  1. Baseline Core Parameters (A9C20844)
ParameterelementBaseline Value
Brand/SeriesSchneider Acti9 iCT
Pole Number/Contacts4P 4NO (4-pole, 4 normalerweise offen)
Nennstrom40A (AC-7a) / 15A (AC-7b)
Spulenspannung220-240V AC 50Hz
Applicable Voltage400V und
Utilization CategoryAC-1/3/7a (Complies with IEC 60947-4-1/IEC 61095)
Montagemethode35mm Standard DIN Rail (Modularer Aufbau)
Abmessungen85mm*54mm*60mm, IP20 Protection Class
  1. Cross-Brand Model Comparison Table
BrandSerieCorresponding ModelPole Number/ContactsNennstromSpulenspannungMontagemethodeMatching Notes
SchneiderActi9 iCTA9C20844 (Baseline)4P 4NO40A (AC-7a)220-240V undDIN RailOriginal baseline model
ChintNCH8 (Modular)NCH8-40/40 AC220/230V4P 4NO40A220-230V undDIN RailPerfect match: Same pole number/contacts/current/mounting method, suitable for lighting/heating/motor loads
ChintCJX2 (Universal)CJX2-4004 220V4P 4NO40A220V undBolt/DIN Rail OptionalIndustrial-grade alternative, consistent contact capacity, suitable for AC-3 operating conditions
DelixiCDCH8s (Household/Modular)CDCH8s40/40 220-240V4P 4NO40A220-240V undDIN RailSuitable for household/small industrial applications, similar size, ideal for lighting/heating loads
DelixiCJX2s (Universal)CJX2s-4004 220V4P 4NO40A220V undBolt/DIN Rail OptionalIndustrial-grade alternative, consistent performance parameters, suitable for motor control
ABBA Series (Mounted Type)A50-40-00*220-230V4P 4NO40A220-230V undDIN RailModular design, same parameter matching, suitable for AC-1/3 loads
ABBESB (Mounted Type)ESB40-40N-06 230V4P 4NO40A230V undDIN RailIndustrial mounted type, suitable for lighting/heating loads, entspricht IEC 60947-4
SiemensSIRIUS 3RT23 (4-pole)3RT2326-2BB404P 2NO+2NC (Configurable)40A220V undDIN RailRequires additional auxiliary contacts to achieve 4NO; suitable for motor loads (7.5kW/400V)
SiemensSIRIUS 3RT14 (Resistive Load Dedicated)3RT1483-1BB404P 4NO40A220V undDIN RailDesigned specifically for AC-1 resistive loads, ideal for heating/lighting systems
LS ElectricGMC (Universal)GMC-40 40A 4P 4NO 220V4P 4NO40A220V undDIN RailKorean brand alternative, consistent parameters, suitable for industrial automation systems
OmronDILM (Modular)DILM40-10(4NEIN) 220V4P 4NO40A220V undDIN RailEuropean standard design, suitable for AC-3 motor control (7.5kW/400V)

III. Key Matching Guidelines

  1. Perfect Match Models (Highly Recommended)

Chint NCH8-40/40 AC220/230V: Fully identical structure to A9C20844, with 4P 4NO, 40A, DIN rail mounting, suitable for the same load types, and more cost-effective.

ABB A50-40-00 220-230V: Modular design, similar dimensions, meets full AC-1/3/7a operating conditions, suitable for projects with high brand compatibility requirements.

  1. Functional Match Models (Note Differences)

Siemens 3RT1483-1BB40: Optimized specifically for AC-1 resistive loads, not recommended for motor control with frequent start-stop cycles (AC-3).

Delixi CDCH8s40/40: Household series with a maximum rated voltage of 230V; derating or compatibility verification is required when used in 400V systems.

  1. Replacement Selection Precautions
  2. Contact Type Verification: Ensure the replacement model is 4NO to avoid control logic errors caused by configurations like 2NO+2NC.
  3. Utilization Category Matching:

Motor control: Must select models compatible with AC-3.

Lighting loads: Must meet AC-7a/7b (rated current 15-40A).

Resistive heating: AC-1 is sufficient for adaptation.

  1. Mounting and Dimensions:

Modular projects: Prioritize DIN rail-mounted models to ensure compatibility with distribution cabinet space.

Replacing existing A9C20844: Verify the width (54mm) to avoid interference during side-by-side installation of multiple units.

  1. Hilfsfunktionen: For surge suppression or status indication, some replacement models require additional accessories (z.B., RC components, indicator lights).
  2. Quick Selection Recommendations
Application ScenarioHighly Recommended ModelsAlternative Modelle
Lighting Control SystemsChint NCH8-40/40 AC220V, Delixi CDCH8s40/40ABB ESB40-40N-06
Resistive Heating EquipmentSiemens 3RT1483-1BB40, Chint CJX2-4004Delixi CJX2s-4004
Motorsteuerung (≤7.5kW/400V)ABB A50-40-00, Chint NCH8-40/40Siemens 3RT2326-2BB40 (Auxiliary contacts required)
Smart Home/Small Distribution BoxesChint NCH8-40/40, Delixi CDCH8s40/40Schneider A9C20844 (Original)