C11B3TM063L Schneider Molded Case Circuit Breaker

C11B3TM063L is a 63A Molded Case Circuit Breaker (MCCB) of Schneider’s ComPacT NSXm series, a new generation of miniaturized power distribution protection component integrated with adjustable thermomagnetic trip protection and high-reliability breaking capacity. It is suitable for industrial/commercial low-voltage power distribution systems. Below is a comprehensive parameter analysis, application scenarios, installation and wiring instructions, and alternative models of this type, meeting the requirements for selection, replacement and operation in an all-round way.

 

  1. Full Interpretation of Model Coding (Core Key for Quick Parameter Understanding)

The model coding of Schneider’s NSXm series consists of letters and numbers, with each segment corresponding to core performance. The breakdown of C11B3TM063L is as follows:

Code SegmentMeaningParameters of This Model
C11Product SeriesComPacT NSXm 63A frame, compact molded case circuit breaker with a rated operating voltage of 690V
BBreaking Capacity ClassClass B breaking capacity, Icu=25kA@415V AC (general-purpose for power distribution circuits)
3Pole Number3-pole (3P), suitable for three-phase power distribution circuits (L1/L2/L3)
TMTrip Unit TypeTM=Thermomagnetic Trip Unit (adjustable thermal overload protection + fixed magnetic short-circuit protection, general-purpose for power distribution/motor circuits)
63Rated Setting Current63에이 (In=63A, rated current of the trip unit; the long-term operating current of the circuit ≤63A)
터미널 유형L=EverLink Connector (crimp-free, quick connection, reducing contact resistance)
  1. 핵심 기술 매개변수 (Complete Specifications)
ItemParameterDescription
Product TypeCompact Molded Case Circuit Breaker (MCCB)The NSXm series is 30% smaller in volume than the traditional NSX series, saving switchgear space
Pole Number3P (3-pole 3D)Dedicated for three-phase three-wire power distribution circuits, without neutral line protection
Trip Unit TypeTM63D Thermomagnetic Trip UnitAdjustable range of thermal trip: 0.7~1.0In (44.1~63A); Fixed magnetic trip: 10In (630에이)
Rated Operating Current (In)63에이Long-term operating current ≤63A, suitable for loads of 63A and below
Rated Operating Voltage (Ue)415뷔와 (50/60헤르츠), 정격 절연 전압 (Ui)=690VSuitable for 400V low-voltage power distribution systems, with insulation performance meeting industrial standards
Breaking CapacityIcu=25kA@415V AC; Ics=12.5kA@415V ACMeets the short-circuit breaking requirements of general industrial/commercial power distribution
과부하 보호 (Thermal Trip)No trip for long-term operation at 1.05In; Trip within 2h at 1.3In; Trip within 1h at 1.5InComplies with IEC60947-2 standard, suitable for overload characteristics of motor/power distribution circuits
단락 보호 (Magnetic Trip)Instant trip at 10In (630에이)Avoids false tripping caused by short-term inrush current such as motor starting
Mounting MethodFixed/Plug-in/Draw-out (optional)Adapts to the installation requirements of different switchgears
Wiring MethodEverLink Crimp-free TerminalsSuitable for copper conductors (16~70mm²)/copper busbars, featuring convenient wiring and low contact resistance
보호 등급IP40 (Housing)Suitable for installation inside switchgears, dust and splash proof
Standard CertificationIEC60947-2, GB14048.2Complies with international/national standards with reliable protection performance
  1. Application Scenarios and Selection Adaptation

3.1 Core Application Scenarios

Protection of branch circuits in 400V three-phase low-voltage power distribution systems (예를 들어, workshop power cabinets, building distribution boxes);

Protection of medium and small motor circuits (suitable for a single three-phase asynchronous motor ≤30kW or a circuit with the total power of multiple motors ≤30kW);

Power distribution protection for power equipment such as air conditioners and water pumps in commercial buildings (예를 들어, shopping malls, office buildings);

Switchgears requiring a compact design (예를 들어, control boxes with limited space, outdoor box-type substations), where the NSXm series saves installation space.

3.2 Key Points for Selection Adaptation

The long-term operating current of the circuit ≤63A and the short-term starting current ≤10In (630에이) to avoid magnetic trip false operation;

The short-circuit fault current ≤25kA (at 415V). If the on-site short-circuit current >25kA, upgrade to a model with Class F breaking capacity (Icu=36kA) (예를 들어, C11F3TM063L);

For motor circuits, it is recommended to set the thermal trip value to 0.95~1.0 times the motor’s rated current to ensure accurate overload protection;

If neutral line protection is required, select a 4P model (예를 들어, C11B4TM063L) suitable for three-phase four-wire power distribution circuits.

