FX2N-48ER is an I/O expansion unit for Mitsubishi MELSEC-F series FX2N PLCs.
It features 24-point DC24V input + 24-point relay output, with built-in power supply, and can directly expand I/O points for small and medium-sized automation control systems.
- Desglose del modelo & Definición
| Código | Significado | Descripción |
| FX2N | Serie | Mitsubishi high-performance compact PLC series, supporting rich expansion and network communication |
| 48 | Total I/O points | 24 inputs + 24 outputs, total 48 mixed I/O |
| E | Expansion type | Must be used with a main unit; built-in power supply for field devices |
| R | Output type | Salida de relé, suitable for AC/DC loads with strong load capacity |
- Key Specifications
Input: 24 points DC24V, sink/source common, response time approx. 10EM
Output: 24 points relay, 2A/AC250V or 2A/DC30V per point; max 8A per common terminal
Fuerza: AC100–240V wide range, 50/60Hz; 460mA DC24V for field devices
Físico: Weight approx. 0.85kilos; Dimensions 182×90×87 mm (Ancho×Alto×Profundidad), DIN rail mountable
Expansión: Arriba a 7 expansion units for FX2N series, max 256 I/O points
- Common Versions
| Suffix | Region | Difference |
| -ES/UL | Europe / North America | CE/UL certified, DC24V input, screw terminals |
| -UA1/UL | North America | Supports AC110V input, UL/CUL certified |
| -DS | Europe | DC24V power, screw terminals, CE compliant |
- Ventajas & Applications
Ventajas: Built-in power supply, simple wiring; relay output can directly drive contactors, solenoids, etc.. Bajo costo, alta confiabilidad.
Applications: Small production lines, equipment automation, control de edificios, maquinaria de embalaje, procesamiento de alimentos, etc..
- Selección & Notas de uso
- Used with FX2N main units (p.ej., FX2N-64MR). Installation order: main unit → expansion unit → special function module.
- Relay response approx. 10EM, not suitable for high-speed switching. For high-speed use, select transistor output (p.ej., FX2N-48ET).
- Screw terminals; observe polarity of input/output common terminals to avoid short circuits.
Diferencias clave: FX2N-48ER vs FX2N-64ER
Main difference: Total I/O points (48 vs 64), corresponding to 24-in 24-out vs 32-in 32-out. Dimensiones, weight, and DC24V auxiliary power also differ; other features are identical.
- Specification Comparison
| Artículo | FX2N-48ER | FX2N-64ER | Difference |
| Total I/O | 48 | 64 | +16 agujas (8 inputs, 8 outputs) |
| Inputs | 24-point DC24V | 32-point DC24V | +8 inputs |
| Outputs | 24-point relay | 32-point relay | +8 outputs |
| Dimensiones | 182×90×87 mm | 220×90×87 mm | 38 mm wider |
| Peso | 0.85 kilos | 1.0 kilos | +0.15 kilos |
| DC24V Aux Power | 460 mamá | 600 mamá | +140 mamá |
| Output Common | 4/8 points per common, 8A max | Same | Identical |
| Expansion Type | Built-in power expansion | Same | Identical |
| Controlar el poder | DC5V from main unit via cable | Same | Identical |
| Compatible PLCs | FX1N/FX2N/FX3G/FX3U | Same | Identical |
- Application Impact
- Control Scale
FX2N-48ER: Small/medium machines, packaging, single-line automation
FX2N-64ER: Medium/large systems, multi-line control, more sensors/actuators
- Espacio de instalación
FX2N-64ER is wider; extra space required in control panel.
- Field Device Power
FX2N-64ER provides more DC24V current for more sensors.
- Expansión
Both support up to 7 expansion units, max 256 I/O.
- Recomendaciones de selección
- Choose based on actual I/O; slight redundancy is acceptable.
- Space-limited panels: prefer FX2N-48ER.
- Many DC24V sensors: prefer FX2N-64ER.
- Costo: FX2N-64ER is slightly more expensive.
contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares