Technical Specifications & Application Guide
This is a 2‑pole, النوع ج, 25أ قاطع الدائرة المصغرة (MCB) from Schneider Electric’s Acti9 series, with order code A9F18225 and rated breaking capacity 6kA.
It provides overload and short‑circuit protection for lighting, socket, and small motor circuits in AC distribution systems.
Features include 3‑stage current limiting, quick make mechanism, and protection degree IP40 (front) / IP20 (محطات).
It is compatible with iC65 series accessories for functional expansion.
- Model Breakdown
| شفرة | معنى | وصف |
| SCHNEIDER | ماركة | شنايدر إلكتريك (فرنسا), global electrical equipment manufacturer |
| iC65N | مسلسل | Acti9 iC65 MCB, N‑type breaking capacity (6ال) |
| 2ص | Number of poles | 2‑pole, breaks phase and neutral simultaneously, for 230V/400V systems |
| ج | منحنى التعثر | النوع ج, instantaneous tripping at 5~10×In (5In~10In) |
| 25أ | التصنيف الحالي | 25 amperes continuous at 30°C ambient |
| A9F18225 | Full order code | Official unique identifier |
- المواصفات الأساسية
| غرض | مواصفة | ملحوظات |
| أساسي | ||
| يكتب | قواطع دوائر مصغرة (MCB) | يتوافق مع اللجنة الانتخابية المستقلة 60898-1 / GB 10963.1 |
| Tripping type | Thermal‑magnetic | الزائد (thermal) + short‑circuit (magnetic) حماية |
| كسر القدرة | 6ال | Max breaking current at rated voltage |
| Rated operational voltage | التيار المتناوب 230 فولت/400 فولت | For 2‑pole version |
| تصنيف الجهد العزل | 500V | Max withstand voltage of insulation |
| Rated impulse withstand voltage | 6كيلو فولت | Surge voltage immunity |
| Rated frequency | 50/60هرتز | Global grid compatible |
| خصائص التعثر | ||
| حماية الزائد | 1.13في (no trip in 1h), 1.45في (trip within 1h) | Meets IEC requirements |
| Short‑circuit protection | Instantaneous at 5In~10In | النوع ج, مناسبة للإضاءة, الأحمال المقاومة, small motors |
| Physical & environmental | ||
| أبعاد (العرض × الارتفاع × العمق) | 18mm×86mm×62mm | Standard modular, 2P = 2 modules (18mm/pole) |
| Protection degree | IP40 (front), IP20 (محطات) | Solid object and moisture protection |
| درجة حرارة التشغيل | -35°C ~ +70°C | Suitable for harsh industrial environments |
| تصاعد | 35مم DIN السكك الحديدية | Standard panel mounting |
| الشهادات | سي سي سي, م, RoHS | Meets Chinese and international safety & environmental standards |
- سمات
- Protection performance
3‑stage current limiting: Quickly limits peak current during short circuit, reduces thermal stress, protects equipment and cables.
Selective protection: Coordinates with upstream breakers for selective tripping, limits fault area.
Fault indication: Red window shows tripped status for quick diagnosis.
- Structural advantages
Dual‑lock clip: Secures firmly on DIN rail, prevents vibration loosening.
Quick make mechanism: Improves closing speed, reduces arcing, extends life.
تصميم وحدات: Accepts auxiliary contacts, alarm contacts, shunt trip, undervoltage trip, إلخ.
- Safety design
Isolation function: Safe isolation distance in OFF position, meets electrical safety rules.
Anti‑misoperation: Handle design prevents accidental closing.
Flame‑retardant housing: V0 grade material improves cabinet safety.
- تثبيت & صيانة
Installation Rules
- Mount vertically (±15°) for proper tripping.
- Wiring: Copper 1.5~35mm², Aluminium 2.5~35mm², torque 1.2~4N·m (depends on cross‑section).
- Environment: Avoid damp, dusty, corrosive or high‑vibration locations.
- Spacing: Maintain clearance for heat dissipation; follow installation manual.
Maintenance Guide
| غرض | Interval | Criterion | حل |
| Visual inspection | شهريا | No damage, no overheating, tight connections | Clean, tighten loose terminals |
| اختبار الوظيفة | ربع سنوية | Manual ON/OFF smooth, no sticking | Operate 3–5 times, check mechanism |
| Trip test | سنويا | الزائد & short‑circuit protection functional | Test with dedicated equipment or simulate overload |
| Accessory check | سنويا | Auxiliary & alarm contacts working | Check contact condition, replace damaged parts |
استكشاف الأخطاء وإصلاحها
- التعثر المتكرر: Check overload → short circuit → high ambient temperature → aging.
- Cannot close: Check short circuit → handle position → trip reset → loose wiring.
- Overheating: Check terminal torque → overload → ventilation.
- Upgrade & استبدال
5.1 Same‑series Upgrades
iC65H-2P-C25A (A9F28225): H‑type, 10ال, for higher short‑circuit current.
iC65L-2P-C25A (A9F38225): L‑type, 15ال, for heavy industrial use.
iC65N-2P-C25A‑Vigi (A9V58225): With residual current protection (RCCB), prevents electric shock.
5.2 Functional Accessories
| ملحق | Typical Model | وظيفة |
| Auxiliary contact | A9A26924 | 1NO+1NC, remote status indication |
| Shunt trip | A9X16224 | Remote tripping, على سبيل المثال, fire alarm |
| Undervoltage trip | A9X16624 | Auto‑trip on low voltage |
| Alarm contact | A9A27924 | Signal when breaker trips |
5.3 Cross‑series Alternatives
| مسلسل | استبدال | التوافق |
| Easy9 | EA9AN 2P C25A | Same dimensions, 6ال, economical |
| Acti9 CVS | CVS100B 2P C25A | مكب, higher breaking capacity (10ال), main circuit use |
| Merlin Gerin | C65N 2P C25A | Fully compatible with iC65 |
- التطبيقات
- Commercial buildings: Offices, المحلات التجارية, hotels – lighting & socket circuits.
- Industrial automation: Control panels, small motors (≤5.5kW), VFD input protection.
- Residential: Home distribution – air conditioners, أدوات المطبخ.
- Public facilities: Schools, المستشفيات, stadiums – electrical safety.
- اختيار & Purchasing Tips
- مطابقة التحميل: Type C for lighting, مآخذ, small motors (≤5.5kW). Use Type B for pure resistive, Type D for large motors.
- كسر القدرة: Choose N (6ال), ح (10ال), ل (15ال) based on system short‑circuit current.
- البولنديين: 2P for 230V single‑phase where phase + neutral must be disconnected.
- Accessories: Add aux, shunt, undervoltage for smart systems.
- Authenticity: Buy from authorized Schneider distributors.
- Quick Fault Guide
| Symptom | السبب المحتمل | حل |
| Trips immediately after closing | Short circuit / الزائد | Locate short, reduce load or upsize breaker |
| Trips after running a while | الزائد / ارتفاع درجة الحرارة | Reduce load, تحسين التهوية, check cable size |
| Handle cannot be pushed to ON | Not reset / wiring fault | Pull to OFF first, then ON; check circuit |
| Terminal overheating | Loose connection | Retorque after power off, check terminals |
| No operation | Thermal‑magnetic unit failed | Replace MCB, check coordination |
SCHNEIDER iC65N-2P-C25A
Cross‑Brand Replacement Guide
Core Summary: The iC65N-2P-C25A (A9F18225) can be directly replaced by equivalent MCBs from major international and domestic brands.
Key matching requirements:
2ص, النوع ج, 25أ, 6ال, 35mm DIN rail mounting.
- International Brand Direct Replacements
ايه بي بي
| استبدال | Order Code | Breaking | التوافق |
| S202-C25 | 2CDS252001R0254 | 6ال | Best match, same dimensions, direct swap |
| S202M-C25 | 2CDS262001R0254 | 10ال | Higher breaking capacity |
| S202L-C25 | 2CDS242701R0254 | 4.5ال | Economy option |
سيمنز
| استبدال | مسلسل | Breaking | التوافق |
| 5SL6225-7 | 5SL | 6ال | Direct replacement, اللجنة الانتخابية المستقلة 60898-1 |
| 5SY6225-7 | 5SY | 6ال | Economy range |
| 5SN6225-7CN | 5SN | 6ال | Classic, reliable |
إيتون
| استبدال | مسلسل | Breaking | التوافق |
| FAZ6-C25/2 | FAZ | 6ال | Same dimensions & mounting |
| PL9-C25/2 | PL9 | 6ال | High performance, fast limiting |
Moeller
| استبدال | مسلسل | Breaking | التوافق |
| FAZ6-C25/2 | FAZ | 6ال | Same dimensions & mounting |
| PL9-C25/2 | PL9 | 6ال | High performance, fast limiting |
- Chinese Domestic Brands
| ماركة | استبدال | Breaking | التوافق |
| CHINT | NXB-63-2P C25 | 6ال | Cost‑effective, direct fit |
| DELIXI | CDM3-63C25/2P | 6ال | Same dimensions |
| Liangxin | NDM1-63C25/2P | 6ال | High quality domestic |
| TENGEN | TGM1-63C25/2P | 6ال | الحماية الأساسية, economical |
- Critical Parameter Matching
| غرض | Original (iC65N-2P-C25A) | Must Match | قابل للتعديل | ملحوظات |
| البولنديين | 2ص | 2ص | – | Disconnect phase + neutral |
| Curve | النوع ج (5~10In) | النوع ج | – | For lighting & small motors |
| حاضِر | 25أ | 25أ | – | Continuous rating |
| Breaking | 6ال | ≥6kA | Can be higher (10ال) | Ensure safe short‑circuit interruption |
| تصاعد | 35مم DIN السكك الحديدية | 35مم DIN السكك الحديدية | – | Standard panel mount |
| Width | 18مم | 18مم | H/D may vary | Fits standard spacing |
| الجهد االكهربى | التيار المتناوب 230 فولت/400 فولت | التيار المتناوب 230 فولت/400 فولت | – | Universal AC system |
- ملاحظات الاستبدال & Best Practice
Before Replacement
System short‑circuit current ≤ breaking capacity of replacement.
35مم DIN السكك الحديدية, space, terminal size compatible.
Protection coordination with upstream/downstream devices.
Accessory mounting interface compatible.
Replacement has valid certifications (سي سي سي, م).
Procedure
- Power off and verify voltage absence.
- Remove wiring and old breaker.
- Clip replacement onto DIN rail.
- Torque terminals correctly.
- Test ON/OFF and tripping.
- Update labeling and drawings.
When NOT to replace
Original uses dedicated Schneider accessories (على سبيل المثال, Vigi modules).
System short‑circuit current exceeds replacement rating.
Load inrush >10في (unsuitable for Type C).
Extreme environment outside replacement specs.
- Recommended Replacement Levels
| مستوى | النماذج الموصى بها | طلب | Advantage |
| 1st | ABB S202-C25 | Industry, تجارة | Full performance, global support |
| Siemens 5SL6225-7 | |||
| 2nd | Eaton FAZ6-C25/2 | Control panels | Good value, easy install |
| Moeller DIL M9-25 C/2 | |||
| 3rd | CHINT NXB-63-2P C25 | Residential, economy | Low cost, fast local supply |
| DELIXI CDM3-63C25/2P |
- Common Issues & الحلول
| مشكلة | Cause | حل |
| Frequent tripping after replacement | Wrong curve / الزائد | Confirm Type C, check load, upsize if needed |
| Will not fit | Wrong rail / عرض | Use 35mm DIN rail, 18mm width model |
| Wiring difficult | Incompatible terminals | Use suitable lugs or select compatible model |
| Insufficient breaking capacity | استبدال < system short鈥慶ircuit current | Use higher version (على سبيل المثال, ABB S202M-C25, 10ال) |
Cross‑brand replacement for SCHNEIDER iC65N-2P-C25A depends on parameter matching + mechanical compatibility + protection coordination.
Top international brands (ايه بي بي, سيمنز) give identical performance.
Domestic brands (CHINT, DELIXI) offer cost savings.
Always verify specifications and follow electrical safety standards.
المقاولين,قاطع الدائرة,العاكس للطاقة الشمسية,عداد كهرباء,البطاريات الشمسية