A9F44102 and A9F18102 are two fully compatible, directly interchangeable Miniatur-Leistungsschalter aus der Acti9-Serie von Schneider Electric. Their core difference lies in product series iteration (iC60N → iC65N) and order code numbering, while their electrical parameters and mounting dimensions are almost identical.

  1. Model and Core Parameter Comparison
ArtikelA9F44102A9F18102
SerieiC60N (legacy version)iC65N (new/replacement version)
Full SpecificationiC60N 1P C2AiC65N 1P C2A
Anzahl der Pole1P (single-pole)1P
Nennstrom2A2A
AuslösekurveTyp C (5~10 Zoll)Typ C
Bruchkapazität6Die (Icn, 230V)6Die (Icn) / 50Die (Icu)
Nennspannung230/400V und230/400V und
SchutzgradIP20IP20
MontageDIN rail (18mm Breite)DIN rail (18mm Breite)
Abmessungen (B×H×T)18×85×78.5mm18×94×78.5mm
  1. Hauptunterschiede
  2. Product Iteration

A9F44102: Legacy iC60N series, schrittweise auslaufen.

A9F18102: Upgraded iC65N series, the official replacement for A9F44102.

Interchangeability: 100% compatible, can be replaced directly without rewiring or adjusting installation space.

  1. Minor Performance Differences

Bruchkapazität: The ultimate breaking capacity (Icu) of iC65N (A9F18102) reaches 50kA, higher than iC60N, providing stronger safety performance.

Physical Height: iC65N is 94mm high, slightly taller than the 85mm of iC60N, but the mounting width and depth remain the same.

  1. Order Code Explanation

A9F: Fixed prefix for the Acti9 series

44: Represents the iC60N series

18: Represents the iC65N series

1: 1 Pole (1P)

02: Rated current 2A

  1. Replacement and Selection Recommendations

Direkter Ersatz: A9F44102 (iC60N 1P 2A) → A9F18102 (iC65N 1P 2A)

Higher Breaking Capacity: For 10kA breaking capacity, select iC65H 1P C2A (A9F27102)

Anwendung: Both models are suitable for standard 2A load protection scenarios such as lighting circuits and control circuits.