위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

CHINT NM1LE-250S-4300-200A MCCB - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

회로 차단기/

CHINT NM1LE-250S-4300-200A MCCB

BrandReplacement Model
슈나이더EZD250E4200ELN (integrated leakage)
슈나이더NSX250N 4P 200A TM200D + Vigi NSX 250
씨줄A2C250 TMF200/2000 4P integrated leakage
씨줄Tmax T2N250 TMD200/2000 4P + RC221
지멘스3VM1250-4ED32-0AA0
MitsubishiNV250-SV 4P 200A
DELIXICDM1LE-250/4300 200A
DELIXICDM3LS-250S/4300A 200A
TENGENTGM1LE-250/4300 200A
Changshu SwitchCM1L-250/4300 200A
NADERNDM1L-250/4300 200A
HUYUHUM1LE-250/4300 200A

  • 제품 세부정보

NM1LE-250S-4300-200A is a moulded case residual current circuit breaker (RCCB/MCCB with earth leakage protection) from CHINT (NM1LE Series).

  1. Full Model Explanation

NM1LE: 시리즈 코드

N: CHNT company code

M: Moulded case circuit breaker

1: Design sequence

LE: With earth leakage / residual current protection

250: Frame rating current 250A (maximum frame current for this series)

S: Breaking capacity class (Standard type, ultimate breaking capacity Icu=30kA)

4300: Poles & functions

4: 4 극 (3P+N)

3: Thermal-magnetic trip with overload + 단락 보호

00: No accessory trips (no undervoltage, no shunt trip)

200에이: Rated operational current In=200A (continuous permissible current)

  1. Key Technical Parameters (NM1LE-250S/4300 200A)
Rated operational voltage UeAC 400V/415V (3-phase 4-wire)
Rated insulation voltage Ui800다섯
Rated impulse withstand voltage Uimp8kV
Rated frequency50헤르츠
Ultimate breaking capacity Icu30그만큼 (Type S standard)
Service breaking capacity Ics15그만큼
Trip characteristicThermal-magnetic (distribution type)
Rated residual operating current IΔn50엄마 / 100엄마 / 200엄마 (3 adjustable steps)
Residual operating timeStandard type ≤ 0.1s (time‑delay optional)
Number of poles4피 (Pole N type A: no overcurrent trip, always closed)
MountingFixed type (front connection mainly)
Applicable standardsGB/T 14048.2, IEC 60947-2
  1. Main Functions
  2. Overload protection: Thermal trip delays and trips when current exceeds 200A.
  3. Short-circuit protection: Magnetic trip operates instantly within 30kA short-circuit current.
  4. Residual current (earth leakage) protection: Detects current imbalance between phase and neutral; trips quickly at set values (50/100/200엄마) to prevent electric shock and electrical fires.
  5. Infrequent switching: Can be used as a main switch for circuits and equipment.
  6. 일반적인 응용 분야

3-phase 4-wire distribution systems, industrial equipment, building power distribution, construction temporary power, main circuits in shopping malls and factories, and other occasions requiring earth leakage + overload + short-circuit triple protection.

Complete Technical Data Sheet

CHINT NM1LE-250S/4300 200A

All parameters are from CHINT official catalog and manual, applicable to NM1LE-250S/4300 200A (4-pole moulded case residual current circuit breaker).

