Full Name: CHINT JYB-714 Series Liquid Level Relay (YB-714 is a simplified model)
Key Specifications:
Control voltage: AC220V 50Hz
Contact rating: 3A AC220V (sarcină rezistivă)
Contact configuration: 1 changeover contact (NU + NC)
Probe current: ≤ 50μA (safe low current)
Control distance: ≤ 1km (length of probe cable)
Temperatura de functionare: -5°C ~ +40°C
- Funcții de bază & Aplicații
Funcţie: Detects water level via electrodes, automatically controls pump start/stop, supporting water supply / drainage modes.
Aplicații tipice:
Civil water towers, elevated tanks, underground cisterns
Industrial circulating water systems, small sewage treatment equipment
Not suitable for: Oil, pure water (low conductivity), flammable and explosive liquids
- Operating Principle (Electrode Detection)
- Water Supply Mode: When water level is below the low limit, electrodes 5-6 conduct, relay energizes, pump starts. When water rises to high limit, electrodes 6-7 conduct, relay de-energizes, pump stops.
- Drainage Mode: When water level exceeds high limit, electrodes 6-7 conduct, relay energizes, pump starts. When water drops to low limit, electrodes 5-6 disconnect, relay de-energizes, pump stops.
- Terminal Definition (Standard 8‑pin Base)
| Terminal No. | Funcţie | Wiring Description |
| 1 | Power Line L | Connect to AC220V Live wire |
| 2 | În mod normal închis (NC) | Commonly used for drainage mode |
| 3 | Common (COM) | Common terminal of contacts |
| 4 | Deschis normal (NU) | Commonly used for water supply mode |
| 5 | Power Neutral N | Connect to AC220V Neutral wire |
| 6 | Middle Level Electrode | Main detection electrode |
| 7 | High Level Electrode | Upper limit stop detection |
| 8 | Low Level Electrode | Lower limit start detection |
- Typical Wiring (Single‑phase Water Pump)
- Water Supply Control:
Terminal 1 to L, Terminal 5 to N
Terminal 6 to middle level, 7 to high level, 8 to low level
Terminal 4 (NU) + Terminal 3 (COM) connect to contactor coil control
- Drainage Control:
Terminal 1 to L, Terminal 5 to N
Terminal 6 to middle level, 7 to high level, 8 to low level
Terminal 2 (NC) + Terminal 3 (COM) connect to contactor coil control
- Instalare & Note de utilizare
- Electrode Installation:
Electrode material: 304 stainless steel recommended for corrosion resistance
Spacing: ≥ 10cm between high/low electrodes; ≥ 15cm between electrodes and tank wall
Avoid installation in bubble‑prone areas
- Electrical Safety:
Route signal cables separately, keep ≥ 30cm from power cables
Must be protected by a 10A circuit breaker
Use waterproof junction boxes in damp environments
- Daily Maintenance:
Clean scale and dirt from electrodes regularly to maintain conductivity
Inspect probe cable insulation for damage
- Common Faults & Depanare
| Fault Symptom | Cauza posibila | Soluţie |
| No operation at all | Poor power connection / incorrect voltage | Measure AC220V between terminals 1 şi 5 |
| Fails to detect water level | Broken probe wire / electrode fouling | Verificați cablajul, clean electrodes |
| Malfunction / false triggering | Excessively high sensitivity / shorted electrodes | Adjust electrode spacing, check insulation |
| Contact welding / sticking | Supraîncărcare / contact aging | Replace relay; install freewheeling diode across contactor coil |
- Selecţie & Alternative
Upgraded Model: JYB-714B (with LED indicator for clearer status)
Alternative Brands: Xinling HHY7G/HHY7P, People Electrical Appliance JYB series (parameter‑compatible)
Nota: For high‑power pumps, must use an AC contactor; do not drive directly (limited 3A contact capacity)
Recommended Replacements for CHINT JYB-714 (YB-714) 3A AC220V Liquid Level Relay
- CHINT Original Upgraded Alternatives
| Model | Key Improvements | Aplicație |
| JYB-714B AC220V | Added LED operating status indicator for clear visualization | All basic level control requiring status indication |
| JYB-714C AC220V | Dual LED indicators (supply/drain), enhanced anti-interference | Industrial environments with frequent mode switching |
Matching Core Parameters: All retain 3A AC220V contact rating, 1 changeover contact, electrode detection, fully compatible with original base and wiring.
- Direct Domestic Brand Alternatives (100% Parameter Compatible)
- Delixi Series
JYB-714 AC220V (tip standard)
JYB-714A AC220V (improved, stronger anti-interference)
Caracteristici: Same platform design as CHINT, universal 8‑pin base, lower price, wide service network.
- Xinling Electric Series
HHY7G AC220V (water supply dedicated)
HHY7P AC220V (drainage dedicated)
Caracteristici: 3A AC220V contact rating, control distance up to 100m, suitable for long probe cables.
- People Electrical Appliance Series
JYB-714 AC220V liquid level relay
Caracteristici: Compliant with GB/T14048.5, excellent moisture resistance, ideal for humid environments.
- Specialized Alternatives (Upgraded Functions / Medii speciale)
- CKC (Taiwan)
C61F-GP-N AC220V non-float liquid level relay
Avantaje: Imported quality, strong anti-interference, suitable for precision control, supports 3A AC220V load.
- OMRON
61F-GP AC220V liquid level control relay
Avantaje: Internationally renowned, high reliability, LED status indication, potrivit pentru echipamente critice.
Nota: Requires dedicated base, higher cost.
- Wireless / Smart Alternative
CHINT NB-IoT Intelligent Liquid Level Controller: Remote monitoring, mobile APP control, suitable for unattended sites.
Caracteristici: No wiring needed, data transmission via NB-IoT, supports water level alarms and history query.
- Key Compatibility Requirements for Replacement
| Key Parameter | Must Match | Note |
| Contact Rating | 3A AC220V (sarcină rezistivă) | Direct for small loads; contactor required for high power |
| Configurare contact | 1 changeover contact (NU + NC) | Ensures both supply and drainage modes |
| Tensiune de operare | AC220V 50Hz | Matches original power supply |
| Mounting Base | Standard 8‑pin base | Direct replacement without re-drilling |
| Detection Method | Electrode type (≤50μA safe current) | Compatible with existing probe cables |
- Recommendation Priority
- First Choice: CHINT JYB-714B/C → Original upgrade, fully compatible, clear indication
- Best Value: Delixi JYB-714A → Affordable, stable, convenient service
- Industrial Use: Xinling HHY7G/7P → Long distance, strong anti-interference
- Critical Equipment: OMRON 61F-GP → High reliability for continuous operation
Complete Model List of CHINT Liquid Level Relays
CHINT liquid level relays are available in three main series: JYB-714 (basic type), NJYW1 (industrial enhanced type), and NJB1-YW (modular type). Below is the complete model list by series.
- JYB-714 Series (Core Basic Series)
1.1 Modele standard
| Model | Tensiune de control | Key Features | Sample Order No. |
| JYB-714 AC36V | AC36V 50Hz | Versiunea de bază, no indicator | 710039910301036 |
| JYB-714 AC220V | AC220V 50Hz | Versiunea de bază, no indicator | 710039910301037 |
| JYB-714 AC380V | AC380V 50Hz | Versiunea de bază, no indicator | 710039910301038 |
1.2 Modele îmbunătățite (with LED Indicator)
| Model | Tensiune de control | Key Features | Sample Order No. |
| JYB-714B AC36V | AC36V 50Hz | Single LED operation indicator | 710039910301378 |
| JYB-714B AC220V | AC220V 50Hz | Single LED operation indicator | 710039910301379 |
| JYB-714B AC380V | AC380V 50Hz | Single LED operation indicator | 710039910301380 |
| JYB-714C AC220V | AC220V 50Hz | Dual LED (supply/drain), enhanced anti-interference | 710039910401379 |
| JYB-714C AC380V | AC380V 50Hz | Dual LED (supply/drain), enhanced anti-interference | 710039910401380 |
Common Parameters:
Contact rating: 3A AC220V (sarcină rezistivă)
Contact configuration: 1 changeover contact (NU + NC)
Probe current: ≤ 50μA
Control distance: ≤ 1km
Montare: Standard 8‑pin base (universal)
- NJYW1 Series (Industrial Enhanced Series)
| Model | Tensiune de control | Key Features | Aplicație |
| NJYW1-NL1 AC220V | AC220V 50Hz | Standard, moisture-resistant | Civil / light industrial water towers |
| NJYW1-NL1 AC380V | AC380V 50Hz | Standard, moisture-resistant | Industrial water tanks |
| NJYW1-NL2 AC220V | AC220V 50Hz | Long distance (≤2km) | Large water conservancy |
| NJYW1-NL2 AC380V | AC380V 50Hz | Long distance (≤2km) | Sewage treatment plants |
| NJYW1-BL1 AC220V | AC220V 50Hz | Explosion‑proof | Chemical industry, underground pump rooms |
| NJYW1-BL1 AC380V | AC380V 50Hz | Explosion‑proof | Petrochemical tank farms |
| NJYW1-BL2 AC220V | AC220V 50Hz | Explosion‑proof + long distance | Offshore platforms, mine drainage |
| NJYW1-BL2 AC380V | AC380V 50Hz | Explosion‑proof + long distance | Tunnel drainage systems |
Series Advantages: Protection class IP40, improved anti-interference, stable probe current ≤40μA.
- NJB1-YW Series (Modular Series)
| Model | Tensiune de control | Montare | Aplicație |
| NJB1-YW AC220V | AC220V 50Hz | Montare pe șină DIN | Automation control panels |
| NJB1-YW AC380V | AC380V 50Hz | Montare pe șină DIN | Industrial automation systems |
| NJB1-YW DC24V | DC24V | Montare pe șină DIN | DC control systems, PLC integration |
Caracteristici:
Montare pe șină DIN (35mm standard) for automation integration
Fault diagnosis, PLC compatible
Contact rating increased to 5A AC220V, suitable for direct small pump control
- Model Naming Explanation
- JYB-714 Series: JYB (liquid level relay)-714 (design code)-[A/B/C] (version: A=basic, B=single LED, C=dual LED)-Voltaj
- NJYW1 Series: N (CHINT) JYW (liquid level relay) 1 (code)-[NL/BL] (NL=standard, BL=explosion‑proof)-[1/2] (distance: 1=1km, 2=2km)-Voltaj
- NJB1-YW Series: N (CHINT) JB (modular) 1 (code)-YW (liquid level control)-Voltaj
- Selection Parameter Comparison
| Parametru | JYB-714 Series | NJYW1 Series | NJB1-YW Series |
| Contact Rating | 3A AC220V | 3A AC220V | 5A AC220V |
| Control Distance | ≤1km | ≤1–2km | ≤1km |
| Montare | 8‑pin base | 8‑pin base / rail | 35mm șină DIN |
| Indicator | Opțional (B/C type) | Standard | Standard |
| Anti-interference | Basic | Industrial | Industrial |
| Mediu | Civil / light industry | Industrial / humid | Automation systems |
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare