| モデルセグメント | 説明 |
| フランス | General prefix for Mitsubishi inverters (Frequency Inverter) |
| A840 | Standard model of A800 series for 400V class, high-performance vector control for general industrial use |
| 2600 | Capacity code, corresponding to Normal Duty (ND) 90kW/180A, Super Light Duty (SLD) 132kW/260A |
| 2 | CA type (current control, standard 0–20mA analog input) |
| 60 | Conformal coating on circuit boards, non-plated conductors, enhanced environmental resistance |
- Core Electrical Specifications
| アイテム | Normal Duty (ND) | Super Light Duty (SLD) | Light Duty (LD) |
| 適用モーター出力 | 90kW (150HP) | 132kW (177HP) | 110kW (147HP) |
| 定格出力電流 | 180あ | 260あ | 216あ |
| 入力電力 | 3-phase AC 380–480V, 50/60Hz (±10% tolerance) | ||
| 出力電圧 | 3-phase AC 0–input voltage, proportional to input voltage | ||
| Output Frequency | 0.2–590Hz (max 400Hz in vector control mode) | ||
| 制御方法 | Sensorless Vector Control (RSV), V/F Control, PM Sensorless Vector Control, compatible with Induction Motors (私は) and Permanent Magnet Motors (IPM) | ||
- 主な特長
- High‑Performance Control
Universal vector control, high torque at low speed; 150% 定格トルク(0.5Hz時)
Built-in PID controller for various closed-loop applications
Automatic energy-saving operation, adjusts output voltage according to load to reduce power consumption
- Structure & 保護
Protection class IP00 (open type), suitable for cabinet mounting
Circuit boards with conformal coating (IECに準拠 60721-3-3), resistant to dust, 油, and humidity
包括的な保護: 過電流, 過電圧, 不足電圧, 過熱, earth fault, motor overload, phase loss protection, 等.
- Built-in Interfaces & Expandability
Standard RS-485 communication (Modbus RTU protocol)
Supports various fieldbus extensions: PROFIBUS-DP, DeviceNet, EtherNet/IP, 等.
Analog inputs: 2 チャンネル (0–10V / 0–20mA, 1 channel dedicated for CA-type 0–20mA)
Digital I/O: 5 inputs, 2 outputs (expandable)
- 過負荷容量 & Environmental Parameters
| 負荷の種類 | 過負荷容量 | 環境条件 |
| Normal Duty (ND) | 150% rated current for 60s, 200% rated current for 3s (inverse-time characteristic) | Operating temp: -10℃to 50℃C (derating above 40℃C) |
| Super Light Duty (SLD) | 110% rated current for 60s, 120% rated current for 3s | Storage temp: -20℃ to 65℃ |
| Light Duty (LD) | 120% rated current for 60s, 150% rated current for 3s | Relative humidity: 5% に 95% (non-condensing) |
- 代表的な用途
General industrial machinery: コンプレッサー, パンプス, ファン, conveyors, mixers, 等.
Metal processing: machine tool spindles, winding equipment, wire drawing machines
Lifting & conveying: クレーン, エレベーター, automated storage systems
化学薬品 & 製薬: mixing, reaction, and conveying equipment in process industries
建物 & HVAC: air conditioning systems, パンプス, fan energy-saving control
- インストール & Selection Guidelines
- インストール要件
Forced-air cooling; ensure sufficient ventilation (≥100mm clearance on all sides)
垂直に取り付ける, avoid direct sunlight and corrosive gas environments
Recommended input reactor and EMC filter for improved stability and EMC performance
- Selection Notes
Select load rating based on actual load type (constant torque / variable torque)
For frequent starting/stopping or heavy starting, select one frame size larger than motor power
For long cable runs, consider voltage drop and dv/dt effects; install output reactor if necessary
- 代替モデル & 注文情報
Direct replacement: FR-A840-02600-E2-60 (European version, no built-in DC reactor)
Upgraded model: FR-A840-02600-E2-60CRN (with Ethernet interface)
Official order number: 297582 (base model)
The Mitsubishi FR-A840-02600-2-60 is a high-performance, high-reliability 400V-class vector inverter, ideal for driving medium-to-high power motors and providing precise speed and torque control in various industrial automation scenarios. Its CA-type control and conformal coating ensure excellent performance in harsh industrial environments.
Mitsubishi FR Series Inverter Model List & Cross-Brand Comparison
- Classification & Model Meaning of Mitsubishi FR Series
1.1 シリーズ概要
| シリーズ | Voltage Class | パワーレンジ | Core Position | 代表的な用途 |
| FR-A800 | 200V (FR-A820) / 400V (FR-A840) | 0.4kW–500kW | Flagship high-performance vector control | 重工業, high-precision torque control, 複雑なモーション制御 |
| FR-F800 | 200V (FR-F820) / 400V (FR-F840) | 0.4kW–400kW | Energy-saving for fans & パンプス | HVAC, 水処理, building automation |
| FR-E800/FR-E700 | 200V/400V | 0.1kW–22kW | Compact general-purpose | Packaging machinery, food & beverage, small production lines |
| FR-D800/FR-D700 | 200V/400V | 0.1kW–75kW | Easy-to-use economy type | Small fans/pumps, conveyors, general machinery |
| FR-CS80 | 200V/400V | 0.4kW–315kW | Heavy-duty special type | クレーン, winders, metallurgical equipment |
| FR-B | 200V/400V | 0.4kW–75kW | Explosion-proof special type | Hazardous areas such as chemical, petroleum, coal mines |
1.2 Full Model Format Explanation
Standard format: FR-XXX-YYYYY-Z-W
| 分野 | 意味 | 例 |
| フランス | General prefix for Mitsubishi inverters (Frequency Inverter) | - |
| XXX | Series code + voltage class | A840 (400V high-performance), F820 (200V fan/pump) |
| YYYYY | Capacity code/power identifier | 02600 (90kW/180A), 15K (15kW) |
| Z | 制御タイプ | 1 (標準, 0–10V), 2 (CA type, 0–20mA), E2 (European version, no built-in DC reactor) |
| W | Special functions | 60 (conformal coating), CRN (Ethernet), R2R (winding dedicated) |
- Complete Model List of Mitsubishi FR Series Inverters
2.1 FR-A840 (400V High-Performance Vector Control) Core Models
| 適用モーター出力 | ND Current | SLD Current | Base Model | Special Model |
| 0.75kW | 2.1あ | 3.0あ | FR-A840-00038-2-60 | FR-A840-00038-E2-60 |
| 1.5kW | 3.7あ | 5.3あ | FR-A840-00052-2-60 | - |
| 2.2kW | 5.0あ | 7.2あ | FR-A840-00072-2-60 | - |
| 5.5kW | 11.5あ | 16.5あ | FR-A840-00170-2-60 | - |
| 11kW | 23あ | 33あ | FR-A840-00330-2-60 | - |
| 15kW | 30あ | 43あ | FR-A840-00430-2-60 | - |
| 30kW | 60あ | 86あ | FR-A840-00860-2-60 | FR-A840-00860-E2-60 |
| 90kW | 180あ | 260あ | FR-A840-02600-2-60 | FR-A840-02600-E2-60 |
| 132kW | 240あ | 345あ | FR-A840-03450-2-60 | - |
| 280kW | 500あ | 720あ | FR-A840-07200-2-60 | - |
2.2 Representative Models of Other Main Series
| シリーズ | Representative Model | Power | 主な特長 |
| FR-F840 | FR-F840-5.5K-2 | 5.5kW | Fan/pump dedicated, built-in PID, energy-saving control |
| FR-E740 | FR-E740-1.5K-CHT | 1.5kW | コンパクト, built-in EMC filter |
| FR-D740 | FR-D740-7.5K-CHT | 7.5kW | Simple operation, 費用対効果の高い |
| FR-A820 | FR-A820-37K-1 | 37kW | 200V high-performance, suitable for light industry |
- Cross-Brand Inverter Comparison Table
Below shows functional and power matching between Mitsubishi FR series and major brands including Siemens, シュナイダー, ABB. Precise selection should consider actual load characteristics and control requirements.
| Mitsubishi Model | シーメンス相当品 | Schneider Equivalent | ABB相当 | Functional Match |
| FR-A840-02600-2-60 (90kW) | SINAMICS G120C 90kW | ATV630D11N4 | ACS580-01-180A-4 | High-performance vector control, suitable for heavy-duty applications |
| FR-F840-5.5K-2 (5.5kW) | SINAMICS G120X 5.5kW | ATV610U75N4 | ACS580-01-015A-4 | Fan/pump dedicated, energy-saving control |
| FR-E740-1.5K (1.5kW) | SINAMICS V20 1.5kW | ATV320U15N4 | ACS180-04-03A3-4 | Compact general-purpose |
| FR-A820-37K-1 (37kW, 200V) | SINAMICS G120 37kW 200V | ATV630D45N2 | ACS580-04-075A-2 | Medium-power vector control for 200V systems |
| FR-CS840-110K (110kW) | SINAMICS S120 110kW | ATV930D160N4 | ACS880-01-246A-3 | Heavy-duty, four-quadrant operation |
- 選定のポイント & 注意事項
- 負荷マッチングの原則
Constant torque loads (conveyors, mixers): select FR-A800 series, rated by ND current
Variable torque loads (ファン, パンプス): select FR-F800 series, rated by SLD current
Frequent start/stop or heavy starting: select one size larger than motor power
- Special Environment Adaptation
Harsh industrial environments: prefer models with “60” サフィックス (conformal coating: FR-A840-XXXXX-2-60)
Explosive/flammable environments: select FR-B series explosion-proof inverters
Ethernet communication: select models with “CRN” サフィックス
- インストール & Maintenance Tips
Vertical mounting, ≥100mm clearance on all sides for ventilation
For long cables, recommend output reactor to reduce dv/dt influence
Regular inspection of cooling fans and capacitors for long-term stable operation
Mitsubishi FR series inverters cover a full power range from 0.1kW to 500kW, meeting diverse needs from basic control to high-precision motion control via differentiated series positioning. For cross-brand selection, focus on core parameters including control method, overload capacity, 通信プロトコル, and environmental resistance to ensure system compatibility and stability.
コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池





















NH42-63-318x560.png)