- Model Code Breakdown
| Code Segment | Sens | Detailed Description |
| FX5 | Series Identifier | Mitsubishi MELSEC iQ-F series, 5th-generation high-performance compact PLC platform, compatible with FX5U/FX5UC/FX5UJ CPUs, supporting high-speed system bus communication |
| 4 | Number of Channels | 4 canale de ieșire analogice independente, capable of simultaneously outputting different analog signals |
| DA | Function Type | Digital-to-Analog conversion, converting PLC digital signals into analog voltage/current signals recognizable by external actuators |
| No Suffix | Installation Type | Basic type with spring clamp terminal block design, directly mounted on the expansion bus to the right of the CPU (non-ADP adapter type) |
- Parametrii tehnici de bază
2.1 Basic Specifications
| Parametru | Valoare | Observații |
| Numărul de canale de ieșire | 4 canale (independent) | Each channel can be independently configured for voltage or current output |
| Occupied I/O Points | 8 points | 4 points for input and 4 points for output |
| Conversion Speed | 80μs per channel | High-speed conversion, suitable for dynamic control scenarios |
| Power Requirement | DC5V, aproximativ. 120mA | Powered by FX5 series CPU or dedicated power module |
| Insulation Method | Optocoupler insulation between output terminals and PLC, non-insulated between channels | Anti-interference design to protect PLC system |
| Clasa de protectie | IP20 | For cabinet installation, rezistent la praf |
| Dimensiuni (W×H×D) | 40mm×90mm×102.2mm | Compact design, saving cabinet space |
| Greutate | Aproximativ. 0.2kg | Lightweight, easy to install |
| Temperatura de operare | 0~55℃ | Industrial standard environment |
2.2 Analog Output Performance Parameters
| Output Type | Range | Corresponding Digital Value | Rezoluţie | Accuracy (25±5℃) | Deviation Range |
| Tensiune de ieșire | 0~10V | 0~32000 | 312.5μV | ±0.1%FS | ±20mV |
| 0~5V | 0~32000 | 156.25μV | ±0.1%FS | ±10mV | |
| 1~5V | 6400~32000 | 125μV | ±0.1%FS | ±8mV | |
| -10~+10V | -32000~+32000 | 312.5μV | ±0.1%FS | ±20mV | |
| Ieșire curentă | 0~20mA | 0~32000 | 625nA | ±0.1%FS | ±20μA |
| 4~20mA | 6400~32000 | 500nA | ±0.1%FS | ±16μA |
Accuracy Note: Accuracy is ±0.2%FS within the temperature range of -20~55℃
- Scenarii de aplicare & Guidance
3.1 Typical Application Fields
| Industry | Scenariul aplicației | Specific Cases |
| Process Control | Flow/Pressure/Temperature Regulation | Valve positioner control, PID loop regulation, temperature controllers |
| Motion Control | Speed/Torque Control | Inverter frequency setting, servo drive speed control, DC motor speed regulation |
| Automatizare industrială | Actuator Control | Proportional valves, hydraulic systems, pneumatic control valves, analog display instruments |
| Test & Measurement | Signal Simulation | Sensor simulation, test equipment calibration, analog signal generators |
| Medical Equipment | Precision Control | Medical analyzers, laboratory equipment, pharmaceutical machinery |
3.2 Puncte cheie de selecție
- Channel Requirement: Confirm the required number of analog output channels; 4 channels meet most small and medium-sized control systems
- Output Type: Select voltage (0~10V/-10~+10V) or current (4~20mA) output based on actuator type
- Accuracy Requirement: Choose FX5-4DA for high-precision control (de ex., ±0.1%); consider economical alternatives for general control
- Response Speed: Verify if 80μs conversion speed meets requirements for fast dynamic response systems (de ex., servo control)
- Metoda de instalare: FX5-4DA mounts directly to the right of the CPU; FX5-4DA-ADP mounts on DIN rail via extension cable
- Compatibilitate: Only compatible with FX5 series CPUs; select corresponding models for older series like FX3U
- Instalare & Configuration Guide
