1SDA064868R1 is the official order code for the ABB Tmax XT Series Molded Case Circuit Breaker (MCCB), corresponding to the full model:
XT4H 250 Ekip LS/I 4p F F
- Schlüsselparameter
| Artikel | Spezifikation |
| Serie | Tmax XT4 Series |
| Nennstrom | In = 250A |
| Polen | 4-Pole |
| Bruchkapazität | H-Typ: 50kA at 415V |
| Release Unit | Ekip LS/I electronic release |
| Schutzfunktionen | L (Überlast) + S (kurze Verzögerung) + ICH (instant) |
| Montage | Behoben / Frontanschluss |
| Nennspannung | 400/415V und |
- Produktpositionierung
Industrial-grade power distribution protection for power distribution panels, motor circuits, industrial equipment, and building power distribution
Mid-to-high end ABB MCCB with high reliability, suitable for automated power distribution systems
- Standard English Description (for tender / inquiry)
ABB Circuit Breaker MCCB Tmax XT4H250, 250A, 4P, 50Die, Ekip LS/I, Behoben, 1SDA064868R1
- Common Alternative / Similar Models in the Same Series (XT4 250A 4P)
1SDA064867R1: XT4H250 3P
1SDA064898R1: XT4L250 4P (lower breaking 36kA)
1SDA064878R1: XT4S250 4P (medium breaking 42kA)
Complete Model List, Brand Cross‑Reference & Order Code Manual
for ABB Tmax XT Series MCCBs
- Core Model System
1.1 Frame Specifications & Grundparameter
The Tmax XT series covers frame currents from 160A to 1600A across 7 frame sizes, suitable for various power‑rating distribution protections:
| Frame | Rahmenstrom | Klasse brechen | Polen | Nennspannung | Anwendung |
| XT1 | 160A | S/L/N/H | 3P/4P | 690V AC/500V DC | Small distribution, lighting circuits |
| XT2 | 160A | S/L/N/H/V | 3P/4P | 690V AC/500V DC | Industrial equipment, motor protection |
| XT3 | 250A | S/L/N/H | 3P/4P | 690V AC/500V DC | Building distribution, small‑medium factories |
| XT4 | 250A | S/L/N/H/V | 3P/4P | 690V AC/500V DC | Large motors, Industrielle Automatisierung |
| XT5 | 630A | L/N/H | 3P/4P | 690V AC/500V DC | Distribution rooms, large factories |
| XT6 | 1000A | L/N/H | 3P/4P | 690V AC/500V DC | Large power stations, heavy industry |
| XT7/XT7M | 1250A/1600A | L/N/H/M | 3P/4P | 690V AC/500V DC | Extra‑large industry, power grid support |
1.2 Model Coding Rule
XT[Frame][Klasse brechen][Rahmenstrom] [Release Type] [Nennstrom] [Polen] [Montage]
Beispiel: XT4H 250 Ekip LS/I 4p F F (Bestellcode: 1SDA064868R1)
1.3 Breaking Capacity Classes
| Klasse | Bruchkapazität (415V) | Anwendung |
| S | 36Die | Standard industrial environment |
| L | 42Die | General industrial loads |
| N | 50Die | Schwerindustrie, large motors |
| H | 85Die | High short‑circuit risk areas |
| V | 120kA/150kA | Extra‑large factories, grid side |
| M | 200Die | Extra‑high voltage distribution, special industry |
- Complete Model List by Frame
XT1 160A Series (Basic Type)
| Vollständiges Modell | Order Code | Freigeben | Nennstrom | Merkmale |
| XT1S 160 TMF 16-160 3P FF | 1SDA074621R1 | Thermal‑Magnetic Fixed | 16-160A | Economic, 36Die |
| XT1L 160 TMD 16-160 4P FF | 1SDA074658R1 | Thermal‑Magnetic Adjustable | 16-160A | Adjustable overload, 42Die |
| XT1N 160 Ekip LS 100 3P FF | 1SDA074725R1 | Electronic LS | 100A | Elektronischer Schutz, 50Die |
XT2 160A Series (High Performance)
| Vollständiges Modell | Order Code | Freigeben | Nennstrom | Merkmale |
| XT2L 160 TMD 32-320 4P FF | 1SDA067662R1 | Thermal‑Magnetic Adjustable | 32-320A | 120Die, motor protection |
| XT2V 160 Team LSIG 160 3P FF | 1SDA067721R1 | Electronic LSIG | 160A | 150Die, voller schutz |
| XT2N 160 Ekip C LSIG R63 FF 3P | 10152869 | Electronic LSIG + Comms | 63A | With communication, smart distribution |
XT3 250A Series
| Vollständiges Modell | Order Code | Freigeben | Nennstrom | Merkmale |
