Le Chint Universal Transfer Switch LW5D16YH3/3 is a highperformance switch specifically designed for industrial control, suitable for scenarios such as voltage measurement and motor control. The following are its core information and application guidelines:
- Analyse du modèle et paramètres de base
- Signification du modèle
LW5D: Code de série (L transfer switch, W universal, 5 design serial number, D positioning type).
16: Rated thermal current 16A (applicable to AC15/DC13 loads).
YH3/3: Function code (YH voltage measurement, 3 3section contact system, 3 3 operation positions).
- Technical ParametersClick on the red text to view the
Tension nominale: AC 380V/DC 220V.
Contact form: 3 independent sections of contacts, supporting threephase voltage switching (such as UAB, UBC, UCA).
Operation angle: Fourposition positioning at 0° (middle position), 90°, 180°, and 270°, and voltage switching is achieved by rotating the handle.
Attestation: Complies with GB/T 14048.5 et CEI 6094751 normes, and has passed 3C certification (Certificate number: 2024010305685092).
- Scénarios d'application typiques
- Voltage Measurement
Used to switch the voltmeter in the power distribution cabinet to measure the threephase line voltage (such as UAB, UBC, UCA).
Wiring example
Inlet terminal: Terminals 1, 5, et 9 are connected to the threephase power supply (L1, L2, L3).
Outlet terminal: Terminals 2 et 4 are connected to the voltmeter, and terminals 6 et 10, as well as terminals 8 et 12, are shortcircuited internally through the connection piece.
- Contrôle du moteur
Supports functions such as forward and reverse rotation and twospeed switching of motors below 5.5kW (the corresponding model needs to be selected, such as LW5D16 5.5N/3).
Wiring key points
Circuit principal: Connect the motor power cable to the output terminals of the switch (such as 2/T1, 4/T2, 6/T3).
Circuit de commande: Achieve motor rotation direction or speed switching through the onoff of contacts.
- Exigences particulières
Explosionproof and anticorrosion: A customized model (such as LW5D16YH3/3Ex) is required to meet the use in dangerous environments.
Seismic reinforcement: Complies with the GB 50260 seismic code and is suitable for highvibration occasions.
III. Installation et entretien
- Méthode d'installation
Railmounted: Quickly installed through a 35mm standard rail, économiser de l'espace dans l'armoire.
Bolt fixation: Use M4 bolts to fix it on the panel to ensure mechanical stability.
- Spécifications de câblage
Contact layout: Terminals 112 are divided into three groups (14, 58, 912), and each group corresponds to a voltage gear.
Insulation requirements: Après le câblage, check the insulation resistance (≥10 MΩ) to avoid short circuits.
- Maintenance Suggestions
Replacement of vulnerable parts: The height of components such as contactor coils and indicator lights is ≤1.8m for easy operation.
Regular inspection: Clean the contacts quarterly to ensure good contact; calibrate the action value of the protection device annually.
- Model Selection and Procurement
- Comparaison des modèles
| Modèle | Number of Contact Sections | Operation Positions | Applications typiques |
| LW5D16YH2/2 | 2 sections | Three positions | Twophase voltage measurement |
| LW5D16YH3/3 | 3 sections | Four positions | Threephase voltage measurement |
| LW5D16 5.5N/3 | 3 sections | Three positions | Forward and reverse rotation control of motors |
- Canaux d'approvisionnement
Ecommerce platforms: Suning.com, JD.com, Alibaba, etc., with a unit price of approximately 2333 yuan (including freight).
Authorized distributors: A business license needs to be provided, and bulk purchases are supported (such as Beijing Chuangxinjie Electromechanical Equipment Co., Ltd.).
- Acceptance Key Points
Function test: Manual/automatic opening and closing, and the dualpower supply switching time ≤100ms.
Document verification: It should include circuit diagrams, component lists, a copy of the 3C certification, and the factory test report.
- Foire aux questions
- How to distinguish between voltage/current transfer switches?
Voltage type (YH): Fewer contact groups (tel que 3 sections), used to switch the voltmeter.
Current type (LH): More contact groups (tel que 6 sections), used to switch the ammeter.
- Can it replace Schneider’s similar products?
It is necessary to confirm the installation dimensions (such as a panel opening of 55×55mm) and contact logic. It is recommended to consult the manufacturer’s technical support.
- How to customize the explosionproof type?
It is necessary to communicate with the manufacturer in advance and provide the explosionproof grade (such as Ex d IIB T4 Gb) and installation environment parameters.
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires














NH42-63-318x560.png)