Schneider MT08N1 3P 800A is a fixed 3-pole intelligent air circuit breaker (ACB) belonging to the Masterpact MT series. It has a frame current and rated current of 800A, with an N1-class breaking capacity (50kA@400V). Suitable for incoming line/bus tie protection and power distribution in power distribution systems, it is commonly used in primary/secondary power ...

  • تفاصيل المنتج

Schneider MT08N1 3P 800A is a fixed 3-pole intelligent air circuit breaker (ACB) belonging to the Masterpact MT series. It has a frame current and rated current of 800A, with an N1-class breaking capacity (50kA@400V). Suitable for incoming line/bus tie protection and power distribution in power distribution systems, it is commonly used in primary/secondary power distribution of industrial plants, large buildings and data centers. Below are the complete specifications and core details:

Core Technical Parameters

ItemالمعلمةRemarks
ModelMT08N1 3P 800A (Order Code: MT08N1)MT series; 08=800A frame; N1=50kA breaking capacity
SeriesMasterpact MT (Air Circuit Breaker)Intelligent type, zero arcing, compatible with Micrologic control units
رقم القطبThree-phase power distribution, no neutral protection (4P optional)
التصنيف الحالي (في)800أ (at 40℃)Long-term continuous current-carrying capacity
Frame Current (Iu)800أMaximum current adaptable to the breaker body
Rated Operational Voltage (Ue)690فولت تيار متردد 50/60 هرتزInsulation Voltage (Ui) = 1000V
Short-circuit Breaking Capacity (وحدة العناية المركزة)50ال (400الخامس و)N1 class, متوافق مع IEC 60947-2
Short-time Withstand Current (اي سي دبليو)42kA/1s (400V)Ability to withstand short-circuit impact
Making Capacity (Icm)105ال (440الخامس و)Ability to close short-circuit current
Impulse Withstand Voltage (Uimp)12kVStrong surge resistance
Control UnitCompatible with Micrologic 2.0/5.0/6.0, إلخ.Long-time delay/short-time delay/instantaneous/earth fault protection
طريقة التركيبFixed (ف) / Drawout (د)Standard dimensions for fixed 3P model: 301×276×196mm
Wiring MethodFront/back panel screw clamping terminalsSuitable for top/bottom cable entry
Operation Methodكهربائي + manual (for maintenance)Equipped with closing/opening buttons and status indicators
Mechanical/Electrical Service Life10,000 mechanical operations; 2,000 electrical operations (ايه سي-3)High durability
Certificationsسي سي سي, اللجنة الانتخابية المستقلة, UL, CSA, EACGreen Premium compliant

Core Functions & Protection Features

  1. Full Intelligent Protection: Realizes long-time delay (overload), short-time delay (ماس كهربائى), instantaneous (heavy short circuit) and earth fault protection via the Micrologic control unit. Parameters can be precisely set to adapt to cascade coordination in multi-level power distribution systems.
  2. Measurement & Monitoring: Displays real-time electrical parameters such as current, voltage and power, with fault memory and alarm output functions. Supports Modbus and other communication protocols, and can be integrated into SCADA systems.
  3. Zero Arcing Design: Optimized arc extinguishing chamber with zero arcing distance, improving cabinet safety and space utilization.
  4. وظيفة العزل: Compliant with IEC 60947-2, can be used as an isolating switch (without controller).

سيناريوهات التطبيق & اختيار النقاط الرئيسية

Typical Scenarios: Primary/secondary power distribution links such as incoming line cabinets of industrial plants, power distribution of large buildings, UPS output of data centers, photovoltaic/energy storage combiner boxes, إلخ. It is used for power distribution and short-circuit, overload, earth fault protection of lines/equipment.

Key Selection Tips:

Control Unit: 2.0 for basic protection; 5.0/6.0 with added measurement and communication functions, select according to requirements.

Mounting Type: Fixed type is cost-effective; drawout type facilitates maintenance and allows breaker replacement without power outage.

– كسر القدرة: N1 (50ال) meets general power distribution needs; upgrade to N2/H1/H2 class if short-circuit current is high.

Procurement & Replacement Recommendations

  1. Complete Order Specification: Must specify MT08N1 + control unit model + mounting method + رقم القطب, على سبيل المثال, MT08N1 F MIC 2.0 3ص.
  2. Replacement Compatibility: Can directly replace MT08N2/H1 and other models with the same frame size. Dimensions differ from the NW series; verify cabinet installation space before replacement.
  3. Price Reference (December 2025): Domestic fixed type with MIC 2.0 control unit is approximately RMB 14,500-16,000 per unit; drawout type is priced higher.

Breaking Capacity Comparison Table of Schneider Masterpact MT08 Series (800أ)

ItemMT08N1 3P 800AMT08N2 3P 800AMT08H1 3P 800AMT08H2 3P 800ARemarks
Breaking Capacity ClassN1N2H1H2N=Standard type; H=High breaking type
Rated Ultimate Short-circuit Breaking Capacity (وحدة العناية المركزة) @400V AC50ال70ال100ال150الCompliant with IEC 60947-2
Rated Service Short-circuit Breaking Capacity (Ics) @400V AC50ال (100% وحدة العناية المركزة)70ال (100% وحدة العناية المركزة)100ال (100% وحدة العناية المركزة)150ال (100% وحدة العناية المركزة)Can carry rated current continuously after breaking
Short-time Withstand Current (اي سي دبليو) @400V AC/1s42ال50ال85ال120الAbility to withstand short-circuit impact
Making Capacity (Icm) @440V AC105ال147ال210ال315الAbility to close short-circuit current
Rated Operational Voltage (Ue)690الخامس و690الخامس و690الخامس و690الخامس وInsulation Voltage (Ui) = 1000V
التصنيف الحالي (في)800أ (at 40℃)800أ (at 40℃)800أ (at 40℃)800أ (at 40℃)Frame Current (Iu) = 800A
Optional Pole Number3P/4P3P/4P3P/4P3P/4P4P with neutral protection
طريقة التركيبFixed/DrawoutFixed/DrawoutFixed/DrawoutFixed/DrawoutDrawout type requires additional chassis
Compatible Control UnitsMicrologic 2.0/5.0/6.0/7.0Micrologic 2.0/5.0/6.0/7.0Micrologic 2.0/5.0/6.0/7.0Micrologic 2.0/5.0/6.0/7.07.0 is a high-end measurement and control unit, supporting power quality analysis
أبعاد (Fixed 3P, W×H×D)301×276×196mm301×276×196mm301×276×210mm301×276×225mmHigh breaking types have slightly increased depth due to optimized arc extinguishing chambers
Mechanical Service Life10,000 العمليات10,000 العمليات10,000 العمليات10,000 العملياتElectrical service life: 2,000 العمليات (ايه سي-3)
Price Reference (December 2025, Fixed Type + Micrologic 2.0)RMB 14,500-16,000/unitRMB 17,000-19,000/unitRMB 22,000-25,000/unitRMB 28,000-32,000/unitDrawout type: 30%-40% price increase; imported model: عن 50% price increase
سيناريوهات التطبيق النموذجيةGeneral industrial plants, incoming line/bus tie of building power distributionMedium-voltage distribution outgoing terminals, industrial scenarios with high short-circuit currentHeavy industrial plants, data centers, photovoltaic/energy storage combiner systemsPower grids with high short-circuit current, supporting large generator setsSelect according to grid short-circuit current level

Complete Order Code Examples & Stocking Recommendations

  1. Complete Order Code Specification (4 Core Elements Required)

Ordering Schneider MT series requires specifying frame size + breaking capacity class + mounting method + control unit + رقم القطب. Examples are as follows:

MT08N1 F MIC 2.0 3ص: 800A N1 class, نوع ثابت, Micrologic 2.0 control unit, 3-pole

MT08H1 D MIC 5.0 4ص: 800A H1 class, drawout type, Micrologic 5.0 control unit, 4-pole

  1. Stocking & توصيات الاختيار
  2. Select by Short-circuit Current

First calculate the expected short-circuit current at the distribution point: choose N1 class (highest cost-performance) if ≤50kA; N2 class if 50-70kA; H1/H2 class if >70ال.

For industrial plants close to substations with high short-circuit current, prioritize H1 class.

  1. Select by Operation & Maintenance Requirements

Choose fixed type for general power distribution scenarios, featuring low cost and small space occupation;

Choose drawout type for scenarios where power outage for maintenance is not allowed (على سبيل المثال, data centers, hospitals), enabling live replacement of the breaker body.

  1. Select by Functional Requirements
Control Unit ModelCore Functionsالسيناريوهات القابلة للتطبيق
Micrologic 2.0Basic protection (long-time delay/short-time delay/instantaneous)General power distribution without measurement and control requirements
Micrologic 5.0Protection + electrical parameter measurement (current/voltage/power)Buildings and factories requiring energy consumption monitoring
Micrologic 6.0Protection + قياس + communication (Modbus/Profibus)Intelligent power distribution systems requiring SCADA integration
Micrologic 7.0Full functions + power quality analysis (harmonics/unbalance)Data centers, precision manufacturing workshops
  1. Stocking Recommendations

For regular trade stocking, prioritize MT08N1 F MIC 2.0 3ص, which adapts to 80% of general power distribution scenarios and ensures fast inventory turnover;

For heavy industry customers, stock a small quantity of MT08H1 F MIC 5.0 3P to meet high short-circuit current requirements;

Customize drawout models on demand; large-scale stocking is not recommended (high capital occupation and strong model specificity).

