Technical File of Chint CJX2-6511 + NR2-93
Chint CJX2-6511 + NR2-93 is a standard electromagnetic starter combination, consisting of a CJX2-6511 contactor de CA and an NR2-93 thermal overload relay. It is mainly used for remote control, overload and phase failure protection of AC motors, and is widely applied in industrial automation and electrical control systems.
- Interpretación del modelo
| Component | Modelo | Meaning |
| contactor | CJX2-6511 | CJX2: código de serie (based on Schneider LC1-D technology) |
| 65: Rated current of main contacts is 65A | ||
| 11: Auxiliary contact configuration (1 normalmente abierto + 1 normalmente cerrado) | ||
| Relé de sobrecarga térmica | NR2-93 | NR2: código de serie |
| 93: Frame size is 93A (adjustable current range: 23-93A) | ||
| /z: With manual/automatic reset selection (standard configuration) |
- Parámetros técnicos básicos
- CJX2-6511 AC Contactor
| Elemento de parámetro | Specification Value | Observaciones |
| Rated Operational Voltage | 690V y | 50/60Hz |
| Rated Operational Current | 65A | Under AC-3 utilization category and 380V condition |
| Tensión nominal de aislamiento | 690V | – |
| Rated Impulse Withstand Voltage | 6kV | – |
| Control Coil Voltage | 24V/36V/110V/220V/380V AC | Opcional, 220V/380V are common choices |
| Main Contact Configuration | 3NO (3 Normalmente abierto) | For making and breaking the main circuit |
| Configuración de contacto auxiliar | 1NO + 1CAROLINA DEL NORTE | For interlocking of control circuits |
| Vida mecánica | ≥ 10 millones de operaciones | – |
| Vida eléctrica | ≥ 1 millones de operaciones | Under AC-3 utilization category |
| Método de montaje | Screw mounting / 35mm standard DIN rail | Compatible with DIN rail |
| Temperatura ambiente | -5℃ ~ +40℃ | 24-hour average temperature ≤ +35℃ |
- NR2-93 Thermal Overload Relay
| Elemento de parámetro | Specification Value | Observaciones |
| Rated Operational Voltage | 690V y | 50/60Hz |
| Frame Size | 93A | – |
| Adjustable Current Range | 23-32A, 30-40A, 37-50A | Multiple specifications available, matched with 65A contactor |
| 48-65A, 55-70A, 63-80A | ||
| 80-93A | ||
| Clase de viaje | 10A | Overload protection characteristic (tripping time is 2-10 seconds at 10 veces la corriente nominal) |
| Función de protección | Protección contra sobrecarga + phase failure protection | Three-phase bimetallic strip structure |
| Método de reinicio | Manual/automatic selectable | Standard configuration is /Z type |
| Método de montaje | Plug-in mounting with CJX2 contactor | Can be mounted independently |
| Ambient Temperature Compensation | Yes | Ensures protection accuracy under different ambient temperatures |
III. Functional Features
- Features of CJX2-6511 Contactor
High-performance Contacts: Silver alloy contacts with excellent conductivity, strong arc erosion resistance and long service life.
Low-noise Design: Optimized electromagnetic system to reduce noise during pull-in and release.
Estructura modular: Expandable auxiliary contacts for flexible installation.
Safe and Reliable: Cumple con GB/T 14048.4 and IEC/EN 60947-4-1 estándares, with short-circuit protection coordination capability.
Amplia adaptabilidad de voltaje: Control coil is compatible with multiple voltage levels to meet the requirements of different control circuits.
- Features of NR2-93 Thermal Overload Relay
Comprehensive Protection: Provides both overload and phase failure protection to prevent motor burnout due to phase loss operation.
Compensación de temperatura: Maintains stable protection characteristics when ambient temperature changes.
Action Indication: Clear trip status indication for easy fault troubleshooting.
Flexible Reset: Manual/automatic reset selection to adapt to different control requirements.
Plug-in Mounting: Perfectly matched with CJX2 contactor for quick installation and space saving.
- Advantages of the Combined System
Integrated Control and Protection: The contactor is responsible for circuit on/off and motor starting, while the thermal overload relay provides overload/phase failure protection, forming a complete control and protection unit.
Standardized Design: Complies with international standards and can be seamlessly integrated with other electrical components.
Easy Maintenance: Modular structure allows easy component replacement and reduces maintenance costs.
- Ámbito de aplicación
- Control de motores: Suitable for frequent starting, stopping, forward and reverse rotation control of three-phase AC motors with power below 30kW (380V).
- Equipos industriales: General machinery such as fans, bombas de agua, compresores, conveyors and machine tools.
