EBS203C-200A-3P is a 3-pole, 200A rated earth-leakage ノーヒューズサーキットブレーカー (MCCB/ELCB) LS電気製 (旧LSインダストリアルシステムズ / LG産業システム). It provides overcurrent, short-circuit and earth-leakage protection for three-phase electrical circuits.
📌 Model Explanation
EBS203C: EBS series earth-leakage MCCB; 200 = frame size (の), 3 = number of poles (3P), C = thermal-magnetic trip type (TM).
200あ: 定格動作電流 200 amperes.
3P: 3 極, suitable for three-phase three-wire systems.
⚙️ Key Specifications
| アイテム | 仕様 |
| Frame size (の) | 200AF~399AF |
| Rated short‑circuit breaking capacity (ICU) | 85kA at AC220V; 37kA at AC400V |
| 定格電圧 | AC220/460V |
| Protection functions | 過負荷, short‑circuit, earth leakage (100/200/500mA optional) |
| 旅行タイプ | Thermal‑magnetic trip (TM), instantaneous trip rating 12×In |
| 寸法 (高さ×幅×奥行き) | 165×105×87mm |
| 重さ | 約. 1.2kg |
| 認証 | CE, CCC |
🛠️ Applications & 互換性
Typical applications: 産業用配電, production line equipment, power and lighting circuits, suitable for three-phase applications requiring reliable earth-leakage and short-circuit protection.
Recommendation: Can be used with Meta-MEC series products for selective protection and coordination to improve system reliability.
🔄 Equivalent & Series Models
同じシリーズ: EBS203C-100A/125A/150A/175A, EBS204C (4-ポール), 等.
Alternative references: ABB Tmax series, Schneider NSX series, Chint NM8L series and other equivalent earth-leakage MCCBs. Breaking capacity and mounting dimensions must be matched.
📦 Supply & Procurement
ブランド: LS電気 (LSIS), originally manufactured in South Korea.
Purchasing channels: Authorized LS Electric distributors in China, industrial platform www.bestcontactor.com. Typical price is around one thousand RMB; negotiable for bulk orders.
The core difference between EBS203C-200A-3P and EBS203C-200A-4P (スタンダードモデル: EBS204C-200A) lies in the number of poles and the control method of the neutral (N) conductor, which directly affects wiring, protection scope and application scenarios.
- Structural Differences
EBS203C-200A-3P (3-ポール)
Structure: 3 line/incoming terminals, controlling only L1, L2, L3 (three-phase live conductors).
中性 (N): Does not pass through the breaker; directly connected.
保護: Provides overload, short-circuit and earth-leakage protection only for three-phase live conductors.
EBS204C-200A-4P (4-ポール)
Structure: 4 line/incoming terminals, controlling L1, L2, L3 + N (three-phase live conductors + neutral).
中性 (N): Passes through the breaker and switches simultaneously with phase conductors.
保護: Protects three-phase live conductors + neutral and can disconnect a faulty neutral line.
- Key Parameter Comparison
| アイテム | EBS203C‑200A‑3P | EBS204C‑200A‑4P |
| Frame / 現在 | 200の, 200あ, thermal‑magnetic type C | 同一 |
| 遮断容量 | 37kA at AC400V; 85kA at AC220V | 同一 |
| Protection functions | 過負荷, short‑circuit, earth leakage | 同一 |
| 極 | 3P (3‑pole) | 4P (4‑pole) |
| 中性 (N) | Bypasses the breaker | Switched with phases |
| 幅 | Narrower (約. 105mm) | Wider (約. 140mm) |
| Applicable system | Three‑phase three‑wire (IT, TN‑C without PEN) | Three‑phase four‑wire (TN‑S, TN‑C‑S, TT) |
Ⅲ. Functional & Safety Differences
- Switching range
3P: Switches phases only. Neutral remains live, posing electric shock risk during maintenance.
4P: Switches both phases and neutral. Fully isolates power, safer and compliant with standards.
- Earth-leakage protection effectiveness
3P: Only detects three-phase current imbalance. Cannot protect against neutral faults (例えば, neutral-to-earth short circuit).
4P: Monitors total current of four poles (L1-L2-L3-N), trips on neutral leakage for complete protection.
- System compatibility
3P: Suitable for pure three-phase loads (モーター, パンプス) with no single-phase loads and no neutral in the panel.
4P: Suitable for mixed three-phase + single-phase systems (コマーシャル, 工業用, building distribution); neutral disconnection required for safety.
- セレクションガイド
Choose 3P (EBS203C):
Loads are pure three-phase motors, コンプレッサー, heaters, 等, with no 220V single-phase circuits.
Neutral in the distribution box does not pass through this breaker; space is limited.
Choose 4P (EBS204C):
System is TN-S / TN-C-S (separate N and PE conductors).
Circuit supplies single-phase loads (点灯, ソケット, control circuits); neutral must be switched.
Required by safety standards (メンテナンス, earth-leakage protection, earthing systems).
まとめ
3P = space-saving, cost-effective → dedicated for three-phase power
4P = safer, more complete → required for mixed power distribution
LS Electric EBS Series Earth-Leakage MCCBs (ELCB): Model List & Cross-Brand Cross-Reference
- EBS Series Model System & Full List
Core features of EBS series: Earth-leakage molded case circuit breakers on LS Electric’s (formerly LS / LG産業システム) Metasol platform, with built-in earth-leakage protection modules, 過負荷に対する三重保護を提供, short-circuit and residual current (earth leakage) for low-voltage distribution systems.
