Schneider Electric A9P52606 is a disyuntor miniatura (MCB) of the Acti9 iC40 series, featuring 1P+N pole configuration, 6Una corriente nominal, and C-type tripping curve. It is designed for overload and short-circuit protection of conventional distribution circuits such as lighting and socket systems, with a rated breaking capacity of 6kA (IEC 60947‑2)/4.5el (EN 60898). It adopts DIN rail mounting and has an IP20 protection rating.
- Interpretación del modelo
| Artículo | Details |
| Modelo | A9P52606 |
| Serie | Acti9 iC40 |
| Tipo | Disyuntor en miniatura (MCB) |
| Configuración de polos | 1P+N (1 protective pole, N pole for switching only) |
| Corriente nominal | 6A |
| Curva de disparo | Tipo C |
| Capacidad de ruptura | 6el (IEC 60947‑2), 4.5el (EN 60898‑1) |
| Método de montaje | DIN Rail |
| Protection Rating | IP20 |
- Parámetros técnicos básicos
| Parámetro | Valor | Standard |
| Rated Operational Voltage (Ue) | 230V AC 50/60Hz | EN/IEC 60947‑2 |
| Corriente nominal (En) | 6A | EN/IEC 60947‑2 |
| Característica de disparo | Tipo C (instantaneous tripping at 5In‑10In) | EN/IEC 60898‑1 |
| Ultimate Breaking Capacity (uci) | 6el (230V y) | EN/IEC 60947‑2 |
| Service Breaking Capacity (icn) | 4.5el (230V y) | EN/IEC 60898‑1 |
| Rated Impulse Withstand Voltage (Uimp) | 4kV | EN/IEC 60947‑2 |
| Overvoltage Category | Ⅲ | EN/IEC 60947‑2 |
| Grado de contaminación | 3 | EN/IEC 60947‑2 |
| Temperatura de funcionamiento | -25℃ ~ 70 ℃ | EN/IEC 60947‑2 |
| Vida eléctrica | 20,000 operaciones | EN/IEC 60947‑2 |
| Vida mecánica | 20,000 operaciones | EN/IEC 60947‑2 |
| Dimensiones (W×D×H) | 1 module (18milímetros) × 44mm × 91mm | Schneider Electric Technical Manual |
| Neutral Pole Position | Left Side | Schneider Electric Technical Manual |
| Tripping Unit Type | Thermal-magnetic | Schneider Electric Technical Manual |
- Functional Features
- 1P+N Design: Live wire protection plus synchronous neutral wire switching, suitable for single-phase distribution systems, with clear wiring and convenient maintenance.
- Type C Tripping Curve: Suitable for conventional loads such as lighting and sockets, balancing overload time-delay and short-circuit instantaneous tripping, with strong resistance to inrush current.
- High Breaking Capacity: 6el (IEC 60947‑2)/4.5el (EN 60898‑1), capable of handling severe short-circuit faults and ensuring distribution safety.
- Standard Mounting: DIN rail mounting with 1-module width, saving switchgear space, and compatible with Acti9 series accessories (p.ej., contactos auxiliares, alarm contacts).
- Adaptabilidad ambiental: IP20 protection rating, resistant to temperatures ranging from -25℃ to 70℃, meeting the requirements of industrial and civil distribution environments.
- Ámbito de aplicación
– Overload and short-circuit protection for single-phase distribution circuits of lighting, enchufes, motores pequeños, etc., in commercial buildings and industrial plants.
Places with high requirements for power supply reliability, such as office buildings, hoteles, and hospitals.
Compatible with Acti9 series distribution boxes, used in scenarios such as terminal power distribution and branch circuit protection.
- Recomendaciones de selección
- Coincidencia de carga: Type C curve is suitable for non-inductive loads (p.ej., iluminación, enchufes); avoid selecting Type D (for power loads) or Type B (for electronic equipment) curves.
- Circuit Matching: With a rated current of 6A, it is suitable for 1.5mm² copper core cables (long-term current-carrying capacity ≥ 10A), and the circuit length should be ≤ 100m.
- Capacidad de ruptura: The 6kA breaking capacity is suitable for terminal distribution; the front-end should be equipped with molded case circuit breakers with higher breaking capacity (p.ej., 15kA and above).
