Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Despre Contact |

 ABB machinery drive ACS355-01E-02A4-2 - Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare

electric/

ABB machinery drive ACS355-01E-02A4-2

ABB ACS355 series general machinery drive, 0.37 kW / 0.5 HP, single-phase 200–240 V input, IP20 protection, rated output current 2.4 O. Suitable for speed control and energy-saving operation of small machinery. 1 Model Code Explanation Code Part Meaning ACS355 ABB general machinery drive series 01E Protection class IP20, for installation in enclosed electrical cabinets ...

  • Detalii despre produs

ABB ACS355 series general machinery drive, 0.37 kW / 0.5 HP, single-phase 200–240 V input, IP20 protection, rated output current 2.4 O. Suitable for speed control and energy-saving operation of small machinery.

1 Model Code Explanation

Code PartSens
ACS355ABB general machinery drive series
01EClasa de protectie IP20, for installation in enclosed electrical cabinets
02A4Rated output current 2.4 O
2Single-phase 200–240 V AC (±10%), 50/60 Hz input

2 Key Technical Data

ItemValoare
Rated power0.37 kW (0.5 HP)
Rated output current2.4 O (at 40°C)
Input voltage / frecvenţăSingle-phase 200–240 V AC (±10%), 50/60 Hz
Output voltage / frecvenţăThree-phase 0–240 V AC, 0–500 Hz
Clasa de protectieIP20 (indoor cabinet installation)
Control methodScalar control (V/f), built-in application macros
Overload capability150% de curent nominal pentru 60 s; 180% pentru 2 s
Cooling methodNatural cooling
Dimensiuni (W×H×D)169×70×135 mm
GreutateAproximativ. 1.2 kg
Order code3AUA0000058166
EMC performanceBuilt-in EMC filter, compliant with EN 61800-3

3 Key Features

3.1 Flexible Control

Predefined application macros: constant torque, fan/pump, PID control, etc.

Local/remote control switching via keypad, terminals or fieldbus

Built-in PID controller for closed-loop flow, pressure, etc.

3.2 Reliable Protection

Overcurrent, suprasarcina, overvoltage, undervoltage, supraîncălzire, phase loss protection

Motor over-temperature protection (requires external PTC)

Short-circuit and earth-fault protection

3.3 Easy Operation

Compatible control panel with ACS350/510/550 series

Parameter copy function for fast commissioning

MTBF > 100,000 hours for continuous operation

4 Aplicații tipice

Small conveyors, packaging machinery

Fans, pompe (small HVAC systems)

Mixers, centrifuges and small processing machines

Automatic doors, roller shutters

Medical equipment, laboratory instruments

Textile, printing and other light industrial machinery

5 Instalare & Commissioning Guidelines

5.1 Cerințe de instalare

Must be installed in an enclosed electrical cabinet

Ambient temperature: 0–40°C (derate 10% at 40–50°C)

Mount vertically, keep ≥ 100 mm clearance above and below for cooling

Avoid dust, oil, corrosive gases

Input protection: 10 A MCCB (C-curve) or fuse recommended

5.2 Basic Commissioning Steps

  1. Pre-power check: Verify wiring (L1/N input, U/V/W output), terminal torque, proper earthing
  2. Parameter initialization

Group 99: set motor rated voltage, actual, power, viteză

Select application macro (Standard, PID, etc.)

  1. Control configuration

Local control: via control panel

Remote control: via DI terminals or optional Modbus RTU

  1. Operation test

Test fără sarcină: run at 5–10 Hz, check rotation and stability

Test de sarcină: gradually apply load, verify current and temperature

Adjust acceleration/deceleration time (1–10 s recommended)

6 Cross-Brand Replacement Options (0.37 kW, 1-phase 220 V, IP20)

MarcaModelKey Matching Points
SchneiderATV12HU04M20.37 kW, 1-phase 220 V, IP20, similar size
SiemensV20 6SL3210-5BB12-5UV10.37 kW, 1-phase 220 V, IP20, integrated EMC
ChintNVF2-0.37/20.37 kW, 1-phase 220 V, IP20, economical alternative
ABB alternativeACS150-01E-02A4-2Same power range, more compact design

7 Selecţie & Maintenance Tips

7.1 Recommended Options

Braking function: optional braking resistor (75 Oh / 50 W recommended)

Communication: add RS485 module

Enhanced EMC: additional input EMC filter

7.2 Întreţinere

Clean cooling channels every 6 months

Check terminal torque annually

Avoid frequent starts/stops ( 20 times per day)

Storage temperature: -25°C până la +60°C, dry environment

ABB ACS355-01E-02A4-2

Installation and Commissioning Manual

Overview: This manual provides complete instructions for safety, installation, cablare, parameter setting and commissioning of the ACS355-01E-02A4-2 drive (0.37 kW / 0.5 HP, single-phase 200–240 V) for general machinery speed control and energy saving.

1 Safety Instructions (Must Read)

1.1 Electrical Safety

Power-off procedure: Disconnect all power before installation, wiring or maintenance. Wait 5 minutes for internal capacitors to discharge.

Earthing: PE terminal must be reliably earthed (earth resistance ≤ 4 Oh)

Overcurrent protection: Install 10 A MCCB (C-curve) or fuse on input side

Test de izolare: Only test motor cables; do NOT apply voltage to the drive itself

1.2 Mechanical Safety

Rotating parts (shaft, coupling, pulley) must be guarded

Mount vertically on solid surface to avoid vibration

Do not modify internal circuits or structures

1.3 Environmental Safety

Temperatura de functionare: 0–40°C (derate 10% at 40–50°C)

Umiditate: 5–95% RH, necondens

IP20: must be installed in enclosed cabinet

2 Product Overview and Model Identification

2.1 Explicația modelului (ACS355-01E-02A4-2)

CodeSens
ACS355ABB general machinery drive series
01EIP20, cabinet-mounted
02A4Rated output current 2.4 O (40°C)
2Single-phase 200–240 V AC, 50/60 Hz

2.2 Core Specifications

ItemValoare
Rated power0.37 kW (0.5 HP)
Input voltageSingle-phase 200–240 V AC (±10%)
Output voltageThree-phase 0–240 V AC
Output frequency0–500 Hz
Overload capacity150% pentru 60 s, 180% pentru 2 s
CoolingNatural cooling
Dimensiuni (W×H×D)169×70×135 mm
GreutateAproximativ. 1.2 kg
Order code3AUA0000058166

3 Installation Procedure

3.1 Preparation

  1. Unpack and inspect drive for damage
  2. Choose well-ventilated, dust-free location inside cabinet
  3. Tools: Phillips screwdriver (PH2), wire stripper, crimping tool, multimeter, insulation tape

3.2 Mounting

  1. Mount vertically on flat metal plate
  2. Keep ≥ 100 mm above/below, ≥ 50 mm left/right clearance
  3. Fix with M4 screws, tightening torque: 1.2–1.5 N·m

4 Electrical Wiring

4.1 Terminal Description (ACS355-01E Series)

SectionTerminalDescriereWiring
Power CircuitL1/NSingle-phase 200–240 V input1.5–2.5 mm² copper
PEProtective earth≥ 2.5 mm² copper
U/V/W3-phase output to motor1.5–2.5 mm² copper
Circuit de controlDI1–DI3Digital inputs0.5–1.5 mm², max 50 m
AI1/AI2Analog inputs (0–10 V / 0–20 mA)Shielded twisted pair, max 100 m
AO1Analog output (0–20 mA)Shielded twisted pair, max 100 m
+24V/GND24 V DC supply (max 100 mA)0.5–1.5 mm²
RS485+/–Modbus RTUShielded twisted pair, max 1000 m

4.2 Pași de cablare

  1. Power wiring: L1/N to mains, PE to earth, U/V/W to motor
  2. Control wiring (Standard macro example):

DI1: Redirecţiona (FWD), DI2: Verso (REV), DI3: Reset

AI1: Speed reference (0–10 V)

  1. Check torque, izolare, and phase sequence

5 Setări parametri

5.1 Keypad Functions

▶/■: Început / Stop

▲/▼: Adjust value

ENTER: Confirm

ESC: Back

LOC/REM: Local / Remote

5.2 Quick Motor Settings (Group 99)

ParametruNumeSettingNota
9901LanguageChinese / EnglishUser choice
9902Application macro1 (Standard)General use
9903Motor type1 (Asynchronous)Standard induction motor
9904Motor rated power0.37 kWFrom nameplate
9905Motor rated voltage220/230/240 VFrom nameplate
9906Motor rated currentMotor nominalTypically ~2.1 A
9907Motor rated frequency50/60 HzFrom nameplate
9908Motor rated speedMotor nominal~1400–1450 rpm
9909Number of motor poles4Standard for 0.37 kW
9910Control mode1 (V/f)Scalar control

5.3 Common Application Parameters

GroupParametruNumeRecommended Value
101001Max frequency50/60 Hz
1002Min frequency0 Hz
202001Acceleration time3–10 s
2002Deceleration time3–10 s
212101Acc/dec type1 (Linear)
404001DI1 function1 (FWD)
4002DI2 function2 (REV)
4003DI3 function9 (RESET)
505001AI1 type1 (0–10 V)
5002AI1 minimum0%
5003AI1 maximum100%
161607Save parameters1

6 Commissioning Flow

6.1 Pre-Power Check

Correct power and control wiring

Motor and drive area clear

Cabinet ventilation OK

Input voltage: 200–240 V single-phase

6.2 First Power-Up

Close MCCB, display shows REM or LOC

Check for fault codes

Verify Group 99 motor parameters

6.3 Motor Identification (Opțional)

Set 9910 = 2 (ID Run)

Press ENTER; drive runs motor briefly

Completed when shown COMPLETE

6.4 Test fără sarcină

Switch to LOCAL

Run at 5 Hz, check rotation

Increase to rated frequency, check noise and vibration

6.5 Test de sarcină

Switch to REMOTE

Control speed via AI1

Check output current ≤ 2.4 O

Adjust acc/dec to avoid overcurrent

Test protection functions

7 Depanare

7.1 Common Fault Codes

FaultDescriereCauzaRemedy
OVERCURRENTOvercurrentSuprasarcina motorului, scurt-circuitCheck load, motor, parameters
OVERVOLTAGESupratensiuneHigh mains, fast decelerationCheck voltage, increase dec time
UNDERVOLTAGESubtensiuneLow supply, loose connectionCheck mains and wiring
OVERTEMPOverheatingHigh temp, blocked coolingImprove ventilation, clean heatsink
MOTOR OVERLOADSuprasarcina motoruluiExcessive loadCheck application, reduce load
FAULT RESETTrip reset requiredFault occurredFix cause, reset via DI3 or keypad

7.2 Typical Issues

SymptomCauzaSoluţie
Motor does not startWrong LOC/REM, missing DI signalCheck mode, wiring and parameters
Unstable speedAI noise, poor parametersUse shielded cable, adjust filtering
Communication failureWrong settings, bad wiringCheck Group 98, RS485, termination

8 Întreţinere

8.1 Routine Maintenance

Clean cooling channels every 6 months

Check terminal torque annually

Log operating current and temperature

8.2 Long-Term Storage

Temperature: -25°C până la +60°C

Dry, ventilated environment

Power on for 1 hour every 6 months

9 Appendix: Options and Replacements

9.1 Recommended Options

Braking resistor: 100 Oh / 50 W

EMC filter

RS485 Modbus RTU module

Shielded cable for control wiring

9.2 Cross-Brand Alternatives (0.37 kW, 1-phase 220 V, IP20)

MarcaModelMatching Features
SchneiderATV12HU04M20.37 kW, 1-phase 220 V, IP20
SiemensV20 6SL3210-5BB12-5UV10.37 kW, 1-phase 220 V, IP20
ChintNVF2-0.37/20.37 kW, 1-phase 220 V, IP20
ABBACS150-01E-02A4-2Direct same-power replacement

Manual Version: V1.0 (based on ABB official ACS355 manual, adapted for ACS355-01E-02A4-2)

Effective Date: February 2026

Copyright: ABB Group, Toate drepturile rezervate

Prev:

Lasă un răspuns