- モデルの命名規則
EBS □□□ – □□□A – □P
EBS: Series code (earth-leakage MCCB)
1st digit: Frame size (5=50AF, 10=100AF, 20=200AF, 40=400AF)
2nd digit: Number of poles (3=3P, 4=4P)
3rd letter: 遮断容量クラス (C=標準, S=high)
□□□A: 定格電流 (で)
□P: Number of poles (3P/4P, consistent with 2nd digit)
- Complete Model List by Frame Size
1) 50AF Frame (EBS53C / EBS54C)
| 極 | 定格電流 | Full Model | 遮断容量 (AC400V) |
| 3P | 10A/16A/20A/25A/32A/40A/50A | EBS53C‑10A~50A | 18の |
| 4P | 10A/16A/20A/25A/32A/40A/50A | EBS54C‑10A~50A | 18の |
2) 100AF Frame (EBS103C / EBS104C)
| 極 | 定格電流 | Full Model | 遮断容量 (AC400V) |
| 3P | 63A/75A/100A | EBS103C‑63A/75A/100A | 37の |
| 4P | 63A/75A/100A | EBS104C‑63A/75A/100A | 37の |
3) 200AF Frame (EBS203C / EBS204C)
| 極 | 定格電流 | Full Model | 遮断容量 (AC400V) |
| 3P | 125A/150A/175A/200A/225A/250A | EBS203C‑125A~250A | 37の |
| 4P | 125A/150A/175A/200A/225A/250A | EBS204C‑125A~250A | 37の |
4) 400AF Frame (EBS403C / EBS404C)
| 極 | 定格電流 | Full Model | 遮断容量 (AC400V) |
| 3P | 250A/300A/350A/400A | EBS403C‑250A~400A | 50の |
| 4P | 250A/300A/350A/400A | EBS404C‑250A~400A | 50の |
- Earth-Leakage Parameters (Whole Series)
残留動作電流 (IΔn): 30mA/100mA/300mA/500mA optional (default 30mA for personal protection)
Operating time: ≤0.3s (IΔn=30mA), ≤0.1s (IΔn≥100mA)
Protection type: Type A (交流 + pulsating DC leakage), suitable for modern electronic loads
- Cross-Brand Equivalent Table for EBS Series
Below are equivalent models from major brands with matching core parameters (frame, 定格電流, 極, 遮断容量) for replacement reference.
| LS EBS Model | ABB Tmax XT | Schneider NSX | Chint NM8L | Delixi CDM1L |
| EBS53C‑50A‑3P | XT1N160 TMD50 3P RCCB | NSX100N TM50D 3P Vigi | NM8L‑100S/3300 50A | CDM1L‑100C/3300 50A |
| EBS103C‑100A‑3P | XT1N160 TMD100 3P RCCB | NSX100N TM100D 3P Vigi | NM8L‑100S/3300 100A | CDM1L‑100C/3300 100A |
| EBS203C‑200A‑3P | XT2N250 TMD200 3P RCCB | NSX250N TM200D 3P Vigi | NM8L‑250S/3300 200A | CDM1L‑250C/3300 200A |
| EBS204C‑200A‑4P | XT2N250 TMD200 4P RCCB | NSX250N TM200D 4P Vigi | NM8L‑250S/4300 200A | CDM1L‑250C/4300 200A |
| EBS403C‑400A‑3P | XT4N630 TMD400 3P RCCB | NSX630N TM400D 3P Vigi | NM8L‑630S/3300 400A | CDM1L‑630C/3300 400A |
Key Notes for Replacement
- Breaking capacity matching: Select alternatives with breaking capacity ≥ original EBS model to ensure short-circuit protection reliability.
- Earth-leakage module compatibility:
ABB requires RC221/RC222 earth-leakage accessories
Schneider requires Vigi modules (built-in / add-on)
Domestic NM8L/CDM1L have built-in earth-leakage modules, no extra parts needed
- Mounting dimension check: Width may vary between brands (例えば, EBS203C-200A-3P: 105mm; Schneider NSX250: 108mm), affecting panel layout.
- Wiring type: Ensure replacement supports original mounting (fixed / plug-in) and connection (フロント / rear wiring).
Ⅲ. 主な違い: EBS203C-200A-3P vs EBS204C-200A-4P
| アイテム | EBS203C‑200A‑3P (3‑pole) | EBS204C‑200A‑4P (4‑pole) |
| 極 & 端子 | 3 main terminals (L1/L2/L3) | 4 main terminals (L1/L2/L3/N) |
| Neutral control | Neutral bypasses breaker | Neutral switched with phases |
| Protection scope | 過負荷, short‑circuit, leakage on phases only | Full protection on phases + neutral (including neutral leakage) |
| 幅 | 105mm | 140mm |
| Applicable system | 3‑phase 3‑wire (IT, TN‑C without PEN) | 3‑phase 4‑wire (TN‑S, TN‑C‑S, TT) |
| Safety level | Phases switched only; extra isolation needed | Full isolation; higher safety |
- 選択 & Procurement Advice
- 極の選択
Pure three-phase power loads (モーター, コンプレッサー) → choose 3P (EBS203C)
Mixed three-phase + single-phase loads (点灯, ソケット) → choose 4P (EBS204C) to meet safety standards
- Earth-leakage current selection
Personal protection (ソケット回路) → IΔn = 30mA
Electrical fire prevention (power/lighting mains) → IΔn = 100mA / 300ミリアンペア
- Purchasing channels
Authorized domestic distributors, industrial e-commerce platform www.bestcontactor.com
Regular stock models: EBS53C-50A, EBS103C-100A, EBS203C-200A, EBS403C-400A, 等.