The 6SL3210-1PB15-5UL0 is a power module of the Siemens SINAMICS G120 series. Below is its key information:
Paramètres de baseSiemens6SL3210-1KE18-8UF1
Suitable Motor Power:
– Heavy overload: 0.75 kw (200% overload for 3 s, 150% overload for 57 s, 100% overload for 240 s; température ambiante: -10°C to +50°C).
– Light overload: 1.1 kw (150% overload for 3 s, 110% overload for 57 s, 100% overload for 240 s; température ambiante: -10°C to +40°C). Numéro de modèle Siemens 6SL3210-1KE23-2UF1
Power Supply Voltage: 200–240 V ±10%, frequency 47–63 Hz, 1AC/3AC (single-phase input/three-phase output or three-phase input/three-phase output; specific descriptions may vary slightly due to data differences. En général, three-phase input/output is the mainstream understanding. Here, the module supports three-phase input/output as a common scenario, and the broad description of 1AC/3AC in some materials covers input/output possibilities in different application scenarios, with three-phase being the primary application). Siemens S7-1200 series PLC
Courant nominal: 6 UN.
Classe de protection: IP20.
DimensionsSiemens6ES7253-1AA22-0XA0 (EM253)
– Some data show 291x100x165 (height x width x depth) mm (FSB size).
– Other descriptions include 114.00×185.00×365.00 mm (differences may exist due to measurement methods or different versions; the former is used as the common description for the module’s own dimensions, while the latter may include packaging or size definitions under different specifications).
Poids: 2.9 KG.
Caractéristiques du produitSiemens6ES7235-0KD22-0XA0
– Belongs to the PM240-2 series, with no built-in filter and an integrated brake chopper.
– Control mode: integrated fieldbus; communication supports PROFINET-PN.
Champ d'application
Suitable for industrial automation control, it can drive various types of motors and is commonly used in scenarios such as drive control for fans, pompes, compresseurs, etc.. (specific applications need to be combined with actual system configurations and equipment requirements).
Installation and Wiring Guide for Siemens 6SL3210-1PB15-5UL0 Power Module
- Installation GuideModule Siemens 6ES7231-5QA30-0XB0
- Installation Environment Requirements
Température ambiante: -10°C to +50°C (light overload) or +40°C (heavy overload); derating is required above 40°C.
Humidity: ≤95% relative humidity, pas de condensation.
Altitude: ≤1000 m (derating is required for higher altitudes). 6ES7142-5AF00-0BA0Siemens
Classe de protection: Only suitable for control cabinets with IP20 protection.
Installation Position: Install vertically, leaving at least 100 mm of heat dissipation space on all sides.
- Mechanical Installation Steps
- Montage sur rail: Fix the bottom slot of the module using a DIN rail (TS35/7.5 or TS35/15).
- Screw Fixing: Tighten with M4 screws through the mounting holes on the top of the module (couple: 0.8–1.0 Nm).
- Module Arrangement: When paralleling multiple units, the spacing between adjacent modules should be ≥25 mm (vertical direction) or ≥100 mm (horizontal direction).
- Wiring Methods
- Power Supply Wiring (L1/L2/L3)
Tension d'entrée: 200–240 V AC, three-phase (or single-phase input; refer to the manual for details).
Spécification du câble: It is recommended to use 2.5–6 mm² stranded copper wires (selected according to the load current).
Étapes de câblage:
- Remove the terminal cover (located on the front of the module).
- Connect the power supply cables to the L1, L2, L3 terminals (no polarity requirement).
- Tighten the terminal screws (couple: 1.2–1.5 Nm).
- Motor Wiring (U/V/W)
Spécification du câble: It is recommended to use 2.5–6 mm² stranded copper wires (needs to match the power supply cables).
Étapes de câblage:
- Connect to the U, V, W terminals (corresponding to the three-phase windings of the motor).
- Ensure the motor matches the module’s power (0.75–1.1 kW).
- Brake Resistor Wiring (+/-)
Brake Resistor Requirements: An external brake resistor is required (recommended value: 200Ω/500W).
Étapes de câblage:
- Connect the brake resistor to the + and DB terminals (the module has a built-in brake chopper).
- If no braking function is needed, short-circuit the + and DB terminals.
- Control Circuit Wiring
Digital Inputs (DI): 6 entrées numériques (support PNP/NPN), default voltage 24V DC.
Analog Input (AI): 1 analog input (0–10V or 0–20mA, requires jumper settings).
Digital Outputs (DO): 2 sorties relais (rating: 2A/250 V CA).
Analog Output (AO): 1 analog output (0–20mA).
Wiring Key Points:
– Lay control cables separately from power cables to avoid interference.
– Use shielded cables with the shield grounded at one end.
- PROFINET Communication Wiring
Interface: Integrated RJ45 interface (X1).
Topology: Supports linear, star, or ring topologies.
Étapes de câblage:
- Use CAT5e or higher Ethernet cables to connect to a PLC or switch.
- Termination resistor setting: Only activate the termination resistor for the last device in the network (set via a switch on the module).
III. Safety Precautions
- Power-Off Operation: Disconnect the main power supply and wait for at least 5 minutes (for capacitor discharge) before wiring.
- Exigences de mise à la terre: The module’s casing must be reliably grounded (ground resistance ≤10Ω).
- Polarity Check: Ensure correct polarity for power supply and brake resistor wiring.
- EMC Compliance: Use shielded power cables and follow Siemens’ EMC installation guidelines.
- Commissioning Recommendations
- Paramétrage: Set basic parameters via STARTER or the SINAMICS G120C operation panel (par ex., P0003=3 to activate expert-level parameters).
- Motor Identification: Perform quick commissioning (P0010=1) and automatic motor identification (P1910=1).
- Operation Test: Run (no-load) first, and only apply load after confirming correct direction and parameters.
For more detailed steps, refer to the Siemens official document 6SL3210-1PB15-5UL0 Operation Manual (document number: A5E30077851).