  1. Detailed Model Coding Rules for 7UM62 Series
  2. Siemens product information PDF 그리고 information on alternative brands in China

The Siemens SIPROTEC 4 7UM62 series uses a 12-digit segmented structure. The complete coding format is:

코드 세그먼트설명Standard Options비고
7UM62제품 시리즈7UM62SIPROTEC 4 multifunctional protection for generators, motors and transformers
[Function Version]Protection Function Scope11=StandardDetermines protection logic and available algorithms
12=Enhanced
13=Full (Generator‑dedicated)
[Housing Type]치수 & I/O Quantity1=1/2 19″, 7BI, 12BO, 1 readyDefines I/O capacity and display type
2=1/1 19″, 15BI, 20BO, 1 ready
3=Graphic display, 1/2 19″, 7BI, 12BO
[터미널 유형]Connection TerminalB=Screw terminalB for fixed installation; E for frequent replacement
E=Plug‑in terminal (2/3‑pin)
[CT Rating]CT Ratio & SensitivityB=5A standardMatches on‑site CT for accurate measurement
E=1A standard
H=1A high‑sensitivity (IEE)
L=5A low‑sensitivity
[Region/Standard]기준 & LanguageA=Germany, 50헤르츠, IEC, GermanDefines protection curves and HMI language
B=Global, 50/60헤르츠, IEC/ANSI, English (UK)
C=USA, 60헤르츠, ANSI, English (US)
D=Customized
[Special Function]Additional Function0AA0=BasicSpecial functions require separate authorization
0HA0=With communication
0AC0=Enhanced event recording
0FA0=With synchrocheck
  1. Complete Model Matrix of 7UM62 Series (Grouped by Configuration)

2.1 Standard Function Version (7UM6211)

완전한 모델주문 번호.Core Configuration애플리케이션
7UM6211-1BB02-0AA07UM6211-1BB02-0AA01/2 19″, 7BI/12BO, screw, 5A CT, globalSmall/medium motor protection, general industry
7UM6211-1EB01-0HA07UM6211-1EB01-0HA01/2 19″, 7BI/12BO, plug‑in, 1A CT, with commsDistributed control systems, frequent maintenance
7UM6211-2BB02-0AA07UM6211-2BB02-0AA01/1 19″, 15BI/20BO, screw, 5A CT, globalLarge motors/transformers, complex logic
7UM6211-2EB91-0AA07UM6211-2EB91-0AA01/1 19″, 15BI/20BO, plug‑in, 1A CT, customizedCritical power equipment, custom protection
7UM6211-3BB02-0HA07UM6211-3BB02-0HA01/2 19″, graphic display, 7BI/12BO, screw, 5A CT, with commsImportant equipment with local monitoring

2.2 Enhanced Function Version (7UM6212)

완전한 모델주문 번호.Core ConfigurationEnhanced Functions
7UM6212-1EB01-0AC07UM6212-1EB01-0AC01/2 19″, 7BI/12BO, plug‑in, 1A CT, event recordingFault recording, harmonic analysis
7UM6212-2BB02-0FA07UM6212-2BB02-0FA01/1 19″, 15BI/20BO, screw, 5A CT, synchrocheckGrid‑parallel operation, out‑of‑sync prevention
7UM6212-3EB01-0HA07UM6212-3EB01-0HA01/2 19″, graphic display, 7BI/12BO, plug‑in, 1A CT, with commsGraphic UI + advanced comms for smart substations

2.3 Full Function Version (7UM6213) – Generator Dedicated

완전한 모델주문 번호.Core ConfigurationGenerator Protection Features
7UM6213-2EB22-0HA07UM6213-2EB22-0HA01/1 19″, 15BI/20BO, plug‑in, 1A CT, with comms100% stator earth fault, rotor earth fault protection
7UM6213-1BB02-0AA07UM6213-1BB02-0AA01/2 19″, 7BI/12BO, screw, 5A CT, globalSmall hydro & captive power generators
7UM6213-3EB91-0AC07UM6213-3EB91-0AC01/2 19″, graphic display, 7BI/12BO, plug‑in, 1A CT, event recordingGraphic fault analysis for large generators

2.4 Special Configurations (by CT & Region)

CT TypeRegion SettingTypical ModelsApplication Features
5A StandardGlobal (IEC/ANSI)7UM6211-1BB02-0AA0Most industrial power systems
7UM6211-2BB02-0AA0
1A Standard미국 (ANSI)7UM6211-1EB01-0CA0Standard for North American power systems
7UM6211-2EB01-0CA0
1A High‑SensitivityGlobal (IEC/ANSI)7UM6211-1EH01-0HA0High‑impedance earthing systems, improved earth fault detection
7UM6211-2EH01-0HA0
5A Low‑SensitivityEurope (IEC)7UM6211-1BL02-0AA0High‑capacity equipment, reduced maloperation
7UM6211-2BL02-0AA0
  1. 핵심 기능 & Technical Specifications

3.1 General Technical Data

설명
Measuring Channels8×Current, 4×VoltageFull monitoring for three‑phase systems
Sampling Rate24 samples/cycleAccurate transient capture, high reliability
CommunicationRS485 standard, Ethernet optionalSupports IEC 60870‑5‑103, 모드버스, 등.
Supply Voltage110/220V AC/DCWide‑range design
주변 온도-25℃ ~ +70℃Industrial and outdoor installation
Protection DegreeIP30For panel mounting

3.2 Core Protection Functions

Integrated comprehensive protection (varies by version):

Overcurrent protection (ANSI 50/51)

Impedance protection (ANSI 21)

Out-of-step protection (ANSI 78)

Over/undervoltage (ANSI 59/27)

Over/underfrequency (ANSI 81)

Stator/rotor earth fault (ANSI 64)

Reverse power (ANSI 32)

Synchrocheck (ANSI 25)

  1. Selection & Ordering Notes
  2. Function Version

기준 (11): General motors & transformers

Enhanced (12): Advanced monitoring & event analysis

Full (13): Generator-specific, including 100% stator earth fault

  1. Housing & I/O

1/2 19″ (7BI/12BO): Space-limited panels

1/1 19″ (15BI/20BO): Complex logic, more I/O

Graphic display (3xx): Local operation & fault diagnosis

  1. CT Matching

Confirm on-site CT ratio (5A/1A)

High-sensitivity versions for high-impedance earthing

  1. Region & 기준

Global (비): IEC/ANSI compliant, ideal for export

Regional (A/C): Optimized for local standards

  1. Replacement Models

7UM62 series is discontinued; recommended successor: 7UM85 series (SIPROTEC 5)

Cross-brand alternatives: ABB REF615, Schneider Sepam 80 series, ABB RET670 (generator-dedicated)