| Segmentul de model | Descriere |
| FR | General prefix for Mitsubishi inverters (Frequency Inverter) |
| A840 | Standard model of A800 series for 400V class, high-performance vector control for general industrial use |
| 2600 | Capacity code, corresponding to Normal Duty (ND) 90kW/180A, Super Light Duty (SLD) 132kW/260A |
| 2 | CA type (current control, standard 0–20mA analog input) |
| 60 | Conformal coating on circuit boards, non-plated conductors, enhanced environmental resistance |
- Core Electrical Specifications
| Articol | Normal Duty (ND) | Super Light Duty (SLD) | Light Duty (LD) |
| Applicable Motor Power | 90kW (150HP) | 132kW (177HP) | 110kW (147HP) |
| Rated Output Current | 180O | 260O | 216O |
| Putere de intrare | 3-phase AC 380–480V, 50/60Hz (±10% tolerance) | ||
| Tensiune de ieșire | 3-phase AC 0–input voltage, proportional to input voltage | ||
| Output Frequency | 0.2–590Hz (max 400Hz in vector control mode) | ||
| Control Method | Sensorless Vector Control (RSV), Control V/F, PM Sensorless Vector Control, compatible with Induction Motors (IM) and Permanent Magnet Motors (IPM) | ||
- Key Features
- High‑Performance Control
Universal vector control, high torque at low speed; 150% rated torque at 0.5Hz
Built-in PID controller for various closed-loop applications
Automatic energy-saving operation, adjusts output voltage according to load to reduce power consumption
- Structura & Protecţie
Protection class IP00 (open type), suitable for cabinet mounting
Circuit boards with conformal coating (conform cu IEC 60721-3-3), resistant to dust, oil, and humidity
Protecție cuprinzătoare: supracurent, supratensiune, subtensiune, supraîncălzire, earth fault, motor overload, phase loss protection, etc.
- Built-in Interfaces & Expandability
Standard RS-485 communication (Modbus RTU protocol)
Supports various fieldbus extensions: PROFIBUS-DP, DeviceNet, EtherNet/IP, etc.
Analog inputs: 2 canale (0–10V / 0–20mA, 1 channel dedicated for CA-type 0–20mA)
Digital I/O: 5 inputs, 2 outputs (expandable)
- Capacitate de suprasarcină & Parametrii de mediu
| Tip de încărcare | Capacitate de suprasarcină | Condiții de mediu |
| Normal Duty (ND) | 150% curent nominal pentru 60 de secunde, 200% rated current for 3s (inverse-time characteristic) | Operating temp: -10℃to 50℃C (derating above 40℃C) |
| Super Light Duty (SLD) | 110% curent nominal pentru 60 de secunde, 120% rated current for 3s | Storage temp: -20℃ to 65℃ |
| Light Duty (LD) | 120% curent nominal pentru 60 de secunde, 150% rated current for 3s | Relative humidity: 5% la 95% (necondens) |
- Aplicații tipice
General industrial machinery: compresoare, pompe, fani, transportoare, mixere, etc.
Metal processing: fusuri de mașini-unelte, winding equipment, wire drawing machines
Lifting & conveying: macarale, lifturi, automated storage systems
Chemical & farmaceutic: mixing, reaction, and conveying equipment in process industries
Clădire & HVAC: sisteme de aer conditionat, pompe, fan energy-saving control
- Instalare & Ghid de selecție
- Cerințe de instalare
Forced-air cooling; ensure sufficient ventilation (≥100mm clearance on all sides)
Montați vertical, avoid direct sunlight and corrosive gas environments
Recommended input reactor and EMC filter for improved stability and EMC performance
- Note de selecție
Select load rating based on actual load type (constant torque / variable torque)
For frequent starting/stopping or heavy starting, select one frame size larger than motor power
For long cable runs, consider voltage drop and dv/dt effects; install output reactor if necessary
- Replacement Models & Informații de comandă
Înlocuire directă: FR-A840-02600-E2-60 (European version, no built-in DC reactor)
Upgraded model: FR-A840-02600-E2-60CRN (with Ethernet interface)
Official order number: 297582 (base model)
The Mitsubishi FR-A840-02600-2-60 is a high-performance, high-reliability 400V-class vector inverter, ideal for driving medium-to-high power motors and providing precise speed and torque control in various industrial automation scenarios. Its CA-type control and conformal coating ensure excellent performance in harsh industrial environments.
Mitsubishi FR Series Inverter Model List & Cross-Brand Comparison
- Classification & Model Meaning of Mitsubishi FR Series
1.1 Series Overview
| Serie | Clasa de tensiune | Gama de putere | Core Position | Aplicații tipice |
| FR-A800 | 200V (FR-A820) / 400V (FR-A840) | 0.4kW–500kW | Flagship high-performance vector control | Industrie grea, high-precision torque control, complex motion control |
| FR-F800 | 200V (FR-F820) / 400V (FR-F840) | 0.4kW–400kW | Energy-saving for fans & pompe | HVAC, water treatment, building automation |
| FR-E800/FR-E700 | 200V/400V | 0.1kW–22kW | Compact general-purpose | Packaging machinery, food & beverage, small production lines |
| FR-D800/FR-D700 | 200V/400V | 0.1kW–75kW | Easy-to-use economy type | Small fans/pumps, transportoare, general machinery |
| FR-CS80 | 200V/400V | 0.4kW–315kW | Heavy-duty special type | Cranes, winders, metallurgical equipment |
| FR-B | 200V/400V | 0.4kW–75kW | Explosion-proof special type | Hazardous areas such as chemical, petroleum, mine de cărbune |
1.2 Full Model Format Explanation
Standard format: FR-XXX-YYYYY-Z-W
| Field | Sens | Exemplu |
| FR | General prefix for Mitsubishi inverters (Frequency Inverter) | – |
| XXX | Cod de serie + clasa de tensiune | A840 (400V high-performance), F820 (200V fan/pump) |
| YYYYY | Capacity code/power identifier | 02600 (90kW/180A), 15K (15kW) |
| Z | Control type | 1 (standard, 0–10V), 2 (CA type, 0–20mA), E2 (European version, no built-in DC reactor) |
| W | Special functions | 60 (conformal coating), CRN (Ethernet), R2R (winding dedicated) |
- Complete Model List of Mitsubishi FR Series Inverters
2.1 FR-A840 (400V High-Performance Vector Control) Core Models
| Applicable Motor Power | ND Current | SLD Current | Base Model | Special Model |
| 0.75kW | 2.1O | 3.0O | FR-A840-00038-2-60 | FR-A840-00038-E2-60 |
| 1.5kW | 3.7O | 5.3O | FR-A840-00052-2-60 | – |
| 2.2kW | 5.0O | 7.2O | FR-A840-00072-2-60 | – |
| 5.5kW | 11.5O | 16.5O | FR-A840-00170-2-60 | – |
| 11kW | 23O | 33O | FR-A840-00330-2-60 | – |
| 15kW | 30O | 43O | FR-A840-00430-2-60 | – |
| 30kW | 60O | 86O | FR-A840-00860-2-60 | FR-A840-00860-E2-60 |
| 90kW | 180O | 260O | FR-A840-02600-2-60 | FR-A840-02600-E2-60 |
| 132kW | 240O | 345O | FR-A840-03450-2-60 | – |
| 280kW | 500O | 720O | FR-A840-07200-2-60 | – |
2.2 Representative Models of Other Main Series
| Serie | Representative Model | Putere | Key Features |
| FR-F840 | FR-F840-5.5K-2 | 5.5kW | Fan/pump dedicated, built-in PID, energy-saving control |
| FR-E740 | FR-E740-1.5K-CHT | 1.5kW | Compact, built-in EMC filter |
| FR-D740 | FR-D740-7.5K-CHT | 7.5kW | Simple operation, rentabil |
| FR-A820 | FR-A820-37K-1 | 37kW | 200V high-performance, suitable for light industry |
- Cross-Brand Inverter Comparison Table
Below shows functional and power matching between Mitsubishi FR series and major brands including Siemens, Schneider, ABB. Precise selection should consider actual load characteristics and control requirements.
| Mitsubishi Model | Siemens Equivalent | Schneider Equivalent | ABB Equivalent | Functional Match |
| FR-A840-02600-2-60 (90kW) | SINAMICS G120C 90kW | ATV630D11N4 | ACS580-01-180A-4 | High-performance vector control, suitable for heavy-duty applications |
| FR-F840-5.5K-2 (5.5kW) | SINAMICS G120X 5.5kW | ATV610U75N4 | ACS580-01-015A-4 | Fan/pump dedicated, energy-saving control |
| FR-E740-1.5K (1.5kW) | SINAMICS V20 1.5kW | ATV320U15N4 | ACS180-04-03A3-4 | Compact general-purpose |
| FR-A820-37K-1 (37kW, 200V) | SINAMICS G120 37kW 200V | ATV630D45N2 | ACS580-04-075A-2 | Medium-power vector control for 200V systems |
| FR-CS840-110K (110kW) | SINAMICS S120 110kW | ATV930D160N4 | ACS880-01-246A-3 | Heavy-duty, four-quadrant operation |
- Puncte cheie ale selecției & Note
- Load Matching Principles
Constant torque loads (transportoare, mixere): select FR-A800 series, rated by ND current
Variable torque loads (fani, pompe): select FR-F800 series, rated by SLD current
Frequent start/stop or heavy starting: select one size larger than motor power
- Special Environment Adaptation
Harsh industrial environments: prefer models with “60” suffix (conformal coating: FR-A840-XXXXX-2-60)
Explosive/flammable environments: select FR-B series explosion-proof inverters
Ethernet communication: select models with “CRN” suffix
- Instalare & Sfaturi de întreținere
Vertical mounting, ≥100mm clearance on all sides for ventilation
For long cables, recommend output reactor to reduce dv/dt influence
Regular inspection of cooling fans and capacitors for long-term stable operation
Mitsubishi FR series inverters cover a full power range from 0.1kW to 500kW, meeting diverse needs from basic control to high-precision motion control via differentiated series positioning. For cross-brand selection, focus on core parameters including control method, capacitate de suprasarcina, communication protocol, and environmental resistance to ensure system compatibility and stability.
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare





















NH42-63-318x560.png)