ABB ACS355 series general machinery drive, 0.37 kilovatios / 0.5 caballos de fuerza, single-phase 200–240 V input, IP20 protection, rated output current 2.4 A. Suitable for speed control and energy-saving operation of small machinery.
1 Model Code Explanation
| Code Part | Meaning |
| ACS355 | ABB general machinery drive series |
| 01E | Protection class IP20, for installation in enclosed electrical cabinets |
| 02A4 | Rated output current 2.4 A |
| 2 | Single-phase 200–240 V AC (±10%), 50/60 Hz input |
2 Key Technical Data
| Artículo | Valor |
| Rated power | 0.37 kilovatios (0.5 caballos de fuerza) |
| Rated output current | 2.4 A (a 40°C) |
| Input voltage / frecuencia | Single-phase 200–240 V AC (±10%), 50/60 Hz |
| Output voltage / frecuencia | Three-phase 0–240 V AC, 0–500 Hz |
| Clase de protección | IP20 (indoor cabinet installation) |
| Control method | Scalar control (V/f), built-in application macros |
| Overload capability | 150% of rated current for 60 s; 180% para 2 s |
| Cooling method | Natural cooling |
| Dimensiones (Ancho×Alto×Profundidad) | 169×70×135 mm |
| Peso | Aprox.. 1.2 kilos |
| Order code | 3AUA0000058166 |
| EMC performance | Built-in EMC filter, compliant with EN 61800-3 |
3 Key Features
3.1 Flexible Control
Predefined application macros: constant torque, fan/pump, PID control, etc..
Local/remote control switching via keypad, terminals or fieldbus
Built-in PID controller for closed-loop flow, pressure, etc..
3.2 Reliable Protection
sobrecorriente, sobrecarga, sobretensión, subtensión, calentamiento excesivo, phase loss protection
Motor over-temperature protection (requires external PTC)
Short-circuit and earth-fault protection
3.3 Easy Operation
Compatible control panel with ACS350/510/550 series
Parameter copy function for fast commissioning
MTBF > 100,000 hours for continuous operation
4 Aplicaciones típicas
Small conveyors, maquinaria de embalaje
aficionados, zapatillas (small HVAC systems)
Mixers, centrifuges and small processing machines
Automatic doors, roller shutters
Medical equipment, instrumentos de laboratorio
Textile, printing and other light industrial machinery
5 Instalación & Commissioning Guidelines
5.1 Requisitos de instalación
Must be installed in an enclosed electrical cabinet
Temperatura ambiente: 0–40°C (derate 10% at 40–50°C)
Mount vertically, keep ≥ 100 mm clearance above and below for cooling
Avoid dust, oil, corrosive gases
Input protection: 10 A MCCB (curva C) or fuse recommended
5.2 Basic Commissioning Steps
- Pre-power check: Verify wiring (L1/N input, U/V/W output), terminal torque, proper earthing
- Inicialización de parámetros
Group 99: set motor rated voltage, actual, fuerza, velocidad
Select application macro (Estándar, PID, etc.)
- Control configuration
Local control: via control panel
Remote control: via DI terminals or optional Modbus RTU
- Operation test
Prueba sin carga: run at 5–10 Hz, check rotation and stability
prueba de carga: gradually apply load, verify current and temperature
Adjust acceleration/deceleration time (1–10 s recommended)
6 Cross-Brand Replacement Options (0.37 kilovatios, 1-fase 220 V, IP20)
| Marca | Modelo | Key Matching Points |
| Schneider | ATV12HU04M2 | 0.37 kilovatios, 1-fase 220 V, IP20, similar size |
| siemens | V20 6SL3210-5BB12-5UV1 | 0.37 kilovatios, 1-fase 220 V, IP20, integrated EMC |
| chint | NVF2-0.37/2 | 0.37 kilovatios, 1-fase 220 V, IP20, economical alternative |
| ABB alternative | ACS150-01E-02A4-2 | Same power range, more compact design |
7 Selection & Consejos de mantenimiento
7.1 Recommended Options
Braking function: optional braking resistor (75 Ω / 50 W recommended)
Communication: add RS485 module
Enhanced EMC: additional input EMC filter
7.2 Maintenance
Clean cooling channels every 6 meses
Check terminal torque annually
Avoid frequent starts/stops (≤ 20 times per day)
Storage temperature: -25°C a +60°C, dry environment
ABB ACS355-01E-02A4-2
Installation and Commissioning Manual
Overview: This manual provides complete instructions for safety, instalación, wiring, parameter setting and commissioning of the ACS355-01E-02A4-2 drive (0.37 kilovatios / 0.5 caballos de fuerza, single-phase 200–240 V) for general machinery speed control and energy saving.
