Schneider Electric IC65N-3PC16A

IC65: Represents the Schneider Acti9 series of miniature circuit breakers, with a frame rating current of 63A.

ن: Indicates the breaking capacity class. The N - type has a breaking capacity of 6kA (at 230/400V AC).

3ص: Denotes a three - pole design, which is used in three - phase four - wire or three - phase three - wire circuits and can disconnect three phase lines simultaneously.

C16A: Refers to a Type C tripping curve and a rated current of 16A. It is suitable for loads with moderate inrush currents, such as lighting and sockets.

  • تفاصيل المنتج

The IC65N-3PC16A from Schneider Electric is a Miniature Circuit Breaker (MCB) specifically designed for endofline power distribution. It is suitable for protecting threephase circuits against overload and shortcircuit damage. Below is a detailed analysis of its core parameters, application scenarios, and key selection points:

1. Model Meaning and Core Parameters

1.1 Model Breakdown

IC65: Represents the Schneider Acti9 series of miniature circuit breakers, with a frame rating current of 63A.

ن: Indicates the breaking capacity class. The Ntype has a breaking capacity of 6kA (at 230/400V AC).

3ص: Denotes a threepole design, which is used in threephase fourwire or threephase threewire circuits and can disconnect three phase lines simultaneously.

C16A: Refers to a Type C tripping curve and a rated current of 16A. It is suitable for loads with moderate inrush currents, such as lighting and sockets.

1.2 Key Electrical Parameters

الجهد المقنن: 230/400الخامس و, supporting a frequency of 50/60Hz.

Tripping Characteristics:

حماية الزائد: Achieved through the thermal effect of a bimetallic strip. It trips in approximately 30 seconds when the current reaches 1.5 أضعاف التيار المقنن (24أ).

ShortCircuit Protection: The electromagnetic trip unit acts instantaneously when the current is 5 – 10 أضعاف التيار المقنن (80 – 160أ).

كسر القدرة:

وحدة العناية المركزة (Ultimate ShortCircuit Breaking Capacity): 6ال (at 400V AC), which meets the shortcircuit protection requirements in residential and smallscale commercial scenarios.

Ics (Service ShortCircuit Breaking Capacity): 6ال (100% of Icu), ensuring that the circuit breaker can still be used after a shortcircuit occurs.

1.3 Physical Characteristics

أبعاد: It has a width of 54mm (6 modules) and is suitable for installation on a 35mm DIN rail, توفير مساحة في صندوق التوزيع.

فئة الحماية: IP20 (for the terminal part), preventing accidental contact with live components.

Service Life: It has a mechanical life of 20,000 operations and an electrical life of 10,000 العمليات, ensuring high longterm reliability.

2. Application Scenarios and Load Matching

2.1 Typical Application Fields

توزيع الطاقة السكنية: Used for protecting the circuits of highpower electrical appliances such as threephase air conditioners and electric water heaters.

Commercial Buildings: Applied in the lighting systems of offices and shopping malls, as well as for small threephase equipment (على سبيل المثال, elevator control circuits).

Industrial Scenarios: Suitable for endofline power distribution lines of automated production lines and small motors. لكن, it should be noted that the Type C curve may not be suitable for highinrush current loads (على سبيل المثال, directly started motors).

2.2 Load Selection Recommendations

Loads Suitable for Type C Curve:

Lighting fixtures (incandescent lamps, LED lamps, إلخ.).

Ordinary sockets (for computers, televisions, small household appliances).

Resistive loads (electric heaters, water dispensers).

Scenarios to Avoid:

Motors (the starting current can reach 5 – 10 أضعاف التيار المقنن, which may cause false tripping).

Inductive loads such as welding machines and compressors (a Type D curve is recommended).

3. Installation and Expansion Functions

3.1 طريقة التثبيت

Rail Installation: It can be directly fixed on a standard 35mm DIN rail using the snapfit on the back. It supports both top and bottom wire entry, with a wiring torque of 2.5N·m.

سعة الأسلاك: It can accommodate singlecore hard wires (1 – 25مم²) or flexible wires (1 – 16مم²). The tunneltype terminal design ensures a reliable connection.

3.2 Accessory Expansion

Earth Leakage Protection: It can be assembled with a Vigi IC65 earth leakage module (على سبيل المثال, Vigi C16A) to provide 30mA residual current protection. It is suitable for humid environments such as bathrooms and kitchens.

Status Monitoring:

OF Auxiliary Contact: Feeds back the on/off status of the circuit breaker through normally open/normally closed signals, and is used for remote monitoring or PLC systems.

SD Alarm Contact: Triggers an alarm when a fault trip occurs, facilitating quick location of the faulty circuit.

Control Functions:

MX Shunt Trip: Controls the circuit breaker to open remotely (على سبيل المثال, for fire alarm linkage).

MN Undervoltage Trip: Automatically disconnects the circuit when the voltage is abnormal, protecting sensitive equipment.

4. الشهادة والامتثال

International Certifications: It complies with IEC 60898 – 1 (Circuit Breakers for Household and Similar Purposes) و غيغابايت 10963.1 (Chinese Standard). It has obtained CCC and CE certifications, ensuring its applicability in the global market.

القدرة على التكيف البيئي:

– درجة حرارة التشغيل: – 35°C to + 70°C, suitable for widetemperature environments.

Pollution Degree Resistance: فصل 3, enabling stable operation in general industrial environments.

5. Key Selection Considerations

5.1 المطابقة الحالية

The rated current (16أ) should be greater than the maximum continuous load current of the circuit. It is recommended to calculate based on the load power (على سبيل المثال, for threephase loads: Power = √3 × Voltage × Current × Power Factor).

Avoid Overload: على سبيل المثال, the maximum resistive load that a 16A circuit breaker can handle is approximately 10.5kW (400V × 16A × 1.5).

5.2 Verification of Breaking Capacity

Ensure that the prospective shortcircuit current at the installation location does not exceed 6kA. If the shortcircuit risk is high (على سبيل المثال, near a transformer), a type with higher breaking capacity such as Htype (10ال) or Ltype (15ال) should be selected.

5.3 Earth Leakage Protection Requirements

For locations sensitive to personal safety (على سبيل المثال, residential bathrooms, outdoor equipment), an earth leakage module (Vigi) should be used together, rather than relying solely on the overload/shortcircuit protection of the circuit breaker itself.

6. Price and Market Reference

سعر: A single – قاطع الدائرة القطبية (1P C16A) costs approximately 30 – 50 يوان, and a threepole model (3P C16A) ranges from 80 ل 120 يوان. The specific price varies depending on the purchasing channel and quantity.

CostEffectiveness Advantage: Compared with competing products, the IC65N series is renowned for its high reliability, modular design, and wide accessory compatibility. It is suitable for projects with high requirements for stability and expandability.

7. ملخص

The Schneider IC65N – 3PC16A is a threephase circuit breaker with balanced performance. Relying on its 6kA breaking capacity, Type C tripping curve, and flexible accessory expansion, it has become an ideal choice for endofline power distribution in residential, commercial, and light industrial applications. When selecting, a comprehensive evaluation should be conducted based on the load type, shortcircuit risk, and functional requirements. Priority should be given to purchasing through formal channels to ensure product quality and aftersales support.