- Accessory Selection: According to monitoring requirements, select accessories such as auxiliary contacts (p.ej., A9A26924) and alarm contacts (p.ej., A9A26934).
- Solución de problemas
| Fenómeno de falla | Posibles causas | Métodos de solución de problemas |
| Tropiezos frecuentes | Sobrecarga, line grounding/short-circuit, mismatched tripping curve | Check load current and insulation resistance; replace MCB with a matching tripping curve |
| Failure to Close | Unreset tripping mechanism, line short-circuit, ablación por contacto | Manually reset the trip lever, locate the short-circuit point, replace damaged contacts |
| Excessive Temperature Rise | Cableado suelto, contact oxidation, high ambient temperature | Tighten wiring terminals, polish contacts, improve ventilation and heat dissipation |
| Insufficient Breaking Capacity | Lack of front-end protection, excessive short-circuit current in the line | Upgrade front-end protection, select MCB with higher breaking capacity |
- Soluciones alternativas
Intra-series Alternatives: A9P52610 (1P+N, 10A, Tipo C), A9P52616 (1P+N, 16A, Tipo C), etc., maintaining mounting and accessory compatibility.
Cross-series Alternatives: Schneider Electric IDPN series (p.ej., A9D18606, 1P+N, 6A, Tipo C) or ABB S200 series (p.ej., S201M‑C6, 1P+N, 6A, Tipo C). It is necessary to verify the matching of mounting dimensions and breaking capacity.
Complete Guide to Other Models of Schneider Electric Acti9 iC40 Series
Schneider Electric Acti9 iC40 series is a miniature circuit breaker (MCB) specially designed for single-phase/three-phase distribution systems. With 1P+N as the core product, it also provides multiple pole configurations including 2P, 3PAG, 4PAG, and 3P+N. The tripping curves cover Type B/C/D, and the breaking capacity is divided into standard type (4.5kA Icn/6kA Icu) and Type N (6kA Icn/10kA Icu), with rated current covering the full range of 1A~63A. The following is a structured and complete list of models:
- Reglas de nomenclatura de modelos (A9PXXXXXX)
| Position | Code | Meaning |
| 1-2 | A9 | Acti9 Series Identifier |
| 3 | PAG | Exclusive Code for iC40 Series |
| 4 | 2-4 | Capacidad de ruptura: 2 = Standard Type (4.5kA/6kA), 4 = Type N (6kA/10kA) |
| 5 | 6/2/3/4/7 | Configuración de polos: 6 = 1P+N, 2 = 2P, 3 = 3P, 4 = 4P, 7 = 3P+N |
| 6-7 | 01~63 | Corriente nominal: 01 = 1A, 02 = 2A, 04 = 4A, 06 = 6A, 10 = 10A, 16 = 16A, 20 = 20A, 25 = 25A, 32 = 32A, 40 = 40A, 50 = 50A, 63 = 63A |
| Curve Identifier | – | B/C/D: Tipo B (3In-5In), Tipo C (5In-10In), Tipo D (10In-14In) |
- Classified List of Full Series Models
- 1P+N (Most Commonly Used)
Curva de disparo Capacidad de ruptura Corriente nominal Modelo Tipo B Tipo estándar 2A/4A/6A/10A/16A/20A/25A/32A/40A A9P22602/A9P22604/A9P22606/A9P22610/A9P22616/A9P22620/A9P22625/A9P22632/A9P22640 Type N 2A/4A/6A/10A/16A/20A/25A/32A/40A A9P42602/A9P42604/A9P42606/A9P42610/A9P42616/A9P42620/A9P42625/A9P42632/A9P42640 Tipo C Tipo estándar 2A/4A/6A/10A/16A/20A/25A/32A/40A/50A/63A A9P22602/A9P22604/A9P52606/A9P22610/A9P22616/A9P22620/A9P22625/A9P22632/A9P22640/A9P22650/A9P22663 Type N 2A/4A/6A/10A/16A/20A/25A/32A/40A/50A/63A A9P42602/A9P42604/A9P54606/A9P42610/A9P42616/A9P42620/A9P42625/A9P42632/A9P42640/A9P42650/A9P42663 Tipo D Tipo estándar 10A/16A/20A/25A/32A/40A/50A/63A A9P62610/A9P62616/A9P62620/A9P62625/A9P62632/A9P62640/A9P62650/A9P62663 Type N 10A/16A/20A/25A/32A/40A/50A/63A A9P64610/A9P64616/A9P64620/A9P64625/A9P64632/A9P64640/A9P64650/A9P64663 2PAG (Two-pole)
