chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

Cross-Brand Model Comparison Table for Schneider A9C20844 Contactor - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

NoticiasNoticias comerciales

Cross-Brand Model Comparison Table for Schneider A9C20844 Contactor

  1. Baseline Core Parameters (A9C20844)
Elemento de parámetroBaseline Value
Brand/SeriesSchneider Acti9 iCT
Pole Number/Contacts4P 4NO (4-polo, 4 normalmente abierto)
Corriente nominal40A (AC-7a) / 15A (AC-7b)
Voltaje de la bobina220-240V AC 50Hz
Applicable Voltage400V y
Utilization CategoryAC-1/3/7a (Complies with IEC 60947-4-1/IEC 61095)
Método de montaje35mm Standard DIN Rail (Modular Design)
Dimensiones85mm*54mm*60mm, IP20 Protection Class
  1. Cross-Brand Model Comparison Table
MarcaSerieCorresponding ModelPole Number/ContactsCorriente nominalVoltaje de la bobinaMétodo de montajeMatching Notes
SchneiderActi9 iCTA9C20844 (Baseline)4P 4NO40A (AC-7a)220-240V yDIN RailOriginal baseline model
chintNCH8 (Modular)NCH8-40/40 AC220/230V4P 4NO40A220-230V yDIN RailPerfect match: Same pole number/contacts/current/mounting method, suitable for lighting/heating/motor loads
chintCJX2 (Universal)CJX2-4004 220V4P 4NO40A220V yBolt/DIN Rail OptionalIndustrial-grade alternative, consistent contact capacity, suitable for AC-3 operating conditions
DeliciosoCDCH8s (Household/Modular)CDCH8s40/40 220-240V4P 4NO40A220-240V yDIN RailSuitable for household/small industrial applications, similar size, ideal for lighting/heating loads
DeliciosoCJX2s (Universal)CJX2s-4004 220V4P 4NO40A220V yBolt/DIN Rail OptionalIndustrial-grade alternative, consistent performance parameters, suitable for motor control
TEJIDOA Series (Mounted Type)A50-40-00*220-230V4P 4NO40A220-230V yDIN RailDiseño modular, same parameter matching, suitable for AC-1/3 loads
TEJIDOESB (Mounted Type)ESB40-40N-06 230V4P 4NO40A230V yDIN RailIndustrial mounted type, suitable for lighting/heating loads, cumple con IEC 60947-4
siemensSIRIUS 3RT23 (4-polo)3RT2326-2BB404P 2NO+2NC (Configurable)40A220V yDIN RailRequires additional auxiliary contacts to achieve 4NO; suitable for motor loads (7.5kW/400V)
siemensSIRIUS 3RT14 (Resistive Load Dedicated)3RT1483-1BB404P 4NO40A220V yDIN RailDesigned specifically for AC-1 resistive loads, ideal for heating/lighting systems
LS ElectricGMC (Universal)GMC-40 40A 4P 4NO 220V4P 4NO40A220V yDIN RailKorean brand alternative, consistent parameters, suitable for industrial automation systems
OmronDILM (Modular)DILM40-10(4NO) 220V4P 4NO40A220V yDIN RailEuropean standard design, suitable for AC-3 motor control (7.5kW/400V)

III. Key Matching Guidelines

  1. Perfect Match Models (Highly Recommended)

Chint NCH8-40/40 AC220/230V: Fully identical structure to A9C20844, with 4P 4NO, 40A, DIN rail mounting, suitable for the same load types, and more cost-effective.

ABB A50-40-00 220-230V: Diseño modular, similar dimensions, meets full AC-1/3/7a operating conditions, suitable for projects with high brand compatibility requirements.

  1. Functional Match Models (Note Differences)

Siemens 3RT1483-1BB40: Optimized specifically for AC-1 resistive loads, not recommended for motor control with frequent start-stop cycles (AC-3).

Delixi CDCH8s40/40: Household series with a maximum rated voltage of 230V; derating or compatibility verification is required when used in 400V systems.

  1. Replacement Selection Precautions
  2. Contact Type Verification: Ensure the replacement model is 4NO to avoid control logic errors caused by configurations like 2NO+2NC.
  3. Utilization Category Matching:

Motor control: Must select models compatible with AC-3.

Lighting loads: Must meet AC-7a/7b (rated current 15-40A).

Resistive heating: AC-1 is sufficient for adaptation.

  1. Mounting and Dimensions:

Modular projects: Prioritize DIN rail-mounted models to ensure compatibility with distribution cabinet space.

Replacing existing A9C20844: Verify the width (54milímetros) to avoid interference during side-by-side installation of multiple units.

  1. Auxiliary Functions: For surge suppression or status indication, some replacement models require additional accessories (p.ej., RC components, indicator lights).
  2. Quick Selection Recommendations
Escenario de aplicaciónHighly Recommended ModelsModelos alternativos
Lighting Control SystemsChint NCH8-40/40 AC220V, Delixi CDCH8s40/40ABB ESB40-40N-06
Resistive Heating EquipmentSiemens 3RT1483-1BB40, Chint CJX2-4004Delixi CJX2s-4004
Control de motores (≤7.5kW/400V)ABB A50-40-00, Chint NCH8-40/40Siemens 3RT2326-2BB40 (Auxiliary contacts required)
Smart Home/Small Distribution BoxesChint NCH8-40/40, Delixi CDCH8s40/40Schneider A9C20844 (Original)

Anterior:

Próximo:

Deja una respuesta

Dejar un mensaje