Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

Contacteur CA Chint CJ20-100 - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

onduleur solaire/contacteur/

Contacteur CA Chint CJ20-100

Chint CJ20-100 is an AC contactor suitable for the field of industrial control. It is mainly used for remotely connecting and disconnecting circuits, and can be used in conjunction with a thermal overload relay to achieve overload protection for motors. The following are its detailed technical parameters and application instructions: 1. Paramètres techniques de base – Rated Operating ...

  • Détails du produit

Chint CJ20-100 is an Contacteur CA suitable for the field of industrial control. It is mainly used for remotely connecting and disconnecting circuits, and can be used in conjunction with a thermal overload relay to achieve overload protection for motors. The following are its detailed technical parameters and application instructions:

1. Paramètres techniques de base

– Courant de fonctionnement nominal: 100UN, suitable for controlling three-phase motors with a maximum power of 50kW (AC-3, 380V).

– Plage de tension:

Rated Insulation Voltage of Main Circuit: 660V, applicable to AC 50Hz/60Hz circuits.

Optional Control Coil Voltage: AC 110V, 127V, 220V, 380V (50HZ), which should be selected according to actual control requirements.

– Système de contact:

Main Contacts: 3 sets of normally open (3NON), adopting a double-break direct-acting structure, equipped with a clay longitudinal slot arc-extinguishing cover, featuring high breaking capacity.

– Contacts auxiliaires: 2 sets of normally open (2NON) + 2 sets of normally closed (2Caroline du Nord) by default, which can be expanded to 4 sets through an expansion module (par ex., F4 series).

Service Life Indicators:

– Durée de vie mécanique: 10 millions d'opérations; Durée de vie électrique: 1.2 millions d'opérations (AC-3, 380V).

– Fréquence de fonctionnement: Jusqu'à 600 operations per hour under AC-3 category.

2. Installation and Wiring

– Méthodes d'installation:

Screw Fixing: Suitable for fixing on control cabinets or mounting plates. It is necessary to ensure that the inclination angle between the mounting surface and the vertical plane does not exceed ±5°.

– Montage sur rail: Some documents do not clearly state that rail mounting is supported, but the CJ20-10~25A models support 35mm DIN rail mounting. It is inferred that the CJ20-100 may need to be used with an adapter.

– Spécifications de câblage:

Main Contact Wiring: It is recommended to use wires with a cross-sectional area not exceeding 50mm², adopting the front-panel wiring method.

Coil Wiring: Wires should be selected according to the coil voltage, and attention should be paid to polarity (AC coils have no polarity).

3. Matching and Protection

Thermal Overload Relay:

– Modèle recommandé: JR20-160 (5W range, rated current range: 85~100~115A), which is directly connected to the contactor through a conductive plate to achieve overload and phase-failure protection.

Protection Characteristics: When the current exceeds the rated range, the thermal relay acts within a certain period of time to cut off the control circuit.

– Fusible: It is recommended to match with RT16-250 type fuses (breaking capacity: 50le) for short-circuit protection.

4. Scénarios d'application

– Contrôle du moteur: Suitable for AC-3 category loads (par ex., frequent starting and stopping of squirrel-cage motors), and can control motors below 50kW.

– Automatisation industrielle: Widely used in the electrical control systems of equipment such as machine tools, pompes, and fans, supporting remote operation and interlock control.

– Environnements spéciaux: Operating temperature range: -5℃~+40℃, altitude not exceeding 2000m, pollution degree Class 3, which can adapt to general industrial environments.

5. Alternative Models and Upgrade Solutions

Chint NXC Series: Par exemple, NXC-115, which has a smaller size, lower power consumption (coil pull-in power: 550VA → 450VA), supports rail mounting, and its electrical life is increased to 2 millions d'opérations.

Schneider LC1-F Series: Par exemple, LC1-F115, which is compatible with the installation dimensions of CJ20-100, has an electrical life of up to 1.5 millions d'opérations, and is suitable for high-end applications.

6. Précautions

Model Selection Verification: The model should be strictly matched according to the actual load type (AC-3/AC-4), tension, and current to avoid overload operation.

– Installation et entretien:

Regularly check the wear condition of the contacts; when the contact thickness is worn by more than 1/3, it should be replaced.

Ensure that the arc-extinguishing cover has no cracks or dust accumulation to avoid affecting the breaking performance.

– Référence de prix:

The market price of a single CJ20-100 (AC220V coil) is approximately 150~200 RMB, and the JR20-160 thermal overload relay is approximately 100 RMB.

7. Standards and Certifications

It complies with GB/T 14048.4 et CEI 60947-4-1 normes, et a passé la certification CCC, ensuring safety and reliability.

(Note: GB/T refers toNational Standard of the People’s Republic of China”; CCC is the “Certification obligatoire en Chine” mark, a mandatory safety certification system for products sold in the Chinese market.)