Întrerupător motor GV3P80 - Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare

întrerupător de circuit/

Întrerupător motor GV3P80

GV3P80 is a 3‑pole thermal‑magnetic motor circuit breaker from Schneider Electric TeSys GV3 series. It has an adjustment current range of 70–80A, suitable for 45kW (400V) / 55kW (690V) three‑phase motors. It integrates triple protection (suprasarcina, short‑circuit, phase failure) and isolation function, serving as a core protection component in industrial motor circuits. Model Explanation GV3: ...

  • Detalii despre produs

GV3P80 is a 3‑pole thermal‑magnetic motor circuit breaker from Schneider Electric TeSys GV3 series. It has an adjustment current range of 70–80A, suitable for 45kW (400V) / 55kW (690V) three‑phase motors. It integrates triple protection (suprasarcina, short‑circuit, phase failure) and isolation function, serving as a core protection component in industrial motor circuits.

  1. Explicația modelului

GV3: TeSys GV3 motor circuit breaker series (frame size 3)

P: Thermal‑magnetic release (triple protection: suprasarcina + short‑circuit + phase failure)

80: Rated current 80A, adjustable range 70–80A (continuously adjustable)

  1. Key Specifications (Full Data)
ArticolCaietul de sarcini
Poles3P (three‑phase)
Adjustment current range70–80A (continuously adjustable)
Tip de călătorieThermal‑magnetic
Short‑circuit trip multiplier14×In (1120O)
Breaking capacity Icu65kA @ 230V; 50kA @ 400V; 6kA @ 690V
Rated operational voltage Ue690V AC 50/60Hz
Insulation voltage Ui690V și
Impulse withstand voltage Uimp6kV
Suitable motor power45kW @ 400V; 55kW @ 690V; 22kW @ 230V
TerminalsEverLink screw terminals (25–35mm² cable)
MountingDIN rail (width 55mm), screw mountable
Degree of protectionIP20 (front)
Temperatura de functionare-20°C ~ +60°C (derating factor: 0.8 at +60°C)
Mechanical endurance50,000 operating cycles
Electrical endurance20,000 cycles (category AC‑3)
Isolation functionComplies with IEC 60947‑1, can be used as safety isolator
CertificariCCC, CE, UL, CSA, IEC 60947‑4‑1
GreutateAproximativ. 1.02 kg
Dimensiuni (W×H×D)55 × 105 × 78 mm
  1. Funcții de bază & Avantaje
  2. Triple Protection

Thermal trip: Overload inverse‑time protection (simulates motor heating characteristics)

Magnetic trip: Short‑circuit instantaneous protection (fixed 14×In)

Protecție împotriva defecțiunii de fază: Automatic trip under three‑phase unbalance (IEC 60947‑4‑1)

  1. EverLink Terminal Technology

Maintenance‑free, anti‑loosening, oxidation‑resistant, suitable for large‑section cables, reduces wiring failure risks.

  1. Safety Design

Knob operation, lockable in OFF position (până la 3 padlocks)

Clear current scale for precise adjustment

Complies with IEC isolation standards, usable as motor circuit isolator

  1. Wide Environmental Adaptability

Operating altitude: ≤3000m (no derating required)

Vibration resistance: 10–150Hz, 0.5mm amplitude

Shock resistance: 5Gn (11Domnișoară); 30Gn (1Domnișoară)

  1. Referință de selecție (TeSys GV3 Series)
ModelAdjustment CurrentSuitable Power (400V)Tip de călătorieCaracteristici
GV3P6555–65A37kWThermal‑magneticStandard, EverLink terminals
GV3P8070–80A45kWThermal‑magneticThis model, max adjustment current
GV3L8070–80A45kWMagneticShort‑circuit protection only
GV3ME8040–80A45kWThermal‑magnetic3‑step adjustment (40–50/63–80), economy version
GV3P4030–40A22kWThermal‑magneticFor small‑medium motors
  1. Applications

Pornire directă / star‑delta starting circuits for three‑phase asynchronous motors

Main circuit protection for fans, pompe, compresoare, transportoare, masini-unelte

Industrial automation lines, construction equipment motor control

Motor circuits requiring isolation and safety interlock (de ex., emergency stop loops)

Motors with frequent starting/stopping and fluctuating loads

  1. Replacement Options
  2. Schneider same series

GV3L80 (short‑circuit only, lower cost)

GV3ME80 (simplified adjustment, same mounting space)

  1. Competitor alternatives

Siemens: 3RV1041‑4JA10 (70–80A, 3P, thermal‑magnetic)

ABB: MS165‑80 (70–80A, 3P, thermal‑magnetic)

Chinese brands: Chint NM1‑125S, Delixi CDM1‑125 (motor protection curve matching required)

  1. Upgrade solution

Schneider GV4P08N (frame 4, capacitate de rupere mai mare, for motors above 55kW)

Selection Tips

  1. Select adjustment range at 1.1–1.25 × motor rated current
  2. Confirm breaking capacity meets system short‑circuit current requirements
  3. For isolation function, prefer models with certified isolation
  4. For limited wiring space, choose EverLink terminal models to reduce faults

Complete Model List of Schneider Electric TeSys GV Series Motor Circuit Breakers

Schneider TeSys GV series motor circuit breakers include six sub‑series: GV1, GV2, GV3, GV4, GV5, GV6, covering an adjustment range from 0.06A to 800A, suitable for 0.03kW to 400kW (400V) three‑phase motors, with thermal‑magnetic, magnetic, and economy thermal‑magnetic protection types.

  1. GV1 Series (Miniature, discontinued, replaced by GV2ME)

GV1ME01: 0.1–0.16A

GV1ME02: 0.16–0.25A

GV1ME03: 0.25–0.4A

GV1ME04: 0.4–0.63A

GV1ME05: 0.63–1.0A

GV1ME06: 1.0–1.6A

GV1ME07: 1.6–2.5A

GV1ME08: 2.5–4.0A

  1. GV2 Series (Small, 0.06–16A, 0.03–15kW/400V)

2.1 GV2P (Thermal‑magnetic, full protection, knob)

ModelAdjustment CurrentSuitable Power (400V)
GV2P010.1–0.16A0.06kW
GV2P020.16–0.25A0.12kW
GV2P030.25–0.4A0.2kW
GV2P040.4–0.63A0.37kW
GV2P050.63–1.0A0.55kW
GV2P061.0–1.6A0.75kW
GV2P071.6–2.5A1.5kW
GV2P082.5–4.0A2.2kW
GV2P104.0–6.3A3kW
GV2P146.3–10A4kW
GV2P1610–16A7.5kW

2.2 GV2L (Magnetic, short‑circuit only, knob)

ModelAdjustment CurrentSuitable Power (400V)
GV2L010.1–0.16A0.06kW
GV2L020.16–0.25A0.12kW
GV2L030.25–0.4A0.2kW
GV2L040.4–0.63A0.37kW
GV2L050.63–1.0A0.55kW
GV2L061.0–1.6A0.75kW
GV2L071.6–2.5A1.5kW
GV2L082.5–4.0A2.2kW
GV2L104.0–6.3A3kW
GV2L146.3–10A4kW
GV2L1610–16A7.5kW
GV2L2014–20A11kW
GV2L2218–25A15kW

2.3 GV2ME (Economy thermal‑magnetic, pushbutton, 3‑step)

ModelAdjustment CurrentSuitable Power (400V)
GV2ME010.1–0.16A0.06kW
GV2ME020.16–0.25A0.12kW
GV2ME030.25–0.4A0.2kW
GV2ME040.4–0.63A0.37kW
GV2ME050.63–1.0A0.55kW
GV2ME061.0–1.6A0.75kW
GV2ME071.6–2.5A1.5kW
GV2ME082.5–4.0A2.2kW
GV2ME104–6.3A3kW
GV2ME146.3–10A4kW
GV2ME1610–16A7.5kW

2.4 GV2LE (Magnetic with electronic trip, special applications)

GV2LE01 ~ GV2LE22: matching current ratings as GV2L, with electronic trip

  1. GV3 Series (Medium, 9–80A, 5.5–45kW/400V, 55mm latime)

3.1 GV3P (Thermal‑magnetic, full protection, EverLink)

ModelAdjustment CurrentSuitable Power (400V)
GV3P139–13A5.5kW
GV3P1813–18A11kW
GV3P2518–25A15kW
GV3P3223–32A18.5kW
GV3P4030–40A22kW
GV3P5040-50A30kW
GV3P6555–65A37kW
GV3P7365–73A45kW
GV3P8070–80A45kW

3.2 GV3L (Magnetic, short‑circuit only)

GV3L25: 18–25A

GV3L32: 23–32A

GV3L40: 30–40A

GV3L50: 40-50A

GV3L65: 55–65A

GV3L80: 70–80A

3.3 GV3ME (Economy thermal‑magnetic, 3‑step)

ModelAdjustment CurrentSuitable Power (400V)
GV3ME4040-50A30kW
GV3ME6350–63A37kW
GV3ME8040–80A (3 steps: 40–50/63–80)45kW
  1. GV4 Series (Large, 25–115A, 15–55kW/400V, 81mm latime)

4.1 GV4P (Thermal‑magnetic, full protection)

ModelAdjustment CurrentSuitable Power (400V)
GV4P2525–32A18.5kW
GV4P4032–40A22kW
GV4P5040-50A30kW
GV4P6350–63A37kW
GV4P8063–80A45kW
GV4P10080–100A55kW
GV4P115100–115A55kW

4.2 GV4L / GV4LE (Magnetic type)

GV4L25 ~ GV4L115: matching current ratings as GV4P

GV4LE25 ~ GV4LE115: magnetic with electronic trip

4.3 Special GV4 Models

GV4PB80S: UL489 approved, 63–80A

GV4P02N: 2‑pole thermal‑magnetic, special applications

  1. GV5 / GV6 Series (Extra‑large, 100–800A, 55–400kW/400V)

GV5P100: 80–100A

GV5P125: 100–125A

GV5P160: 125–160A

GV5P200: 160–200A

GV6P250: 200–250A

GV6P315: 250–315A

GV6P400: 315–400A

GV6P500: 400–500A

GV6P630: 500–630A

GV6P800: 630–800A

 

  1. Model Naming Rules
Letter/NumberSens
GVTeSys GV series motor circuit breaker
1/2/3/4/5/6Frame size (1 = smallest, 6 = largest)
PThermal‑magnetic trip (suprasarcina + short‑circuit + phase failure)
LMagnetic trip (short‑circuit only)
MEEconomy thermal‑magnetic trip (3‑step, cost‑optimized)
THEMagnetic trip with electronic functions
NumberCurrent rating (de ex., 80 = 70–80A)
  1. Quick Selection Guide
  2. Select adjustment range at 1.1–1.25 × motor rated current
  3. For full protection (suprasarcina + short‑circuit + phase failure): choose P series
  4. If thermal protection exists (de ex., VFD): choose L series (short‑circuit only)
  5. Cost‑sensitive, simple adjustment: choose ME series (3‑step)
  6. Small motors (≤15kW): GV2; medium (15–45kW): GV3; large (≥55kW): GV4–GV6
  7. Note
  8. All models are 3‑pole (3P) for three‑phase asynchronous motors
  9. Protection characteristics comply with IEC 60947‑4‑1
  10. Capacitate de rupere: GV2/GV3 100kA@400V; GV4 65kA@400V
  11. Mounting: 35mm standard DIN rail
  12. Degree of protection: IP20 (front operating part)