- Building Electrical Engineering: Central air conditioning systems, fire pumps and elevator control systems.
- Other Applications: Long-distance controlled power transmission and distribution systems, and electrical circuits requiring overload protection.
- Recomendaciones de selección
- Basic Selection Principles
Contactor Selection: The rated current of main contacts shall be ≥ 1.2-1.5 veces la corriente nominal del motor (inductive load).
Thermal Relay Selection: The adjustable current range shall cover the rated current of the motor (usually set to 0.95-1.05 veces la corriente nominal del motor).
Voltaje de la bobina: Selected according to the power supply of the control circuit, 220V or 380V AC are commonly used.
- Motor Power Matching Table (380V)
| Motor Power | Corriente nominal | Recommended Thermal Relay Specification | Escenario de aplicación |
| 18.5KW | 37A | NR2-93/Z 37-50A | General load |
| 22KW | 44A | NR2-93/Z 37-50A | General load |
| 30KW | 60A | NR2-93/Z 48-65A | Heavy load, frequent starting |
| 37KW | 74A | NR2-93/Z 63-80A | Derating required (65A contactor is close to the limit) |
- Precauciones de instalación y uso
Mounting Direction: The contactor and thermal overload relay can be installed horizontally or vertically, with an inclination angle not exceeding 5°.
Especificaciones de cableado: The terminals of the main circuit shall be tightened to avoid heating; the cross-sectional area of the control circuit wire shall be ≥ 1.5mm².
Requisitos ambientales: Evite la instalación en lugares húmedos., dusty or corrosive gas environments; altitude ≤ 2000m.
Protection Coordination: Must be used with circuit breakers to provide short-circuit protection.
- Solución de problemas
| Fenómeno de falla | Posibles causas | Soluciones |
| El contactor no logra entrar | 1. Low coil voltage/phase loss | 1. Check the power supply voltage to ensure it is within 10% del valor nominal |
| 2. Burned-out coil | 2. Measure the coil resistance and replace the coil if abnormal | |
| 3. Atasco mecánico | 3. Check the iron core and mechanism to remove foreign objects | |
| 4. Open circuit in control circuit | 4. Check the wiring of the control circuit and repair the open circuit | |
| Loud noise after contactor pulls in | 1. Oil stain/dust on iron core end face | 1. Clean the iron core end face |
| 2. Broken short-circuit ring | 2. Replace the iron core or contactor | |
| 3. Voltage fluctuation | 3. Stabilize the power supply voltage | |
| Contact overheating/ablation | 1. Cableado suelto | 1. Tighten the wiring terminals |
| 2. Severe contact wear | 2. Replace the contacts or contactor | |
| 3. Sobrecarga | 3. Check the load and replace with a contactor of larger capacity if necessary | |
| 4. High operating frequency | 4. Reduce the operating frequency or select a contactor suitable for AC-4 utilization category | |
| Frequent tripping of thermal overload relay | 1. Excessively small adjustable current | 1. Adjust the adjustable current to the rated current of the motor |
| 2. Motor overload | 2. Check the motor load and eliminate faults | |
| 3. Phase loss operation | 3. Check the wiring of the main circuit and repair the phase loss | |
| 4. Temperatura ambiente alta | 4. Improve ventilation conditions and reduce the ambient temperature | |
| Thermal overload relay fails to trip | 1. Excessively large adjustable current | 1. Adjust the adjustable current |
| 2. Elemento calefactor dañado | 2. Replace the thermal overload relay | |
| 3. Jammed trip mechanism | 3. Check and repair the trip mechanism |
VII. Substitution and Compatibility
| Component | Chint Model | Compatible/Alternative Model | Observaciones |
| contactor | CJX2-6511 | Schneider LC1-D6511 | Compatible in mounting dimensions and electrical parameters |
| Delixi CDM1-6511 | |||
| ABB A16-30-11 | |||
| Relé de sobrecarga térmica | NR2-93 | Schneider LRD3363 | Similar protection characteristics; attention shall be paid to matching of mounting methods |
| Delixi JR28-93 | |||
| ABB TA25DU |
VIII. Resumen
Chint CJX2-6511 + NR2-93 is a cost-effective and highly reliable motor control and protection solution, especially suitable for frequent starting and protection applications of small and medium-sized motors. Its modular design, standardized interface and comprehensive protection functions make it an ideal choice in the field of industrial automation. Durante la selección, it is necessary to choose the appropriate adjustable current specification of the thermal overload relay and the coil voltage of the contactor according to the motor power, rated current and control requirements.
Service Life Details of Chint CJX2-6511 + NR2-93
The service life of the Chint CJX2-6511 + NR2-93 combination shall be comprehensively evaluated from three dimensions: mechanical life (no-load operation times), electrical life (on-load operation times) and actual service life, which is also affected by various factors such as operating conditions and maintenance level.
