ABB MCCB T6V 800 PR221DS

T6V 800 PR221DS|ABB Tmax T6 Series High Performance Moulded Case Circuit Breaker (MCCB)

Full Model: T6V 800 PR221DS-LS/I In=800 (Common Order Codes: 1SDA069432R1, 1SDA069429R1, 3P/4P selectable)

ブランド: ABB (SACE Tmax Series)

  1. Detailed Model Interpretation
モデルセグメント意味Key Description
T6Series DesignationTmax T6 series, frame current 800A, suitable for medium and high voltage power distribution systems
VBreaking Capacity ClassClass V, ultra-high breaking capacity: 120kA at 400V, 200kA at 220V
800定格電流800あ (same as frame current)
PR221DSTrip Unit TypeElectronic intelligent trip unit with LS/I protection (Long-time delay L, Short-time delay S, Instantaneous I)
LS/IProtection ConfigurationStandard three-stage protection; earth fault protection optional (extra configuration required)
F F取り付け / 繋がりFirst F: Fixed mounting; Second F: Front connection
  1. コア技術パラメータ
ItemSpecification備考
定格電圧 (うえ)690VとSuitable for industrial high-voltage power distribution systems
定格絶縁電圧 (Ui)1000VとHigher than rated operating voltage, large safety margin
Ultimate Breaking Capacity (ICU)120kA@400V, 200kA@220VHighest Class V, 過酷な産業環境に適しています
Rated Operational Current (で)800あMaximum continuous operating current
3P/4P selectable3P for three-phase circuits, 4P includes neutral protection
Trip CharacteristicLS/I three-stage protectionLong-time delay inverse time, short-time / instantaneous definite time
Mounting Type修理済みDraw-out type also available (special model required)
Connection TypeFront connectionCompatible with cables or busbars
Degree of ProtectionIP30Standard switchgear installation protection
Applicable StandardIEC 60947-2International standard for low-voltage switchgear
  1. Key Features & Applications

Core Advantages

  1. Ultra-high breaking capacity: Class V can withstand severe short-circuit faults and ensure system safety
  2. Intelligent protection: PR221DS trip unit provides accurate overload and short-circuit protection with adjustable parameters
  3. Reliable and durable: ABB Tmax series design, suitable for frequent operation and harsh industrial environments
  4. Flexible extension: Supports various accessories (auxiliary contacts, alarm contacts, undervoltage release, 等)

代表的な用途

Main power distribution systems in large industrial plants

690V high-voltage Motor Control Centers (MCC)

Power supply for data centers and critical infrastructure

Combiner box protection for new energy power systems (PV, wind power)

Marine and offshore platform power distribution systems

  1. Reference Replacement Models

Same-brand Upgrades / Replacements

モデル遮断容量Trip Type応用
T6V 800 PR222DS-LSIG120kA@400VWith earth fault protection (G)Systems requiring earth fault detection
T6V 800 PR223DS120kA@400VAdvanced intelligent trip unitApplications requiring remote monitoring and communication
T6S 800 PR221DS70kA@400VStandard breaking capacityGeneral industrial power distribution, lower cost

Cross-brand Alternatives

ブランドモデル主要なマッチングパラメータ
シュナイダーMasterpact MT25H1 800A800あ, 120kA breaking, three-stage protection
シーメンス3WL1210-3BB36-4GA4800あ, 100kA breaking, intelligent trip unit
三菱NF800-SEW800あ, 100kA breaking, electronic trip unit
  1. Selection Notes
  2. Breaking capacity matching: Select V/S/H/N/L classes based on system short-circuit current calculation
  3. Protection function selection: Basic LS/I meets most needs; choose LSIG for earth fault protection
  4. Mounting type: Fixed for standard switchgear, draw-out for easy maintenance and replacement
  5. Accessory configuration: Select auxiliary contacts, alarm contacts, motor operators, 等, according to control requirements
  6. Voltage compatibility: T6V suitable for systems up to 690V; use dedicated 1000V series (例えば, T6L) for higher voltages