4.1 Etape de instalare
- Power-off Operation: Cut off all PLC power before installation to prevent electric shock
- Mechanical Installation:
Mount directly on the expansion bus to the right of FX5U/FX5UC CPU, align with the guide rail and push to lock
For multiple module expansion, install in sequence with ≥5mm gap between modules for heat dissipation
- Specificații de cablare:
Use shielded twisted pair for analog output wiring, with shield grounded at one end (PLC side)
Separate power and signal wiring with a distance ≥100mm to avoid interference
Terminal wiring: +V for positive, -V for negative, COM as common terminal
- Grounding Requirements:
Adopt Class D grounding (ground resistance ≤100Ω) with grounding wire ≥2mm²
Prohibit shared grounding with high-power equipment to prevent ground potential interference
4.2 GX Works3 Parameter Configuration Steps
- Module Addition:
Right-click “Module Information” in project tree → “Add New Module” → Select “Ieșire analogică” → “FX5-4DA” → Set unit number
- Channel Parameter Setting:
Double-click the module to enter parameter interface, set for each channel:
Output type (Voltage/Current)
Range (de ex., 0~10V, 4~20mA)
Output hold function (maintain last output value after power-off)
Calibration parameters (Auto/Manual calibration)
- Programming:
Read/write module data via FROM/TO instructions or use GX Works3 dedicated instructions
Digital-to-analog conversion formula: Analog output value = Digital value × Range / 32000 (unipolar) sau 64000 (bipolar)
4.3 Calibration Process
- Auto Calibration: Execute “Auto Calibration” function in GX Works3; the module automatically completes zero and gain calibration
- Manual Calibration:
Short-circuit output terminals, adjust zero potentiometer to achieve 0 output
Input full-scale digital value, adjust gain potentiometer to achieve full-scale output
- Calibration Cycle: Recommended every 6 luni; shorten to 3 months in harsh environment
- Modele alternative & Recomandări de selecție
5.1 Mitsubishi Same-series Alternative/Upgrade Models
| Model | Main Differences | Scenariul aplicației |
| FX5-4DA-ADP | ADP adapter type, mounted on DIN rail via FX5-ADP-BUS cable, up to 10m from CPU | Limited cabinet space, remote installation required |
| FX5-2DA | 2-channel version, occupying 4 I/O points with more compact size (25mm latime) | Fewer channel requirements, space-saving |
| FX5-8DA | 8-channel version to meet multi-channel control needs | Large-scale control systems requiring more analog outputs |
| FX5U-4DA | Analog output built into FX5U CPU, no additional expansion module needed | Cost-saving, simplified system structure |
| FX5-4DA-P | High-precision version with accuracy improved to 卤0.05%FS | Ultra-high precision control (de ex., process control, echipament medical) |
5.2 Cross-series/Cross-brand Alternative Models
| Marca | Alternative Model | Matching Degree | Caracteristici |
| Mitsubishi FX3U Series | FX3U-4DA | ★★★★☆ | Compatible with FX5U via FX5-CNV-IF adapter, accuracy ±0.2%FS, conversion speed 10ms |
| Siemens | SM 1232 | ★★★★ | S7-1200 series, 4 canale, accuracy ±0.1%FS |
| Schneider | TM2DAI4 | ★★★★ | Modicon M221 series, 4 canale, hot-swappable |
| Domestic Alternative | Tanshuo FX5-4DA-ADP | ★★★★ | Fully compatible with Mitsubishi FX5 series, more cost-effective |
| Omron | CJ1W-DA041 | ★★★☆ | CJ series, 4 canale, conversion speed 50μs |
- Întreţinere & Depanare
6.1 Regular Maintenance Schedule
| Ciclul de întreținere | Articol | Standard | Maintenance Measures |
| Monthly | Inspecție vizuală | No damage, lejeritate, or overheating marks | Clean dust on module surface, check terminal connections |
| Quarterly | Signal Test | Output error ≤±0.1%FS | Measure each channel output with multimeter and compare with set value |
