微信: +86-13184948252 ワッツアップ: 0086-13811255435 電子メール: kent@bestcontactor.com

について 接触 |

シュナイダー C65N-DC/2P-C6A DC ミニチュアサーキットブレーカ - コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池

サーキットブレーカー/

シュナイダー C65N-DC/2P-C6A DC ミニチュアサーキットブレーカ

ParameterValueDescription
Pole Number2PTwo-pole design, protecting both the positive and negative poles of the circuit simultaneously
Rated Current6あMaximum current for normal operation
Tripping CharacteristicType CStandard tripping curve with an instantaneous tripping range of 8.5In 20%
Rated Voltage125V DCSuitable for 125V DC systems
Breaking Capacity6のMaximum short-circuit current that can be safely interrupted at 125V DC
Mounting MethodDIN Rail MountingStandard 35mm rail mounting
Product ModelA9N22423Schneider internal part number

  • 製品詳細

C65N-DC/2P-C6A is a miniature circuit breaker specifically designed for DC systems by Schneider Electric (Acti9 series). The detailed parameters are as follows:

ParameterValueDescription
Pole Number2PTwo-pole design, protecting both the positive and negative poles of the circuit simultaneously
Rated Current6あMaximum current for normal operation
Tripping CharacteristicType CStandard tripping curve with an instantaneous tripping range of 8.5In 20%
Rated Voltage125V DCSuitable for 125V DC systems
Breaking Capacity6のMaximum short-circuit current that can be safely interrupted at 125V DC
Mounting MethodDIN Rail MountingStandard 35mm rail mounting
Product ModelA9N22423Schneider internal part number

Working Principle & Features

The C65N-DC series is a circuit breaker dedicated to DC systems, featuring the following characteristics:

  1. Arc Extinguishing System: Equipped with a special arc extinguishing device designed specifically for DC circuits, effectively quenching DC arcs (DC arcs are more difficult to extinguish than AC arcs).
  2. Tripping Characteristics:

Type C Curve: Suitable for protection of general loads and distribution lines, with an instantaneous tripping current of approximately 51A (8.5×6A).

Thermal-Magnetic Tripping: Integrates dual protection functions of overload protection (thermal protection) and short-circuit protection (magnetic protection).

  1. Structural Features:

Compact design with a depth of only 68mm, saving installation space.

Mechanical service life of up to 20,000 operations, ensuring high reliability.

Protection class IP20 (for the unit itself) / IP40 (when installed in distribution boxes), providing dust and electric shock protection.

アプリケーションシナリオ

This circuit breaker is suitable for various DC power supply systems:

Industrial Automation: DC motor control, PLC control systems.

New Energy Sector: Solar inverter output protection, energy storage systems.

Communication Equipment: DC-powered devices such as base stations and switches.

Rail Transit: Vehicle auxiliary power supply systems.

Marine Electrical Systems: DC distribution systems.

Typical Application: Protecting DC loads below 6A, such as sensors, small controllers, communication modules, 等.

Selection & Usage Notes

  1. Voltage Matching: Must be used with 125V DC systems; not applicable for AC systems.
  2. Current Selection:

The rated current (6あ) should be greater than the maximum operating current of the circuit.

Consider load starting current: Type C curve allows short-term overloads (例えば, motor startup).

  1. Pole Number Selection: The 2P structure disconnects both positive and negative poles simultaneously, providing safer circuit isolation.

C65N-DC/2P-C6A is a compact protection device developed by Schneider for DC systems. Integrating overload protection, short-circuit protection, and circuit control functions, it is particularly suitable for protecting loads below 6A in 125V DC systems.

前へ:

次:

返信を残す