Chint CJX2-6511+NR2-93

ComponentModeloMeaning
contactorCJX2-6511CJX2: código de serie (based on Schneider LC1-D technology)
65: Rated current of main contacts is 65A
11: Auxiliary contact configuration (1 normalmente abierto + 1 normalmente cerrado)
Relé de sobrecarga térmicaNR2-93NR2: código de serie
93: Frame size is 93A (adjustable current range: 23-93A)
/z: With manual/automatic reset selection (standard configuration)

  • Detalles del producto

Technical File of Chint CJX2-6511 + NR2-93

Chint CJX2-6511 + NR2-93 is a standard electromagnetic starter combination, consisting of a CJX2-6511 contactor de CA and an NR2-93 thermal overload relay. It is mainly used for remote control, overload and phase failure protection of AC motors, and is widely applied in industrial automation and electrical control systems.

  1. Interpretación del modelo
ComponentModeloMeaning
contactorCJX2-6511CJX2: código de serie (based on Schneider LC1-D technology)
65: Rated current of main contacts is 65A
11: Auxiliary contact configuration (1 normalmente abierto + 1 normalmente cerrado)
Relé de sobrecarga térmicaNR2-93NR2: código de serie
93: Frame size is 93A (adjustable current range: 23-93A)
/z: With manual/automatic reset selection (standard configuration)
  1. Parámetros técnicos básicos
  2. CJX2-6511 AC Contactor
Elemento de parámetroSpecification ValueObservaciones
Rated Operational Voltage690V y50/60Hz
Rated Operational Current65AUnder AC-3 utilization category and 380V condition
Tensión nominal de aislamiento690V
Rated Impulse Withstand Voltage6kV
Control Coil Voltage24V/36V/110V/220V/380V ACOpcional, 220V/380V are common choices
Main Contact Configuration3NO (3 Normalmente abierto)For making and breaking the main circuit
Configuración de contacto auxiliar1NO + 1CAROLINA DEL NORTEFor interlocking of control circuits
Vida mecánica 10 millones de operaciones
Vida eléctrica 1 millones de operacionesUnder AC-3 utilization category
Método de montajeScrew mounting / 35mm standard DIN railCompatible with DIN rail
Temperatura ambiente-5℃ ~ +40℃24-hour average temperature ≤ +35℃
  1. NR2-93 Thermal Overload Relay
Elemento de parámetroSpecification ValueObservaciones
Rated Operational Voltage690V y50/60Hz
Frame Size93A
Adjustable Current Range23-32A, 30-40A, 37-50AMultiple specifications available, matched with 65A contactor
48-65A, 55-70A, 63-80A
80-93A
Clase de viaje10AOverload protection characteristic (tripping time is 2-10 seconds at 10 veces la corriente nominal)
Función de protecciónProtección contra sobrecarga + phase failure protectionThree-phase bimetallic strip structure
Método de reinicioManual/automatic selectableStandard configuration is /Z type
Método de montajePlug-in mounting with CJX2 contactorCan be mounted independently
Ambient Temperature CompensationYesEnsures protection accuracy under different ambient temperatures

III. Functional Features

  1. Features of CJX2-6511 Contactor

High-performance Contacts: Silver alloy contacts with excellent conductivity, strong arc erosion resistance and long service life.

Low-noise Design: Optimized electromagnetic system to reduce noise during pull-in and release.

Estructura modular: Expandable auxiliary contacts for flexible installation.

Safe and Reliable: Cumple con GB/T 14048.4 and IEC/EN 60947-4-1 estándares, with short-circuit protection coordination capability.

Amplia adaptabilidad de voltaje: Control coil is compatible with multiple voltage levels to meet the requirements of different control circuits.

  1. Features of NR2-93 Thermal Overload Relay

Comprehensive Protection: Provides both overload and phase failure protection to prevent motor burnout due to phase loss operation.

Compensación de temperatura: Maintains stable protection characteristics when ambient temperature changes.

Action Indication: Clear trip status indication for easy fault troubleshooting.

Flexible Reset: Manual/automatic reset selection to adapt to different control requirements.

Plug-in Mounting: Perfectly matched with CJX2 contactor for quick installation and space saving.

  1. Advantages of the Combined System

Integrated Control and Protection: The contactor is responsible for circuit on/off and motor starting, while the thermal overload relay provides overload/phase failure protection, forming a complete control and protection unit.

Standardized Design: Complies with international standards and can be seamlessly integrated with other electrical components.

Easy Maintenance: Modular structure allows easy component replacement and reduces maintenance costs.