1 Safety Instructions (Must Read)
1.1 Electrical Safety
Power-off procedure: Disconnect all power before installation, wiring or maintenance. Wait 5 minutes for internal capacitors to discharge.
Earthing: PE terminal must be reliably earthed (earth resistance ≤ 4 Ω)
Overcurrent protection: Install 10 A MCCB (curva C) or fuse on input side
Prueba de aislamiento: Only test motor cables; do NOT apply voltage to the drive itself
1.2 Mechanical Safety
Rotating parts (shaft, coupling, pulley) must be guarded
Mount vertically on solid surface to avoid vibration
Do not modify internal circuits or structures
1.3 Environmental Safety
Temperatura de funcionamiento: 0–40°C (derate 10% at 40–50°C)
Humedad: 5–95% RH, non-condensing
IP20: must be installed in enclosed cabinet
2 Product Overview and Model Identification
2.1 Model Explanation (ACS355-01E-02A4-2)
| Code | Meaning |
| ACS355 | ABB general machinery drive series |
| 01E | IP20, cabinet-mounted |
| 02A4 | Rated output current 2.4 A (40°C) |
| 2 | Single-phase 200–240 V AC, 50/60 Hz |
2.2 Especificaciones principales
| Artículo | Valor |
| Rated power | 0.37 kilovatios (0.5 caballos de fuerza) |
| Input voltage | Single-phase 200–240 V AC (±10%) |
| Output voltage | Three-phase 0–240 V AC |
| Output frequency | 0–500 Hz |
| Overload capacity | 150% para 60 s, 180% para 2 s |
| Cooling | Natural cooling |
| Dimensiones (Ancho×Alto×Profundidad) | 169×70×135 mm |
| Peso | Aprox.. 1.2 kilos |
| Order code | 3AUA0000058166 |
3 Installation Procedure
3.1 Preparation
- Unpack and inspect drive for damage
- Choose well-ventilated, dust-free location inside cabinet
- Herramientas: Phillips screwdriver (PH2), pelacables, herramienta que prensa, multímetro, insulation tape
3.2 Mounting
- Mount vertically on flat metal plate
- Keep ≥ 100 mm above/below, ≥ 50 mm left/right clearance
- Fix with M4 screws, tightening torque: 1.2–1.5 N·m
4 Electrical Wiring
4.1 Terminal Description (ACS355-01E Series)
| Section | Terminal | Descripción | Alambrado |
| Circuito de potencia | L1/N | Single-phase 200–240 V input | 1.5–2.5 mm² copper |
| educación física | Protective earth | ≥ 2.5 mm² copper | |
| UV/V/W | 3-phase output to motor | 1.5–2.5 mm² copper | |
| Circuito de control | DI1–DI3 | Digital inputs | 0.5–1.5 mm², max 50 metro |
| AI1/AI2 | Analog inputs (0–10 V / 0–20 mA) | Shielded twisted pair, max 100 metro | |
| AO1 | Analog output (0–20 mA) | Shielded twisted pair, max 100 metro | |
| +24V/GND | 24 V DC supply (max 100 mamá) | 0.5–1.5 mm² | |
| RS485+/– | Modbus RTU | Shielded twisted pair, max 1000 metro |
4.2 Pasos de cableado
- Power wiring: L1/N to mains, PE to earth, U/V/W to motor
- Control wiring (Standard macro example):
DI1: Forward (FWD), DI2: Reverse (REV), DI3: Reset
AI1: Speed reference (0–10 V)
- Check torque, insulation, and phase sequence
5 Parameter Settings
5.1 Keypad Functions
▶/■: Comenzar / Detener
▲/▼: Adjust value
INGRESAR: Confirm
ESC: Back
LOC/REM: Local / Remote
5.2 Quick Motor Settings (Group 99)
| Parámetro | Nombre | Setting | Nota |
| 9901 | Language | Chinese / English | User choice |
| 9902 | Application macro | 1 (Estándar) | General use |
| 9903 | Motor type | 1 (Asynchronous) | Standard induction motor |
| 9904 | Motor rated power | 0.37 kilovatios | From nameplate |