| XT3L 250 TMD 32-250 3P FF | 1SDA064821R1 | Thermal‑Magnetic Adjustable | 32-250A | 42Die, building distribution |
| XT3N 250 Ekip LS 200 4P FF | 1SDA064845R1 | Electronic LS | 200A | 50Die, Industrielle Automatisierung |
| XT3H 250 Team LSIG 250 3P FF | 1SDA064872R1 | Electronic LSIG | 250A | 85Die, heavy‑duty protection |
XT4 250A Series (Key Reference)
| Vollständiges Modell | Order Code | Freigeben | Nennstrom | Merkmale |
| XT4H 250 Ekip LS/I 4p FF | 1SDA064868R1 | Electronic LS/I | 250A | 50Die |
| XT4L 250 TMD 32-250 3P FF | 1SDA064867R1 | Thermal‑Magnetic Adjustable | 32-250A | 42Die, 3P |
| XT4V 250 Team LSIG 250 4P FF | 1SDA064898R1 | Electronic LSIG | 250A | 120Die |
XT5‑XT7 Series (High Power)
| Frame | Vollständiges Modell | Order Code | Nennstrom | Bruchkapazität | Anwendung |
| XT5 | XT5N 630 Team LSIG 630 3P FF | 1SDA100491R1 | 630A | 50Die | Distribution room, large factory |
| XT6 | XT6H 1000 Team LSIG 1000 4P FF | 1SDA100628R1 | 1000A | 85Die | Schwerindustrie, power station |
| XT7 | XT7M 1250 Team LSIG 1250 3P FF | 1SDA100755R1 | 1250A | 100Die | Extra‑large industry |
- Release Unit Types & Funktionen
| Freigeben | Englisch | Protection | Anwendung | Genauigkeit |
| TMF | Thermal-Magnetic Fixed | L + ICH | Beleuchtung, small motors | ±15% |
| TMD | Thermal-Magnetic Adjustable | L (adj) + ICH (adj) | Industrial equipment, Pumps | ±10 % |
| Ekip LS | Electronic LS | L + S | Distribution, Transformatoren | ±5% |
| Ekip LS/I | Electronic LS/I | L + S + ICH | Motor circuits, industrial loads | ±5% |
| Team LSIG | Electronic LSIG | L + S + ICH + G (Boden) | Empfindliche Lasten, Rechenzentren | ±3% |
| Ekip Touch | Digital Touch | Full + Communication | Smart distribution | ±2% |
- Main Brand Cross‑Reference
4.1 XT1/XT2 (160A)
| ABB | Schneider (NSX) | Siemens (3VA) | Eaton (IZM) | Chint (NXM) | Breaking |
| XT2N 160 Ekip LS 100 3P | NSX160N Micrologic 5.2E 100A | 3VA2160-5EF32-0AA0 | IZM91H160 TM-D 100A | NXM160S 100A | 50Die |
| XT2V 160 Team LSIG 160 4P | NSX160H Micrologic 6.3E 160A | 3VA2160-5FF32-0AA0 | IZM91V160 LSIG 160A | NXM160H 160A | 120Die |
4.2 XT3/XT4 (250A)
| ABB | Schneider (NSX) | Siemens (3VA) | Eaton (IZM) | Chint (NXM) | Order Code |
| XT4H 250 Ekip LS/I 4P | NSX250N Micrologic 5.3E 250A | 3VA3250-5EF32-0AA0 | IZM92H250 LS/I 250A | NXM250H 250A | 1SDA064868R1 |
| XT4L 250 TMD 250 3P | NSX250S Micrologic 2.3 250A | 3VA3250-5DF32-0AA0 | IZM92L250 TM-D 250A | NXM250S 250A | 1SDA064867R1 |
4.3 XT5‑XT7 (630A~1600A)
| ABB | Schneider (MTZ) | Siemens (3VA) | Eaton (IZM) | Breaking |
| XT5N 630 Team LSIG 630 3P | MTZ630N Micrologic 5.3E 630A | 3VA5630-5EF32-0AA0 | IZM93N630 LSIG 630A | 50Die |
| XT7M 1250 Team LSIG 1250 3P | MTZ1250H Micrologic 6.3E 1250A | 3VA61250-5FF32-0AA0 | IZM96M1250 LSIG 1250A | 100Die |
- Order Code Rules & Beispiele
5.1 Standard Format
1SDA[6 digits]R1 (R1 = standard version)
5.2 Common Order Codes
| Anwendung | ABB Full Model | Order Code |
| Motorsteuerung | XT4H 250 Ekip LS/I 4P FF | 1SDA064868R1 |
| Distribution | XT2N 160 Ekip LS 100 3P FF | 1SDA074725R1 |
| Building | XT3L 250 TMD 200 3P FF | 1SDA064821R1 |
| Data Center | XT2V 160 Team LSIG 160 4P FF | 1SDA067721R1 |
- Auswahl & Replacement Guide
6.1 Core Selection Principles
- Aktuelle Übereinstimmung: In ≥ 1.2 × load current; frame current ≥ 1.5 × In
- Bruchkapazität: Icu ≥ expected short‑circuit current (≥50kA recommended for industry)
- Protection: LS/I for motors; LS for distribution; LSIG for sensitive loads
- Montage: F = Fixed, D = Plug‑in, W = Drawout (FF = Fixed Front)
6.2 Replacement Steps
- Confirm frame + breaking class + release + Stangen
- Match equivalent frame from target brand
- Maintain breaking capacity ≥ original
- Verify mounting dimensions and connections