminals and apply conductive paste
2. Load current exceeds the rated value2. Reduce the load or replace with a larger specification circuit breaker
3. ارتفاع درجة الحرارة المحيطة بشكل مفرط3. Improve ventilation and heat dissipation conditions

سابعا. Installation and Maintenance Notes

  1. قبل التثبيت, confirm that the rated voltage and current of the circuit breaker match the on-site power distribution system, and check that the appearance is intact and the mechanism is free of jamming.
  2. Ensure that the terminals are tightened during wiring to avoid heating caused by poor contact. For front-panel wiring, the wire cross-section should match the 630A current (it is recommended to use 240mm² copper core cable).
  3. Regularly (every 6 شهور) inspect the contact status of the circuit breaker and the flexibility of the mechanical mechanism, and remove dust inside the enclosure.
  4. After a fault trip, the cause of the fault must be investigated first; do not close forcibly to avoid expanding the fault range.

Parameter Comparison Table of NM1-630S-3300 Series (400A/500A/630A)

فئة المعلمةModel Specification
المعلمات الأساسيةNM1-630S-3300-400ANM1-630S-3300-500ANM1-630S-3300-630A
Frame Size Rated Current (Iu)630أ630أ630أ
تصنيف التشغيل الحالي (في)400أ500أ630أ
تصنيف جهد التشغيل (إي)AC 400V 50HzAC 400V 50HzAC 400V 50Hz
رقم القطب3-القطب3-القطب3-القطب
Trip Unit TypeThermal-magnetic (overload long-time delay + short-circuit instantaneous)Thermal-magnetic (overload long-time delay + short-circuit instantaneous)Thermal-magnetic (overload long-time delay + short-circuit instantaneous)
Protection Characteristics
كسر القدرة (وحدة العناية المركزة, AC 400V)35ال35ال35ال
Overload Long-Time Delay Setting Current (و)400أ (1.0في)500أ (1.0في)630أ (1.0في)
Overload Withstand CharacteristicsWithstand 1.05In for long-term operation; no tripping within 1h under 1.3InWithstand 1.05In for long-term operation; no tripping within 1h under 1.3InWithstand 1.05In for long-term operation; no tripping within 1h under 1.3In
Short-Circuit Instantaneous Setting Current (ثانيا)10In = 4000A10In = 5000A10In = 6300A
التثبيت والأسلاك
فئة الحمايةIP20IP20IP20
طريقة التركيبFixed type/draw-out type (خياري)Fixed type/draw-out type (خياري)Fixed type/draw-out type (خياري)
Recommended Matching Copper Core Cable Cross-Section185مم²240مم²240mm²/300mm²
Mechanical and Electrical Service Life
عمر الخدمة الميكانيكية≥20,000 times≥20,000 times≥20,000 times
عمر الخدمة الكهربائية≥10,000 times≥10,000 times≥10,000 times
سيناريوهات التطبيق النموذجية1. Power-side protection for 185kW three-phase motors1. Power-side protection for 250kW three-phase motors1. Power-side protection for 315kW three-phase motors
2. Power distribution branch switch (load current 350-400A)2. Power distribution trunk branch switch (load current 450-500A)2. Power distribution incoming line/bus section switch
3. Power distribution branch in small and medium-sized plants3. Power distribution branch in shopping malls and office buildings3. Power distribution trunk in large plants and high-rise buildings

Supplementary Selection Tips

  1. All specifications of this series have the same breaking capacity. Select the corresponding specification only according to the rated load current; there is no need to verify the breaking capacity additionally.
  2. If the load is a motor with frequent starting, it is recommended to select a specification with a rated current 1.1-1.2 times that of the motor to avoid overload false tripping.
  3. For the same frame size specification, the rated current can be adjusted by replacing the trip unit without replacing the circuit breaker body, reducing the later transformation cost.