  1. Ámbito de aplicación
  2. Control de motores: Suitable for frequent starting, stopping, forward and reverse rotation control of three-phase AC motors with power below 30kW (380V).
  3. Equipos industriales: General machinery such as fans, bombas de agua, compresores, conveyors and machine tools.
  4. Building Electrical Engineering: Central air conditioning systems, fire pumps and elevator control systems.
  5. Other Applications: Long-distance controlled power transmission and distribution systems, and electrical circuits requiring overload protection.
  6. Recomendaciones de selección
  7. Basic Selection Principles

Contactor Selection: The rated current of main contacts shall be ≥ 1.2-1.5 veces la corriente nominal del motor (inductive load).

Thermal Relay Selection: The adjustable current range shall cover the rated current of the motor (usually set to 0.95-1.05 veces la corriente nominal del motor).

Voltaje de la bobina: Selected according to the power supply of the control circuit, 220V or 380V AC are commonly used.

  1. Motor Power Matching Table (380V)
Motor PowerCorriente nominalRecommended Thermal Relay SpecificationEscenario de aplicación
18.5KW37ANR2-93/Z 37-50AGeneral load
22KW44ANR2-93/Z 37-50AGeneral load
30KW60ANR2-93/Z 48-65AHeavy load, frequent starting
37KW74ANR2-93/Z 63-80ADerating required (65A contactor is close to the limit)
  1. Precauciones de instalación y uso

Mounting Direction: The contactor and thermal overload relay can be installed horizontally or vertically, with an inclination angle not exceeding 5°.

Especificaciones de cableado: The terminals of the main circuit shall be tightened to avoid heating; the cross-sectional area of the control circuit wire shall be ≥ 1.5mm².

Requisitos ambientales: Evite la instalación en lugares húmedos., dusty or corrosive gas environments; altitude ≤ 2000m.

Protection Coordination: Must be used with circuit breakers to provide short-circuit protection.

  1. Solución de problemas
Fenómeno de fallaPosibles causasSoluciones
El contactor no logra entrar1. Low coil voltage/phase loss1. Check the power supply voltage to ensure it is within 10% del valor nominal
2. Burned-out coil2. Measure the coil resistance and replace the coil if abnormal
3. Atasco mecánico3. Check the iron core and mechanism to remove foreign objects
4. Open circuit in control circuit4. Check the wiring of the control circuit and repair the open circuit
Loud noise after contactor pulls in1. Oil stain/dust on iron core end face1. Clean the iron core end face
2. Broken short-circuit ring2. Replace the iron core or contactor
3. Voltage fluctuation3. Stabilize the power supply voltage
Contact overheating/ablation1. Cableado suelto1. Tighten the wiring terminals
2. Severe contact wear2. Replace the contacts or contactor
3. Sobrecarga3. Check the load and replace with a contactor of larger capacity if necessary
4. High operating frequency4. Reduce the operating frequency or select a contactor suitable for AC-4 utilization category
Frequent tripping of thermal overload relay1. Excessively small adjustable current1. Adjust the adjustable current to the rated current of the motor
2. Motor overload2. Check the motor load and eliminate faults
3. Phase loss operation3. Check the wiring of the main circuit and repair the phase loss
4. Temperatura ambiente alta4. Improve ventilation conditions and reduce the ambient temperature
Thermal overload relay fails to trip1. Excessively large adjustable current1. Adjust the adjustable current
2. Elemento calefactor dañado2. Replace the thermal overload relay
3. Jammed trip mechanism3. Check and repair the trip mechanism

VII. Substitution and Compatibility

ComponentChint ModelCompatible/Alternative ModelObservaciones
contactorCJX2-6511Schneider LC1-D6511Compatible in mounting dimensions and electrical parameters
Delixi CDM1-6511
ABB A16-30-11
Relé de sobrecarga térmicaNR2-93Schneider LRD3363Similar protection characteristics; attention shall be paid to matching of mounting methods
Delixi JR28-93
ABB TA25DU

VIII. Resumen

Chint CJX2-6511 + NR2-93 is a cost-effective and highly reliable motor control and protection solution, especially suitable for frequent starting and protection applications of small and medium-sized motors. Its modular design, standardized interface and comprehensive protection functions make it an ideal choice in the field of industrial automation. Durante la selección, it is necessary to choose the appropriate adjustable current specification of the thermal overload relay and the coil voltage of the contactor according to the motor power, rated current and control requirements.

Service Life Details of Chint CJX2-6511 + NR2-93

The service life of the Chint CJX2-6511 + NR2-93 combination shall be comprehensively evaluated from three dimensions: mechanical life (no-load operation times), electrical life (on-load operation times) and actual service life, which is also affected by various factors such as operating conditions and maintenance level.