| Every 6 Months | Calibration Check | Zero offset ≤±10mV/±10μA | Perform auto calibration, manual adjustment if necessary |
| Annual | Insulation Test | Insulation resistance ≥10MΩ (500V megohmmeter) | Test module insulation performance under power-off condition |
| System Upgrade | Actualizare firmware | Latest version | Update module firmware via GX Works3 to fix known issues |
6.2 Depanarea defecțiunilor comune & Soluții
| Fenomen de eroare | Cauze posibile | Priority | Pași de depanare |
| No Output Signal | 1. Unconfigured module | High | 1. Check GX Works3 parameter configuration |
| 2. Disabled output channel | 2. Enable channel output function | ||
| 3. Incorrect wiring | 3. Verify wiring (+V/-V/COM) | ||
| 4. Power failure | 4. Measure module DC5V power supply | ||
| Output Accuracy Deviation | 1. Uncalibrated or expired calibration | Medium | 1. Perform auto calibration |
| 2. Ambient temperature out of range | 2. Improve heat dissipation and control ambient temperature | ||
| 3. Mismatched load resistance | 3. Voltage output load ≥400kΩ, current output load 250~500Ω | ||
| 4. Module aging | 4. Replace module | ||
| Output Fluctuation | 1. Excessive power supply ripple | Medium | 1. Install power filter |
| 2. Signal interference | 2. Check shield grounding and keep away from power lines | ||
| 3. Poor grounding | 3. Optimize grounding system with independent grounding | ||
| 4. Unstable load | 4. Check actuator load | ||
| Module Error Report | 1. Incompatible firmware version | High | 1. Update module firmware to latest version |
| 2. Poor expansion bus connection | 2. Reconnect module and check expansion bus | ||
| 3. Damaged module | 3. Replace module for testing |
- Safe Operation Specifications
- Power-off Operation: All installation, cablare, and maintenance work must be performed with PLC completely powered off
- ESD Protection: Discharge static electricity from human body before touching the module to avoid damaging electronic components
- Specificații de cablare:
Prohibit connecting AC power to DC module terminals (may cause module burnout)
Prohibit external wiring to empty terminals to prevent short circuit
- Potrivirea încărcării:
Voltage output: External load resistance ≥400kΩ
Current output: External load resistance 250~500Ω to avoid overload
- Heat Dissipation Requirements:
Leave ≥5mm heat dissipation space around the module
Cabinet temperature ≤55℃; install cooling fan if necessary
- Rezumat & Recomandări de selecție
FX5-4DA is a high-performance 4-channel analog output module in Mitsubishi FX5 series, featuring 80μs high-speed conversion, ±0.1% high accuracy, and independent channel configuration. It is suitable for industrial automation scenarios requiring precise analog signal control. Its core advantages lie in seamless integration with FX5 series CPUs and high-speed system bus communication, fully leveraging the performance of the 5th-generation PLC.
Recomandări de selecție:
- Prioritize FX5-4DA for new projects, as its performance comprehensively outperforms older series like FX3U
- Choose FX5-4DA-ADP adapter type for limited space or remote installation needs
- Recommend FX5-4DA-P high-precision version for high-precision control scenarios (de ex., process control, echipament medical)
- Consider FX5-2DA to save cost and space when channel requirements are low (≤2)
- When used with FX5U CPU, utilize built-in analog functions of the CPU plus FX5-4DA expansion for more flexible system configuration
Comprehensive Guide to Alternative Models for Mitsubishi FX5-4DA Analog Output Module
- Mitsubishi Same-series Alternative/Upgrade Models (Highly Recommended)
The following models are native products of Mitsubishi FX5 series, seamlessly compatible with FX5U/FX5UC/FX5UJ CPUs, and serve as the optimal alternatives to FX5-4DA.