  1. Installation and Wiring Specifications (Key Operations for Accuracy and Safety)

4.1 설치 요구 사항

  1. Mounting Method: For fixed installation, the thickness of the mounting plate ≥2mm and the screw tightening torque ≥12N·m; for plug-in/draw-out installation, ensure proper insertion and no looseness;
  2. Installation Position: Install vertically inside the switchgear, keep a distance of ≥30mm from heating elements (예를 들어, contactors, thermal overload relays) to ensure good heat dissipation;
  3. Operation Space: The circuit breaker’s operating handle is exposed, and a minimum operation space of 50mm is reserved for convenient switching on/off and fault indication checking.

4.2 배선사양

Wiring PartOperation PointsSafety Notes
Main CircuitConnect three-phase L1/L2/L3 to the upper end of the circuit breaker and the lower end to the load with correct phase sequenceIt is strictly forbidden to reverse the incoming and outgoing lines, otherwise the protection performance will be affected
TerminalsInsert conductors/busbars directly into EverLink connectors without crimping to ensure tight contactConductor specification: 16~70mm² copper conductors; copper busbar thickness ≥3mm
Trip Unit AdjustmentRotate the current adjustment knob on the trip unit to align the pointer with the required setting value (44.1~63A)Power off before adjustment to avoid electric shock; tighten the knob after adjustment to prevent setting value deviation caused by vibration
Auxiliary CircuitIf auxiliary contacts/shunt trip units are installed, wire according to the terminal marks and match the control voltage with the coil voltageAuxiliary circuit conductors: ≥1.5mm² copper conductors to avoid signal attenuation

4.3 Commissioning Key Points for Protection Functions

Thermal overload protection: Set the value to 0.9~1.0 times the rated current of the circuit; the circuit breaker shall trip within 2h when simulating an overload (1.3In);

Short-circuit protection: The circuit breaker shall trip instantly (≤0.1s) to interrupt the fault current when simulating a short circuit (10In);

Mechanical operation: Perform switching on/off operations 10 times, check that the circuit breaker has no jamming or abnormal noise, and the trip indication is normal.

  1. Extended Models of the Same Series (Optional as Required)

If the basic C11B3TM063L model cannot meet functional requirements, the extended models of Schneider’s NSXm series with the same specifications are as follows:

모델Core Extended Functions응용 시나리오
C11B3TM063L+MXWith shunt trip unit (AC220V/380V)Remote tripping control (예를 들어, fire linkage, remote power distribution monitoring)
C11B3TM063L+OFWith auxiliary contacts (1 아니요 + 1 NC)Switching on/off status indication, circuit fault signal feedback
C11B3TM063L+MX+OFShunt trip unit + 보조 접점Remote control + status feedback for intelligent power distribution requirements
C11F3TM063LClass F breaking capacity (Icu=36kA@415V)Industrial power distribution circuits with large short-circuit current
C11B4TM063L4-pole (3P+N)Three-phase four-wire power distribution circuits requiring neutral line protection
C11B3TM063BTraditional crimp terminals (B=Bolt terminals)Scenarios requiring replacement with traditional crimp wiring methods
  1. Cross-Brand Alternative Models (Direct Replacement with Matched Parameters)

The following are the direct replacement models of C11B3TM063L from brands such as ABB and Siemens, with completely matched current, breaking capacity and trip characteristics, adapting to the installation dimensions of the original switchgear:

Original ModelAlternative BrandAlternative ModelMatching Points
C11B3TM063L씨줄Tmax XT2N160 TMD63 3P 25kA3P 63A, TMD trip unit, 25kA breaking capacity, dimensionally compatible
C11B3TM063L지멘스3VL6306-1DC33-0AA03P 63A, thermomagnetic trip unit, 25kA breaking capacity, EverLink terminals optional
C11B3TM063L국내의 (친트)NM1-63S/3300 63A3P 63A, thermomagnetic trip unit, 25kA breaking capacity, more cost-effective
C11B3TM063L국내의 (맛있는)CDM3-63S/3300 63A3P 63A, thermomagnetic trip unit, 25kA breaking capacity, dimensionally compatible for installation
  1. Core Safety Notes
  2. Power-off Operation for Installation/Maintenance: All installation, wiring and replacement operations must be carried out with the primary circuit completely powered off; hang aNo Switching Onwarning sign to prevent electric shock;
  3. Specification for Trip Unit Adjustment: Before adjusting the thermal overload setting value, confirm the load type of the circuit; the setting value for motor circuits ≤ the motor’s rated current, and the setting value for power distribution circuits ≤ the calculated current of the circuit;
  4. Avoid Overload Operation: The long-term operating current of the circuit is strictly prohibited to exceed 63A, otherwise it will cause overheating and shortened service life of the circuit breaker, and even trigger safety accidents;
  5. Regular Maintenance and Inspection: Check the temperature of wiring terminals monthly (≤60℃ is normal), inspect the reliability of switching on/off operations quarterly, and conduct a short-circuit protection test annually to ensure the effectiveness of protection functions.