Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

Schneider Electric GV2-ME21C - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

NachrichtHandelsnachrichten

Schneider Electric GV2-ME21C

Schneider Electric GV2-ME21C is a 3-pole thermal-magnetic motor protection circuit breaker belonging to the TeSys GV2M series. Its core parameters cover electrical, Schutz, mechanical and environmental dimensions. Below is the structured and complete technical parameter sheet:

  1. Basic Electrical Parameters
ParameterelementWertStandard/Remarks
Nennbetriebsspannung (Ue)690V und (IEC 60947-2); 600V und (UL 508)Suitable for three-phase industrial circuits
Bemessungsisolationsspannung (Ui)690V undBenchmark for insulation safety
Rated Impulse Withstand Voltage (Uimp)6kVSurge resistance capability
Thermal Overload Setting Current (Und)17-23A10-level adjustable, suitable for motors of corresponding power
Nennbetriebsstrom (Ith)23AUpper limit of long-term current carrying capacity
Polzahl3-poleProtection for the main circuit of three-phase motors
Utilization CategoryAC-3 (IEC 60947-4-1); Category A (IEC 60947-2)Suitable for motor starting, stopping and operation
Control MethodPush-button type (handle operation)Convenient for closing, opening and trip testing
  1. Protection and Breaking Capacity
ParameterelementWertApplicable Conditions
Ultimate Short-Circuit Breaking Capacity (Icu)3kA@690V AC; 15kA@400/415V AC; 50kA@230/240V AC; 6kA@440V AC; 4kA@500V AC50/60Hz, konform mit IEC 60947-2
Service Short-Circuit Breaking Capacity (ICs)75% Icu@690V AC; 50% Icu@440V ACCan continue to be used after breaking
Magnetic Trip Current327-390A (ca. 15-17 times of Ir)Threshold for instantaneous short-circuit protection
Phase Loss ProtectionAvailableReliable tripping in case of three-phase unbalance
Thermal Overload Protection10-level ambient compensationSuitable for working conditions from -20℃ to +60℃
  1. Mechanical and Installation Parameters
ParameterelementWertStandard/Remarks
Montagemethode35mm standard DIN rail (EN 60715) / screw mountingDIN rail mounting is preferred; screw hole spacing is approx. 45mm
Mounting PositionHorizontal/VerticalFlatness error ≤ 0.5mm/m
Terminal TypeScrew-clamp typeSuitable for 2.5-4mm² copper core wires, torque 1.5-2.5N·m
Overall Dimensions (H×W×D)89mm×44.5mm×78.2mmCompact design, saving cabinet space
WeightApprox. 0.26kgLightweight, easy to install
Electrical Service Life100,000 OperationenDurability of closing and opening cycles
Mechanical Service Life200,000 OperationenReliability of the operating mechanism
  1. Environmental and Protection Parameters
ParameterelementWertStandard/Remarks
Ingress Protection Rating (IP)IP20 (main unit)IEC 60529, protection against finger touch
Mechanical Impact Resistance Rating (IK)IK04Resistance to mechanical impact
Betriebstemperatur-20℃~+60℃Wide temperature range for industrial applications
Lagertemperatur-40℃~+85℃No condensation or corrosive gas
CertificationsIEC, UL, CSA, CCC, EAC, Green Premium (RoHS/REACH)Compliant with multiple global regional standards
  1. Anwendbare Motorleistung (Referenz)
Voltage LevelAnwendbare Motorleistung
400/415V und9kW
500V und11kW
690V und18.5kW
  1. Supplementary Core Features
  2. The handle can be locked in the OFF position to prevent accidental closing and improve maintenance safety.
  3. Auxiliary contact modules such as GV2-AE11 (1NO+1NC) can be added for signal feedback or control circuit expansion.
  4. The terminals are suitable for multi-strand flexible wires (cold-pressed terminals are required) to avoid heating caused by loose wiring.

Vorher:

Nächste:

Hinterlassen Sie eine Antwort

Eine Nachricht hinterlassen