| 9905 | Motor rated voltage | 220/230/240 V | From nameplate |
| 9906 | Motor rated current | Motor nominal | Typically ~2.1 A |
| 9907 | Motor rated frequency | 50/60 Hz | From nameplate |
| 9908 | Motor rated speed | Motor nominal | ~1400–1450 rpm |
| 9909 | Number of motor poles | 4 | Standard for 0.37 kilovatios |
| 9910 | Control mode | 1 (V/f) | Scalar control |
5.3 Common Application Parameters
| Group | Parámetro | Nombre | Recommended Value |
| 10 | 1001 | Max frequency | 50/60 Hz |
| 1002 | Min frequency | 0 Hz | |
| 20 | 2001 | Acceleration time | 3–10 s |
| 2002 | Deceleration time | 3–10 s | |
| 21 | 2101 | Acc/dec type | 1 (Linear) |
| 40 | 4001 | DI1 function | 1 (FWD) |
| 4002 | DI2 function | 2 (REV) | |
| 4003 | DI3 function | 9 (REINICIAR) | |
| 50 | 5001 | AI1 type | 1 (0–10 V) |
| 5002 | AI1 minimum | 0% | |
| 5003 | AI1 maximum | 100% | |
| 16 | 1607 | Save parameters | 1 |
6 Commissioning Flow
6.1 Pre-Power Check
Correct power and control wiring
Motor and drive area clear
Cabinet ventilation OK
Input voltage: 200–240 V single-phase
6.2 First Power-Up
Close MCCB, display shows REM or LOC
Check for fault codes
Verify Group 99 motor parameters
6.3 Motor Identification (Opcional)
Set 9910 = 2 (ID Run)
Press ENTER; drive runs motor briefly
Completed when shown COMPLETE
6.4 No-Load Test
Switch to LOCAL
Run at 5 Hz, check rotation
Increase to rated frequency, check noise and vibration
6.5 Prueba de carga
Switch to REMOTE
Control speed via AI1
Check output current ≤ 2.4 A
Adjust acc/dec to avoid overcurrent
Test protection functions
7 Solución de problemas
7.1 Códigos de falla comunes
| Fault | Descripción | Cause | Remedy |
| OVERCURRENT | sobrecorriente | Motor overload, cortocircuito | Check load, motor, parámetros |
| OVERVOLTAGE | Sobretensión | High mains, fast deceleration | Comprobar voltaje, increase dec time |
| UNDERVOLTAGE | Subtensión | Low supply, loose connection | Check mains and wiring |
| OVERTEMP | Overheating | High temp, blocked cooling | Improve ventilation, clean heatsink |
| MOTOR OVERLOAD | Motor overload | Excessive load | Check application, reducir la carga |
| FAULT RESET | Trip reset required | Fault occurred | Fix cause, reset via DI3 or keypad |
7.2 Typical Issues
| Symptom | Cause | Solución |
| Motor does not start | Wrong LOC/REM, missing DI signal | Check mode, wiring and parameters |
| Unstable speed | AI noise, poor parameters | Use shielded cable, adjust filtering |
| Communication failure | Wrong settings, bad wiring | Check Group 98, RS485, termination |
8 Maintenance
8.1 Mantenimiento de rutina
Clean cooling channels every 6 meses
Check terminal torque annually
Log operating current and temperature
8.2 Long-Term Storage
Temperatura: -25°C a +60°C
Dry, ventilated environment
Power on for 1 hour every 6 meses
9 Appendix: Options and Replacements
9.1 Recommended Options
Braking resistor: 100 Ω / 50 W.
EMC filter
RS485 Modbus RTU module
Shielded cable for control wiring
9.2 Cross-Brand Alternatives (0.37 kilovatios, 1-fase 220 V, IP20)
| Marca | Modelo | Matching Features |
| Schneider | ATV12HU04M2 | 0.37 kilovatios, 1-fase 220 V, IP20 |
| siemens | V20 6SL3210-5BB12-5UV1 | 0.37 kilovatios, 1-fase 220 V, IP20 |
| chint | NVF2-0.37/2 | 0.37 kilovatios, 1-fase 220 V, IP20 |
| TEJIDO | ACS150-01E-02A4-2 | Direct same-power replacement |