  1. Officially Nominal Life Parameters
  2. CJX2-6511 AC Contactor
Life TypeStandard ValueTest Condition
Vida mecánica 10 millones de operacionesOperation under no-load and rated coil voltage
Vida eléctrica 600,000 operaciones (AC-3 utilization category)Controlling three-phase asynchronous motor under 380V and rated operating current of 65A
Vida eléctrica 100,000 operaciones (AC-4 utilization category)Frequent starting/reversing/braking conditions with larger current
  1. NR2-93 Thermal Overload Relay
Life TypeStandard ValueTest Condition
Vida mecánica 1 millones de operacionesOperation under no-load and rated control voltage
Vida eléctrica 100,000 operacionesOperation of control circuit under rated working conditions
Heating Element LifeLong-term stable (acerca de 10 años)Normal use without frequent overload tripping
  1. Key Factors Affecting Service Life
  2. Factors Affecting Contactor Life
  1. FactorInfluence MechanismInfluence Degree
    Frecuencia de funcionamientoFrequent operation accelerates mechanical wear and contact ablationAlto (if the frequency is doubled, the life may be halved)
    Tipo de cargaThe life of AC-4 load (frequent starting/reversing) is 60-80% lower than that of AC-3 loadAlto
    Fluctuación de voltajeOvervoltage causes coil overheating, and undervoltage causes contact bouncingMedium-High
    Condiciones ambientalesTemperatura > 40℃, humedad, dust and corrosive gas accelerate agingMedio
    Método de montajeNon-vertical installation (inclination > 5°) affects heat dissipation and mechanical actionBajo
    Maintenance LevelRegular cleaning and terminal tightening can extend the service lifeMedio

    Factors Affecting Thermal Overload Relay Life

FactorInfluence MechanismInfluence Degree
Overload FrequencyFrequent overload tripping causes fatigue of bimetallic stripsAlto
Adjustable CurrentExcessively small adjustable current leads to unnecessary trippingMedio
Temperatura ambienteHigh temperature affects protection accuracy and component lifeMedio
Control Circuit VoltageOvervoltage causes ablation of control contactsBajo

III. Life Estimation in Practical Application

  1. Calculation of Actual Contactor Life (Ejemplo)

Assumed working conditions: AC-3 utilization category, 100 operations per day, 300 working days per year

Theoretical electrical life: 600,000 operaciones

Annual operation times: 100 operations/day × 300 days = 30,000 operations/year

Expected service life: 600,000 ÷ 30,000 = 20 años (ideal working conditions)

If it is AC-4 utilization category with 200 operations per day:

Theoretical electrical life: 100,000 operaciones

Annual operation times: 200 × 300 = 60,000 operations/year

Expected service life: 100,000 ÷ 60,000 = about 1.7 años (severe working conditions)

  1. Estimation of Actual Thermal Overload Relay Life

Control Contact Life: With 50 operations per day, the theoretical 100,000 operations can last for about 5.5 años.

Heating Element Life: Under normal use (less than 5 overload trips per month), it can work stably for 8-10 años.

Overall Life: Usually determined by the life of the contactor; the thermal overload relay can be replaced as a wearing part.

  1. Practical Suggestions for Extending Service Life
  2. Selection Optimization

The rated current of the contactor shall be ≥ 1.2-1.5 veces la corriente nominal del motor.

For frequent starting/reversing conditions, select AC-4 dedicated contactors or use them with derating.

  1. Installation and Usage Specifications

Install vertically with good ventilation; control the ambient temperature within -5℃ ~ +40℃.

Keep the control coil voltage stable within ±10% of the rated value.

Set the adjustable current of the thermal overload relay to 0.95-1.05 veces la corriente nominal del motor.

  1. Maintenance Measures

Regularly clean the contacts and iron core to remove dust and oil stains.

Check the wiring terminals to prevent loosening and heating.

After 3-5 years of operation of the contactor, the contacts and coil can be replaced.

When the thermal overload relay trips frequently, check the motor load and main circuit.

  1. Resumen

Under standard working conditions (AC-3, 100 operations per day), the electrical life of the contactor in the Chint CJX2-6511 + NR2-93 combination is about 20 años, and the mechanical life far exceeds the actual service demand; the overall life of the thermal overload relay is about 10 años. The actual service life mainly depends on the operating frequency, load type and maintenance level, and may be shortened to 1-2 years under severe working conditions. Through reasonable selection, standardized use and regular maintenance, the service life of the equipment can be effectively extended and the replacement cost can be reduced.