Model Interpretation C10F32D100 is the complete order code of Schneider’s new-generation ComPacT NSX series molded case circuit breakers. The meaning of each segment is as follows: Code Segment Meaning Description C10 Frame Size and Breaking Capacity C10 = NSX100F, frame current 100A, breaking capacity Class F (36kA@415VAC) F Breaking Capacity Class F = 36kA@415VAC, مناسب ...

  • تفاصيل المنتج
  1. تفسير النموذج

C10F32D100 is the complete order code of Schneider’s new-generation ComPacT NSX series قواطع دوائر الحالة المصبوبة. The meaning of each segment is as follows:

Code SegmentMeaningوصف
C10Frame Size and Breaking CapacityC10 = NSX100F, frame current 100A, breaking capacity Class F (36kA@415VAC)
فBreaking Capacity ClassF = 36kA@415VAC, suitable for standard industrial applications
3عدد البولنديين3 = 3-pole (3P3D, three-phase three-wire system)
Trip Unit Type2D = MicroLogic 2.2 electronic trip unit with display function
100التصنيف الحالي100أ, adjustable range 90-100A
  1. Core Technical Parameters

المعلمات الأساسية

المعلمةقيمةوصف
Product TypeMolded Case Circuit Breaker (مكب)New-generation ComPacT NSX100F
الجهد المقنن690VAC/50-60HzMaximum operating voltage
التصنيف الحالي (Iu)100أContinuous operating current
Ultimate Breaking Capacity (وحدة العناية المركزة)36kA@415VACUltimate breaking capacity
Service Breaking Capacity (Ics)36kA@415VAC (100%)Service breaking capacity
Mounting TypeFixedStandard mounting, plug-in type optional (C10F32D100P)
Protection CategoryCategory AComplies with IEC 60947-2 معيار

MicroLogic 2.2 Trip Unit Parameters

وظيفة الحمايةمميزةAdjustable Range
Long-time Delay Protection (ل)Overload protection, inverse time-lag0.8-1.0脳Iu (90-100أ)
Short-time Delay Protection (س)Short-circuit protection, definite time-lag3-6脳Iu, adjustable
Instantaneous Protection (I)Short-circuit instantaneous tripping, fixed10脳Iu (1000أ)
Display FunctionCurrent measurement and status indicationReal-time display of three-phase current

Physical and Electrical Characteristics

المعلمةقيمة
Power Loss14.1W
وزنApproximately 2.5kg
Compliance Standardsاللجنة الانتخابية المستقلة 60947-2, GB 14048.2
الشهاداتم, سي سي سي, RoHS

ثالثا. الميزات الوظيفية

  1. Comprehensive Protection: Provides three-stage protection including long-time delay, short-time delay and instantaneous protection, effectively preventing overload and short-circuit faults.
  2. Precise Control: Compared with thermal-magnetic trip units (TM series), electronic trip units offer more accurate protection curves and adjustable parameters.
  3. Status Visualization: MicroLogic 2.2 is equipped with LED display for real-time monitoring of current and fault status.
  4. Modular Design: Supports a variety of accessories (auxiliary contacts, alarm contacts, undervoltage release, إلخ.) for flexible installation.
  5. Environmental Friendly: Schneider Green Signature design, reducing energy consumption and carbon footprint.
  6. Easy Operation: Ergonomic handle for labor-saving operation; front-mounted accessories reduce wiring time by 40%.
  7. سيناريوهات التطبيق
  8. أنظمة توزيع الطاقة الصناعية: Used as main switch or branch switch to protect motors, transformers and distribution lines.
  9. Building Electrical Systems: Low-voltage distribution cabinets in commercial buildings and industrial plants.
  10. Motor Control Centers (MCC): Protect three-phase motors from locked rotor and overload conditions.
  11. Data Centers: Power protection for critical loads to ensure power supply continuity.
  12. New Energy Sector: DC-side protection of photovoltaic inverters and energy storage systems (additional configuration required).
  13. Product Comparison

Comparison with Trip Units of the Same Series

ModelTrip Unit TypeMain Differencesسيناريوهات التطبيق
C10F32D100MicroLogic 2.2Electronic trip unit with display, three-stage protectionIndustrial applications requiring precise protection and monitoring
C10F3TM100TM100D Thermal-Magnetic TripThermal-magnetic trip unit, two-stage protection, cost-effectiveSimple power distribution without precise adjustment requirements
C10F33D100MicroLogic 3.2Added earth fault protection (30-3000أماه)

Comparison with Chint Alternative Models

Schneider ModelChint Alternative ModelSimilaritiesDifferences
C10F32D100NM1-125S/3300 100A3-pole, 100أ, 36kA breaking capacityChint adopts thermal-magnetic trip unit without display; Schneider adopts electronic trip unit with display
NM1-125H/3340 100A3-pole, 100أ, electronic trip unitChint has 50kA breaking capacity with slightly different protection functions
  1. Selection and Usage Recommendations
  2. اختيار النقاط الرئيسية

Select protection curves according to load types: لأحمال المحرك, it is recommended to set short-time delay to 5-6×Iu

Breaking capacity should be greater than the expected short-circuit current of the system

Consider future expansion; rated current should be slightly higher than the actual load current

  1. احتياطات التثبيت

Ensure the mounting surface is flat and the tightening torque meets requirements (screw torque 25N·m)

Corresponding cable lugs must be used for terminal connections to avoid heating caused by poor contact

Leave sufficient heat dissipation space around and avoid close installation with heat-generating components

  1. Maintenance Recommendations

Regular inspection (at least once a year): appearance, tightness status, flexibility of operating mechanism

Check contact condition after short-circuit tripping and replace if necessary

Clean with dry compressed air to avoid moisture and dust accumulation

سابعا. Troubleshooting Guide

Fault Phenomenonالأسباب المحتملةTroubleshooting Steps
Failure to Close1. Undervoltage release without power supply

2. Trip unit malfunction

3. Mechanical lockout

1. Check control power supply (if equipped)

2. Measure trip unit coil resistance

3. Manually reset the trip mechanism

False Tripping1. Overload

2. Short circuit

3. Improper trip unit parameter setting

1. Check load current

2. Check line insulation

3. Reset trip unit parameters

No Display After Tripping1. Trip unit power supply failure

2. Trip unit damage

1. Check trip unit power supply

2. Replace the trip unit