Communication Protocols and Module Configuration of Siemens 3WL1116/3WL1216 1600A ETU45B-G-LCD-3P
- Core Communication Protocols and Module Types
The communication function of this circuit breaker model is implemented via optional communication modules, supporting two mainstream industrial protocols, as detailed below:
| Communication Module Model | Supported Protocol | Physical Interface | Transmission Rate | Address Range |
| COM15 | PROFIBUS DP | 9-pin D-SUB | 9.6 kbps ~ 12 Mbps | 1~126 |
| COM16 | MODBUS RTU | 9-pin D-SUB (RS485) | 1.2 kbps ~ 115.2 kbps | 1~247 |
- Protocol Functions and Application Scenarios
- PROFIBUS DP (COM15 Module)
Supports DPV1 functions (diagnosis, alarm, parameterization), facilitating integration into upper-level systems such as Siemens TIA Portal.
Transmissible data: attuale, voltaggio, power, switch status, trip cause, fault records, ecc.
Typical applications: industrial automation production lines, large-scale factory power distribution systems, seamless connection with S7 series PLCs.
- MODBUS RTU (COM16 Module)
Adopts standard Modbus RTU frame format, supporting commonly used function codes such as 03 (Read Holding Registers), 06 (Preset Single Register) E 10 (Preset Multiple Registers).
Enables remote opening/closing, protection parameter setting, and energy data acquisition.
Typical applications: building automation, infrastructure projects, compatible with third-party SCADA systems.
III. Integration of Communication and Measurement Functions
Plus Measurement Function (optional): Cooperates with communication modules to achieve high-precision energy management, with measurement accuracy as follows:
Current: ±1%
Voltage: ±1.5%
Energia: ±2%
Data Logging Capability: Can store 100 fault records (trip type, time, current value), supporting fault tracing and system diagnosis.
Remote Control: Realizes remote opening/closing and parameter modification through communication module + electric operating mechanism, without on-site operation.
- Configuration and Selection Notes
- Communication modules are optional accessories: The basic model does not include communication functions; COM15 or COM16 modules need to be ordered separately.
- Compatibilità del protocollo: Select the protocol according to the upper monitoring system (PROFIBUS DP is suitable for Siemens systems, while MODBUS RTU is suitable for third-party systems).
- Wiring requirements:
PROFIBUS DP: Use shielded twisted pair cables; the bus length is related to the transmission rate (maximum length of 100m at 12 Mbps).
MODBUS RTU: Adopt RS485 bus, supporting up to 32 connected devices, with a maximum bus length of 1200m (at 9.6 kbps).
- ETU45B-G-LCD Support: The electronic trip unit has a built-in communication interface, allowing direct installation of COM15/COM16 modules without additional hardware.
- Upgrade and Replacement Solution
The Siemens 3WL series has been gradually upgraded to the 3WA series (per esempio., 3WA1116-3EG45-4GA4). In addition to retaining PROFIBUS DP and MODBUS RTU, it has added an Ethernet communication module (supporting PROFINET and EtherNet/IP), making it more suitable for Industry 4.0 and Internet of Things applications.
Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari