Schneider EA9AN4C63 Miniature Circuit Breaker

ماركةReplacement Model
ايه بي بيS204‑C63
سيمنز5SY6463‑7CC
CHINTNXB‑63 4P C63
لذيذCDM30s‑63 4P C63
Schneider upgradeA9F94463 (Acti9 series)

  • تفاصيل المنتج

Schneider Easy9 series 4‑pole 63A C‑curve قاطع الدائرة المصغرة, used for overload and short‑circuit protection in three‑phase four‑wire distribution systems. DIN‑rail mountable, suitable for final distribution in residential, commercial and light industrial applications.

1 شرح النموذج

Partمعنى
EA9ANEasy9 series standard MCB
44 أقطاب (3 phases + ن), all poles with protection function
جC tripping curve (5–10In instantaneous trip), suitable for lighting and resistive/slightly inductive mixed loads
63Rated current 63A (at 30°C ambient)

2 المعلمات التقنية الرئيسية

المعلمةقيمةوصف
Rated operational voltage230/400الخامس وSuitable for single‑/three‑phase systems
تصنيف الجهد العزل400الخامس و
Rated frequency50/60هرتزUniversal frequency
Rated breaking capacity6ال (400V)Standard breaking capacity for general distribution
Tripping typeThermal‑magneticThermal overload protection + magnetic short‑circuit protection
منحنى التعثرC‑curveInstantaneous trip range: 5–10In, moderate inrush current withstand
Number of poles4 protected poles, neutral on the left
Mounting35مم DIN السكك الحديديةStandard electrical cabinet mounting
Electrical endurance10,000 العملياتRated operating cycles
Mechanical endurance20,000 العملياتMechanical operating cycles
أبعادتقريبا. 85mm×78.5mm×18mm (4‑pole width)Standard 4‑pole MCB size
StandardsGB16917/IEC60898National and international standards

3 الوظائف الأساسية & سمات

  1. حماية الزائد: Thermal trip unit acts with current‑time accumulation to prevent overheating and burnout.
  2. Short‑circuit protection: Magnetic trip unit operates instantaneously (<0.1s) to clear short‑circuit current and protect equipment and wiring.
  3. Isolation function: Complies with EN/IEC 60947‑2, can be used as an isolating device.
  4. Quick make: Internal mechanism ensures fast circuit closing.
  5. Operation indication: Clear ON/OFF status indication for easy maintenance.
  6. Safety design: Anti‑misoperation structure, high insulation performance, safe and reliable.

4 التطبيقات النموذجية

Residential distribution: Main incoming breaker for three‑phase four‑wire homes, protecting the entire electrical system.

Commercial buildings: Floor or zone main breaker in offices, مراكز التسوق, الفنادق, إلخ.

Light industry: Branch circuit protection for workshops and production lines, suitable for mixed motor, lighting and socket loads.

Final distribution: Dedicated protection for three‑phase equipment (مكيفات الهواء, مضخات, small machine tools).

5 Cross‑Brand Replacement Reference

ماركةReplacement Modelملحوظات
ايه بي بيS204‑C63Same 4P C63A, 6كا كسر القدرة
سيمنز5SY6463‑7CC4P C63A, standard breaking capacity
CHINTNXB‑63 4P C63Domestic alternative, cost‑effective
لذيذCDM30s‑63 4P C63Similar performance, compatible with domestic panels
Schneider upgradeA9F94463 (Acti9 series)Breaking capacity up to 15kA, improved performance

6 تثبيت & Selection Notes

  1. Installation precautions

Must be mounted on 35mm standard DIN rail, installation depth ≥78.5mm

Terminal suitable for copper conductors: 1.5–35mm²

Neutral must be connected to the designated left terminal – do not reverse.

  1. Selection recommendations

Total three‑phase load current ≤63A, suitable for C‑curve loads (not heavy motor starting).

For distribution systems with short‑circuit current >6ال, upgrade to higher breaking capacity models (على سبيل المثال, Acti9 series).

Derate at ambient temperature >30°C: current reduced by 1% per °C rise.

Schneider EA9AN4C63 vs Acti9 A9F94463 Full Comparison & Upgrade Recommendation

At a glance: A9F94463 (iC60L series) is superior to EA9AN4C63 in breaking capacity, compactness, accessory expandability, and electrical/mechanical endurance, suitable for higher short‑circuit risk and higher reliability/expandability requirements.

EA9AN4C63 is more economical and meets basic protection for standard residential and light commercial use.

1 Core Parameter Comparison

المعلمةEA9AN4C63 (Easy9)A9F94463 (Acti9 iC60L)الفرق الرئيسي
Series positioningEconomic standardHigh‑performance standardA9 higher‑end, richer functions
Poles/Current/Curve4ص / 63أ / C‑curve4ص / 63أ / C‑curveBasic specs identical
Rated breaking capacity6ال (400V)15ال (400V)A9 ×2.5 higher, stronger short‑circuit withstand
تصنيف الجهد العزل400الخامس و400الخامس وSame
Rated operational voltage230/400الخامس و230/400الخامس وSame
Tripping typeThermal‑magneticThermal‑magneticSame
Mounting35مم DIN السكك الحديدية35مم DIN السكك الحديديةSame
أبعاد85mm×78.5mm×18mm (4ص)85mm×44.5mm×18mm (4ص)A9 depth –43%, saves panel space
Wiring capacity1.5–35mm² (copper)1.5–35mm² (copper), dual tunnel terminalsA9 more secure, same conductor range
Electrical endurance10,00015,000A9 +50%
Mechanical endurance20,00025,000A9 +25%
Protection degreeIP20IP20 (terminal IP20B)A9 better terminal protection
توافق الملحقاتBasic accessories (aux./shunt)Full Acti9 range (aux., shunt, UVP, remote, إلخ.)A9 more expandable, supports Ti24
StandardsGB16917/IEC60898GB16917/IEC60898/IEC60947‑2A9 covers more standards
Price rangeتقريبا. ¥150–200تقريبا. ¥350–500A9 ~2–2.5× EA9 price

2 Detailed Performance Differences

2.1 كسر القدرة: Core Safety Gap

EA9AN4C63: 6ال, suitable for general systems with short‑circuit current ≤6kA.

A9F94463: 15kA high breaking capacity, reliably clears higher short‑circuit currents, reduces arc risk.

Suitable for:

Industrial plants, large commercial buildings

Distribution circuits near transformers

Systems where short‑circuit current may exceed 6kA

2.2 تصميم مدمج: Better Space Utilization

A9F94463 depth only 44.5mm, greatly reduced from EA9AN4C63 78.5mm.

Benefits:

Fits slimmer distribution boards/cabinets

Saves installation space, eases maintenance

Ideal for retrofit projects with limited space

2.3 Endurance & Reliability: Longer‑Term Stability

Electrical endurance from 10k → 15k operations; mechanical 20k → 25k.

A9 series uses higher‑grade materials and precision manufacturing for better long‑term stability.

Better vibration and impact resistance for harsh environments.

2.4 Accessory Expandability: Flexible Function Upgrades

EA9AN: Supports only basic auxiliary contacts and shunt trips.

A9F94463: Supports full Acti9 accessory range:

Multi‑function auxiliary / alarm contacts

Remote‑control shunt trips

Over/undervoltage protection modules

Auto‑reclose accessories

Ti24 interface for PLC/BMS integration

3 Upgrade Decision Guide

Recommended to upgrade to A9F94463 if:

  1. Calculated short‑circuit current >6ال
  2. Critical facilities: industrial, large commercial, hospital, data center
  3. Future expansion needed (التحكم عن بعد, voltage monitoring, إلخ.)
  4. Limited panel space requires compact solution
  5. Higher reliability and longer service life required to reduce maintenance cost

Recommended to keep EA9AN4C63 if:

  1. Standard residential / small shop loads, short‑circuit ≤6kA
  2. Budget‑sensitive, cost priority
  3. Basic protection only, no complex accessories
  4. Already installed EA9 panel with matching system parameters

4 ملاحظات الاستبدال

  1. Direct interchangeability: Both 4P C63A, DIN‑rail mount – direct replacement.
  2. Wiring check: A9F94463 neutral position matches EA9AN (left) – no need to reorder wiring.
  3. Derating: Both derate at >30°C (–1% per °C).
  4. توافق الملحقات: Existing EA9 accessories must be replaced with Acti9‑specific versions.