| Curva de disparo | Capacidad de ruptura | Corriente nominal | Modelo |
| Tipo C | Tipo estándar | 6A/10A/16A/20A/25A/32A/40A | A9P52206/A9P52210/A9P52216/A9P52220/A9P52225/A9P52232/A9P52240 |
| Type N | 6A/10A/16A/20A/25A/32A/40A | A9P54206/A9P54210/A9P54216/A9P54220/A9P54225/A9P54232/A9P54240 | |
| Tipo D | Tipo estándar | 16A/20A/32A/40A | A9P62216/A9P62220/A9P62232/A9P62240 |
| Type N | 16A/20A/32A/40A | A9P64216/A9P64220/A9P64232/A9P64240 |
- 3PAG (Three-pole)
| Curva de disparo | Capacidad de ruptura | Corriente nominal | Modelo |
| Tipo C | Tipo estándar | 6A/10A/16A/20A/25A/32A/40A | A9P52306/A9P52310/A9P52316/A9P52320/A9P52325/A9P52332/A9P52340 |
| Type N | 6A/10A/16A/20A/25A/32A/40A | A9P54306/A9P54310/A9P54316/A9P54320/A9P54325/A9P54332/A9P54340 | |
| Tipo D | Tipo estándar | 16A/20A/32A/40A/50A | A9P62316/A9P62320/A9P62332/A9P62340/A9P62350 |
| Type N | 16A/20A/32A/40A/50A | A9P64316/A9P64320/A9P64332/A9P64340/A9P64350 |
- 4PAG (Four-pole)
| Curva de disparo | Capacidad de ruptura | Corriente nominal | Modelo |
| Tipo C | Tipo estándar | 6A/10A/16A/20A/32A/40A | A9P52406/A9P52410/A9P52416/A9P52420/A9P52432/A9P52440 |
| Type N | 6A/10A/16A/20A/32A/40A | A9P54406/A9P54410/A9P54416/A9P54420/A9P54432/A9P54440 |
- 3P+N (Three-pole + Neutral)
| Curva de disparo | Capacidad de ruptura | Corriente nominal | Modelo |
| Tipo C | Tipo estándar | 16A/20A/32A/40A | A9P52716/A9P52720/A9P52732/A9P52740 |
| Type N | 16A/20A/32A/40A | A9P54716/A9P54720/A9P54732/A9P54740 | |
| Tipo D | Tipo estándar | 20A/32A/40A | A9P62720/A9P62732/A9P62740 |
| Type N | 20A/32A/40A | A9P64720/A9P64732/A9P64740 |
- Key Features and Selection Points
- Ventajas principales:
1P+N Design: Live wire protection plus synchronous neutral wire switching, suitable for 230V single-phase systems, saving installation space (1 module = 18mm).
Graded Breaking Capacity: Standard type is suitable for terminal distribution, while Type N is suitable for front-end circuits close to distribution transformers.
Tripping Curve Adaptability: Tipo B (for electronic equipment), Tipo C (for lighting/sockets), Tipo D (for motors/power loads).
- Comparison with the Original Model:
The model you queried: A9P52606: 1P+N, 6A, Tipo C, standard breaking capacity (4.5kA/6kA).
Upgraded Type N version: A9P54606 (breaking capacity upgraded to 6kA/10kA).
Same current with different curves: A9P42606 (Tipo B), A9P62606 (Tipo D).
- Compatibilidad de accesorios: The full series is compatible with Acti9 standard accessories, como contactos auxiliares (A9A26924) and alarm contacts (A9A26934).
- Escenarios de aplicación típicos
| Model Example | Escenario de aplicación |
| A9P52606 (1P+N, 6A, Tipo C) | Residential/commercial lighting circuits, sockets for small electronic devices |
| A9P54616 (1P+N, 16A, Tipo C, Type N) | Kitchen appliances, air conditioner sockets (requiring higher breaking capacity) |
| A9P64232 (2PAG, 32A, Tipo D, Type N) | Power equipment such as single-phase water pumps and compressors |
| A9P54340 (3PAG, 40A, Tipo C, Type N) | Industrial equipment such as three-phase fans and small air compressors |
contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares