Comprehensive Analysis of Schneider C16F2TM160 قواطع دوائر
المعلمات الأساسية
Product Type: ComPacT NSX160F Series Molded Case Circuit Breaker (مكب)
Frame Current: 160أ (Frame Rating)
الجهد المقنن: 690الخامس و (Operating Voltage), 415الخامس و (Breaking Capacity Test Voltage)
كسر القدرة: 18ال (415الخامس و, 50/60هرتز) ملحوظة: Different from the 36kA of 3-pole models
Pole Configuration: 2ص (2 البولنديين) ملحوظة: Not 4 أقطاب
Trip Unit: TMD Thermal-Magnetic Type (Thermal Overload + Magnetic Short-Circuit Protection), Rated Current 160A
Applicable System: تيار متردد/تيار مستمر (Universal for Alternating Current and Direct Current)
Detailed Model Coding
C16F2TM160:
ج: ComPacT Series
16: Frame Current 160A
ف: Breaking Capacity Class (F=18kA, corresponding to F=36kA for 3-pole models)
2: Pole Configuration (2ص)
TM: Trip Unit Type (TMD Thermal-Magnetic Type)
160: Rated Current 160A
المعلمات التقنية التفصيلية
| المعلمة | قيمة |
| تصنيف الجهد العزل | 800الخامس و |
| الحياة الكهربائية | 40,000 Operating Cycles (440الخامس و) |
| الحياة الميكانيكية | 100,000 Operating Cycles |
| درجة حرارة التشغيل | -5℃ ~ +70℃ (Standard Type) |
| درجة الحماية | IP20 (Front Side) |
| طريقة التركيب | Fixed Mounting |
| Compliant Standards | اللجنة الانتخابية المستقلة 60947-2, اللجنة الانتخابية المستقلة 60898-1 |
Core Features
1. تصميم مدمج: Saves space in distribution cabinets and improves installation efficiency
2. Dual Protection: TMD thermal-magnetic trip unit provides overload and short-circuit protection
3. AC/DC Universality: Suitable for various power system environments
4. موثوقية عالية: Robust structure with resistance to vibration and impact
5. Easy Maintenance: Front-panel operation for convenient inspection, repair and replacement
Characteristics of TMD Trip Unit
الحماية الحرارية: Bimetallic strip senses overload current, with inverse time-delay characteristic
الحماية المغناطيسية: Electromagnetic coil detects short-circuit current, with instantaneous action
Fixed Protection Characteristics: Preset at the factory, no on-site adjustment required
No Communication Function: Only provides basic protection, without fault indication and remote monitoring capabilities
سيناريوهات التطبيق
Commercial Buildings: Protection for single-phase 220V/240V power distribution systems such as lighting and air conditioning
Industrial Equipment: Power protection for single-phase motors and small production lines
Infrastructure: Single-phase power supply circuits in places like hospitals and schools
Residential Distribution Boxes: Branch protection for high-end residences (على سبيل المثال, air conditioners, سخانات المياه, إلخ.)
DC Systems: DC power protection for some industrial automation and communication equipment
Comparison with Other Models in the NSX160F Series
| Model | Pole Configuration | كسر القدرة (ال) | Trip Unit Type | Application Scenario |
| C16F2TM160 | 2ص | 18 | TMD | Single-phase system protection |
| C16F3TM160 | 3ص | 36 | TMD | Three-phase system protection |
| C16F4TM160 | 4ص | 36 | TMD | Three-phase four-wire system protection |
| C16F42D160 | 4ص | 36 | Micrologic 2.2 | Systems requiring intelligent protection and communication functions |
احتياطات
Discontinued and Obsolete: Together with the entire NSX160F Series, production was discontinued at the end of 2022, and service support was terminated at the end of 2023
Replacement Models: It is recommended to consider the latest upgraded products of Schneider’s NSX Series (على سبيل المثال, NSX2 Series)
Purchasing Channels: Most products available on the market currently are stock items; please confirm the product status and quality assurance when purchasing
ملخص
Schneider C16F2TM160 is a 2-pole thermal-magnetic molded case circuit breaker with a breaking capacity of 18kA, specifically designed for single-phase or DC systems, and features a compact and reliable structure.
المقاولين,قاطع الدائرة,العاكس للطاقة الشمسية,عداد كهرباء,البطاريات الشمسية