Core Parameter Comparison Table: Schneider MT08 Series vs. Chint NA8G-800 Series

(Both are 800A frame, 3-pole, نوع ثابت, basic protection type, suitable for general power distribution scenarios)

Comparison ItemSchneider MT08N1 3P 800A (Micrologic 2.0)Chint NA8G-800-3P-800A (Basic Trip Unit)Core Difference Summary
Product Series PositioningMasterpact MT series intelligent air circuit breakerNA8G series air circuit breakerSchneider focuses on intelligent measurement & يتحكم + high reliability; Chint focuses on high cost-performance + localized adaptation
Rated Ultimate Short-circuit Breaking Capacity (وحدة العناية المركزة) @400V50ال40الSchneider’s breaking capacity is 25% higher, suitable for scenarios with high short-circuit current
Rated Service Short-circuit Breaking Capacity (Ics) @400V50ال (100% وحدة العناية المركزة)40ال (100% وحدة العناية المركزة)Both support continuous operation after breaking; Schneider has higher redundancy
Short-time Withstand Current (اي سي دبليو) @400V/1s42ال31.5الSchneider has stronger short-circuit impact resistance, suitable for heavy-duty industrial scenarios
Protection FunctionsLong-time delay/short-time delay/instantaneous three-stage protection; expandable earth fault protectionLong-time delay/short-time delay/instantaneous three-stage protection; earth fault protection requires customizationBasic protection is consistent; Schneider offers more flexible expansion functions
Measurement & Control CapabilitySupports electrical parameter display (current/voltage); can be equipped with communication modules for SCADA integrationBasic protection only, no measurement and control functions; measurement supported only by upgraded models (NA8G-800M)Schneider has higher intelligence level, suitable for intelligent power distribution needs
طريقة التركيبFixed/drawout optional; drawout type with standard mechanical interlockFixed/drawout optional; drawout interlock is optionalSimilar structural design; Schneider’s standard interlock offers higher safety
أبعاد (Fixed 3P, W脳H脳D)301脳276脳196mm320脳285脳210mmSchneider is more compact, saving cabinet space
Mechanical/Electrical Service Life10,000 mechanical operations; 2,000 electrical operations (ايه سي-3)8,000 mechanical operations; 1,500 electrical operations (ايه سي-3)Schneider has better durability, suitable for high-frequency operation scenarios
Certification Standardsسي سي سي, اللجنة الانتخابية المستقلة, UL, CSA, EACسي سي سي, اللجنة الانتخابية المستقلةSchneider has broader certification coverage, suitable for export projects
Price Reference (December 2025, Fixed Type)RMB 14,500-16,000/unitRMB 6,500-7,500/unitChint’s price is about 45%-50% of Schneider’s, with outstanding cost-performance
سيناريوهات التطبيق النموذجيةIndustrial plant incoming lines, data centers, high-end buildings, export projectsCivil building power distribution, small and medium-sized factories, localized power distribution renovation projectsSelect according to project budget and reliability requirements
After-sales ServiceNationwide warranty, extensive overseas network; spare parts supply cycle: عن 7 daysNationwide warranty, fast localized service response; spare parts supply cycle: عن 3 daysChint’s after-sales service is more suitable for domestic small and medium-sized customers

Selection Decision Recommendations

  1. Scenarios for Prioritizing Schneider MT08 Series

Export projects (على سبيل المثال, overseas markets such as Algeria), power distribution projects requiring international certifications;

Scenarios with high requirements for short-circuit breaking capacity and reliability, such as data centers and heavy industrial plants;

Intelligent power distribution systems requiring energy consumption monitoring and remote control.

  1. Scenarios for Prioritizing Chint NA8G-800 Series

Domestic civil buildings, small and medium-sized factories and other general power distribution scenarios with limited budgets;

Localized renovation projects requiring fast delivery and after-sales response;

Power distribution circuits with only basic short-circuit and overload protection needs, no intelligence requirements.

  1. Replacement Compatibility Notes

The two series have slightly different mounting dimensions; verify cabinet installation space before replacement;

Chint NA8G series can upgrade measurement and control functions by installing intelligent trip units (على سبيل المثال, NA8G-M), with the cost still lower than that of similarly configured Schneider models.