  1. Basic Identification Parameters
Key ValueNotes
Full product nameMoulded case residual current circuit breaker (earth leakage circuit breaker)Distribution protection type
Brand/SeriesCHINT / NM1LE SeriesUpgraded first generation
Full modelNM1LE-250S/4300 200AStandard front connection, no accessory trips
Frame rating current250에이Max rated current supported by this frame
Rated operational current In200에이Long‑term permissible operating current
Poles4 극 (3P+N)Pole N has no overcurrent trip, always closed
Breaking capacity classType S (Standard)Type H (high breaking) available for same frame
Trip typeThermal-magnetic tripLong‑time delay overload + instantaneous short‑circuit protection
ComplianceGB/T 14048.2, IEC 60947-2CCC certified
  1. Main Circuit Electrical Parameters
Key ValueNotes
Rated operational voltage UeAC 400V/415VFor 3-phase 4-wire systems
Rated insulation voltage Ui800다섯Maximum insulation withstand voltage
Rated impulse withstand voltage Uimp8kVSurge & lightning overvoltage capability
Rated frequency50헤르츠For domestic mains power systems
Rated ultimate short-circuit breaking capacity Icu (AC400V)30그만큼Max safe breaking short-circuit current
Rated service short-circuit breaking capacity Ics (AC400V)15그만큼Can continue normal operation after breaking
Arc distance≤100mmMax arc flash during short-circuit breaking
ConnectionFront connection (standard)Rear connection & plug-in type optional
Main terminal torque12N·mFor M8×16 terminal screws
Recommended copper conductor≥70mm² (solid) / 120mm² (stranded)Copper busbar / cable recommended
  1. Protection Characteristics
Key ValueNotes
Overload protection (thermal trip)Non-tripping at 7.2In; trips within 1h at 1.3InReference temp +30°C, inverse time delay
Short-circuit protection (magnetic trip)Instantaneous setting 12In (2400에이)Distribution type, reliable at 120% setting
Protection functionsOverload, 단락, 잔류 전류 (earth leakage)Can be used for infrequent circuit switching
Inlet/outletTop inlet, bottom outlet (standard)Reverse connection strictly prohibited
  1. Earth Leakage Protection Parameters
Key ValueNotes
Rated residual operating current IΔn50엄마 / 100엄마 / 200엄마, 3 adjustable stepsDIP switch on device
Rated residual non-operating current IΔn00.5×IΔnThreshold to avoid nuisance tripping
Residual operating time (standard)≤0.1s (fast type)Trips within 100ms on earth fault
Earth leakage type교류형Reliable for sinusoidal AC residual current
Test circuitBuilt-in test circuitWith test button; test at least monthly
Earth fault indicationRed mechanical indicatorPops out after earth leakage trip
  1. Environmental & 기계적 매개변수
Key ValueNotes
Operating ambient temperature-5℃ ~ +40℃Derate required beyond this range
Storage temperature-25℃ ~ +70℃Non-energized storage
고도2000m 이하Derate for higher altitude
Pollution degree3Suitable for industrial distribution
Installation categoryIIIFor distribution circuits and main equipment circuits
Ingress protectionIP30 (except terminals)Solid foreign object protection, not waterproof
Mechanical endurance10,000 운영No-load operating cycles
Electrical endurance4,000 운영At rated load
Mounting orientationVertical or horizontal mounting allowedInverted mounting not permitted
  1. 치수 (4-pole, unit: mm)
DimensionNotes
Width W188Total width of 4-pole unit
Height L165Including terminals
Depth H102Body thickness
Horizontal mounting hole spacing140Center-to-center left-right
Vertical mounting hole spacing126Center-to-center up-down
Mounting hole diameter Ød4.5For M4 mounting screws
Minimum clearance≥25mm side, ≥5mm top/bottomFor side-by-side installation

Alternative Models from Other Brands

All below match the core specification:

4 극 (3P+N), 250A frame, 200A rated current, Icu ≥30kA at AC400V, thermal-magnetic overload + 단락 보호, AC-type earth leakage (50/100/200mA adjustable), no accessory trips, front fixed connection.

  1. Domestic High-Compatible Alternatives

(치수, price, function highly matched; ideal for direct replacement)

  1. BrandReplacement Model주요 일치 매개변수설명
    DELIXICDM1LE-250/4300 200AIcu=30kA, 4P 200A, 50/100/200mA adjustable, thermal-magnetic1:1 design with NM1LE, high compatibility, no cabinet modification
    DELIXICDM3LS-250S/4300A 200AIcu=35kA, 4P 200A, adjustable leakage, thermal-magneticNew upgraded series, higher performance
    TENGENTGM1LE-250/4300 200AIcu=30kA, 4P 200A, 50/100/200mA adjustableDirectly compatible with NM1LE
    Changshu SwitchCM1L-250/4300 200AIcu=35kA, 4P 200A, adjustable leakageIndustrial rade high reliability
    NADERNDM1L-250/4300 200AIcu=35kA, 4P 200A, adjustable leakageStable for construction & industry
    HUYUHUM1LE-250/4300 200AIcu=30kA, 4P 200A, 3-step leakageCost-effective direct replacement

    Joint-venture / International Brands

(Higher performance for premium projects & severe conditions)

BrandReplacement Model주요 일치 매개변수설명
슈나이더EZD250E4200ELN (integrated leakage)Icu=36kA, 4P 200A, 30/100/300mA adjustableEconomic universal type
슈나이더NSX250N 4P 200A TM200D + Vigi NSX 250Icu=50kA, 4P 200A, multi‑range leakageHigh‑end industrial grade
씨줄A2C250 TMF200/2000 4P integrated leakageIcu=36kA, 4P 200A, adjustable leakageEconomic building distribution
씨줄Tmax T2N250 TMD200/2000 4P + RC221Icu=36kA, 4P 200A, multi‑range leakageHeavy industrial & foreign projects
지멘스3VM1250-4ED32-0AA0Icu=36kA, 4P 200A, 30/100/300mA adjustableStandard international type
MitsubishiNV250-SV 4P 200AIcu=36kA, 4P 200A, 100/200/500mA adjustableHigh reliability for precision equipment
  1. Key Replacement Notes
  2. Mounting dimension check: Domestic models (CDM1LE, TGM1LE, 등.) are highly compatible with NM1LE for direct replacement. International brands often differ in size and hole spacing.
  3. Minimum breaking capacity: Icu at AC400V must be ≥30kA to ensure safety.
  4. Leakage matching: Prefer 50/100/200mA adjustable; use fast‑acting type ≤0.1s, not time‑delay.
  5. Poles & N-pole characteristic: Must be 4P (3P+N), with N-pole without overcurrent trip, always closed.
  6. Compliance: All replacements must be CCC certified and comply with GB/T 14048.2 / IEC 60947-2.

이전:

다음:

답장을 남겨주세요

메시지를 남겨주세요