- Officially Nominal Life Parameters
- CJX2-6511 AC Contactor
| Life Type | Standard Value | Test Condition |
| Vida mecánica | ≥ 10 millones de operaciones | Operation under no-load and rated coil voltage |
| Vida eléctrica | ≥ 600,000 operaciones (AC-3 utilization category) | Controlling three-phase asynchronous motor under 380V and rated operating current of 65A |
| Vida eléctrica | ≥ 100,000 operaciones (AC-4 utilization category) | Frequent starting/reversing/braking conditions with larger current |
- NR2-93 Thermal Overload Relay
| Life Type | Standard Value | Test Condition |
| Vida mecánica | ≥ 1 millones de operaciones | Operation under no-load and rated control voltage |
| Vida eléctrica | ≥ 100,000 operaciones | Operation of control circuit under rated working conditions |
| Heating Element Life | Long-term stable (acerca de 10 años) | Normal use without frequent overload tripping |
- Key Factors Affecting Service Life
- Factors Affecting Contactor Life
Factor Influence Mechanism Influence Degree Frecuencia de funcionamiento Frequent operation accelerates mechanical wear and contact ablation Alto (if the frequency is doubled, the life may be halved) Tipo de carga The life of AC-4 load (frequent starting/reversing) is 60-80% lower than that of AC-3 load Alto Fluctuación de voltaje Overvoltage causes coil overheating, and undervoltage causes contact bouncing Medium-High Condiciones ambientales Temperatura > 40℃, humedad, dust and corrosive gas accelerate aging Medio Método de montaje Non-vertical installation (inclination > 5°) affects heat dissipation and mechanical action Bajo Maintenance Level Regular cleaning and terminal tightening can extend the service life Medio Factors Affecting Thermal Overload Relay Life
| Factor | Influence Mechanism | Influence Degree |
| Overload Frequency | Frequent overload tripping causes fatigue of bimetallic strips | Alto |
| Adjustable Current | Excessively small adjustable current leads to unnecessary tripping | Medio |
| Temperatura ambiente | High temperature affects protection accuracy and component life | Medio |
| Control Circuit Voltage | Overvoltage causes ablation of control contacts | Bajo |
III. Life Estimation in Practical Application
- Calculation of Actual Contactor Life (Ejemplo)
Assumed working conditions: AC-3 utilization category, 100 operations per day, 300 working days per year
Theoretical electrical life: 600,000 operaciones
Annual operation times: 100 operations/day × 300 days = 30,000 operations/year
Expected service life: 600,000 ÷ 30,000 = 20 años (ideal working conditions)
If it is AC-4 utilization category with 200 operations per day:
Theoretical electrical life: 100,000 operaciones
Annual operation times: 200 × 300 = 60,000 operations/year
Expected service life: 100,000 ÷ 60,000 = about 1.7 años (severe working conditions)
- Estimation of Actual Thermal Overload Relay Life
Control Contact Life: With 50 operations per day, the theoretical 100,000 operations can last for about 5.5 años.
Heating Element Life: Under normal use (less than 5 overload trips per month), it can work stably for 8-10 años.
Overall Life: Usually determined by the life of the contactor; the thermal overload relay can be replaced as a wearing part.
- Practical Suggestions for Extending Service Life
- Selection Optimization
The rated current of the contactor shall be ≥ 1.2-1.5 veces la corriente nominal del motor.
For frequent starting/reversing conditions, select AC-4 dedicated contactors or use them with derating.
- Installation and Usage Specifications
Install vertically with good ventilation; control the ambient temperature within -5℃ ~ +40℃.
Keep the control coil voltage stable within ±10% of the rated value.
Set the adjustable current of the thermal overload relay to 0.95-1.05 veces la corriente nominal del motor.
- Maintenance Measures
Regularly clean the contacts and iron core to remove dust and oil stains.
Check the wiring terminals to prevent loosening and heating.
After 3-5 years of operation of the contactor, the contacts and coil can be replaced.
When the thermal overload relay trips frequently, check the motor load and main circuit.
- Resumen
Under standard working conditions (AC-3, 100 operations per day), the electrical life of the contactor in the Chint CJX2-6511 + NR2-93 combination is about 20 años, and the mechanical life far exceeds the actual service demand; the overall life of the thermal overload relay is about 10 años. The actual service life mainly depends on the operating frequency, load type and maintenance level, and may be shortened to 1-2 years under severe working conditions. Through reasonable selection, standardized use and regular maintenance, the service life of the equipment can be effectively extended and the replacement cost can be reduced.