| Model | Core Differences | Conversion Speed | Accuracy | Occupied I/O Points | Metoda de instalare |
| FX5-4DA-ADP | Adapter type connected via FX5-ADP-BUS cable | 2.5ms per channel | ±0.1%FS (25℃) | 0 points | DIN rail installation, up to 10m from CPU |
| FX5-2DA | 2-channel version with more compact size | 80μs per channel | ±0.1%FS (25℃) | 4 points | Direct installation to the right of CPU |
| FX5-8DA | 8-channel version for multi-channel control | 80μs per channel | ±0.1%FS (25℃) | 16 points | Direct installation to the right of CPU |
| FX5-4DA-P | High-precision version with enhanced performance | 80μs per channel | ±0.05%FS (25℃) | 8 points | Direct installation to the right of CPU |
| FX5U-4DA | Built into FX5U CPU | 80μs per channel | ±0.1%FS (25℃) | None | No additional installation required |
Key Difference Comparison Table
| Feature | FX5-4DA | FX5-4DA-ADP | FX5-2DA | FX5-8DA | FX5-4DA-P |
| Number of Channels | 4 | 4 | 2 | 8 | 4 |
| Installation Position | Right of CPU | Remote rail installation | Right of CPU | Right of CPU | Right of CPU |
| Bus Connection | Direct expansion bus | ADP bus (cable connection) | Direct expansion bus | Direct expansion bus | Direct expansion bus |
| Conversion Speed | 80s per channel | 2.5ms per channel | 80s per channel | 80s per channel | 80s per channel |
| Occupied I/O | 8 points | 0 points | 4 points | 16 points | 8 points |
| Accuracy Grade | 0.1%FS | 0.1%FS | 0.1%FS | 0.1%FS | 0.05%FS |
| Maximum Expansion Quantity | 4 unitati | 4 unitati | 4 unitati | 4 unitati | 4 unitati |
- Mitsubishi Cross-series Alternative Models (Downward Compatible/Upgrade)
Suitable for upgrading from older series or compatible with existing systems.
| Model | Serie | Compatibilitate | Parametrii de bază | Replacement Suggestion |
| FX3U-4DA | FX3U Series | Requires FX5-CNV-IF adapter to connect to FX5U | 10ms per channel, ±0.2%FS | Transitional solution for upgrading old systems to FX5U; not recommended for new projects |
| FX3U-2DA | FX3U Series | Same as above | 10ms per channel, ±0.2%FS | Upgrade for old systems with fewer channel requirements |
| FX5-4A-ADP | FX5 Series | Directly compatible with FX5U | 2.5ms per channel, ±0.1%FS | Select when 2-channel input + 2-channel output are needed simultaneously |
| FX5-8AD-4DA | FX5 Series | Directly compatible with FX5U | 80μs per channel, ±0.1%FS | Large-scale systems with mixed input/output requirements |
- Cross-brand Alternative Models (Performance Equivalent)
The following models from different brands have performance equivalent to FX5-4DA, suitable for brand switching or multi-brand system integration.
| Marca | Alternative Model | Parametrii de bază | Caracteristici |
| Siemens | SM 1232 | 4 canale, 12-rezoluție de biți, ±0.1%FS | S7-1200 series, hot-swappable, seamless integration with Siemens PLCs |
| Schneider | TM2DAI4 | 4 canale, 12-rezoluție de biți, ±0.1%FS | Modicon M221 series, Modbus support, moderate price |
| Omron | CJ1W-DA041 | 4 canale, 12-rezoluție de biți, 50μs per channel | CJ series, high-speed conversion, suitable for fast response systems |
| Rockwell | 1762-OW4 | 4 canale, 12-rezoluție de biți, ±0.1%FS | MicroLogix 1200 series, supports RSLogix programming software |
| Domestic Alternative | Tanshuo FX5-4DA-ADP | 4 canale, 80μs per channel, ±0.1%FS | Fully compatible with Mitsubishi FX5 series, more cost-effective, partially interchangeable parts |
| Delta | DVP04DA-H3 | 4 canale, 12-rezoluție de biți, ±0.2%FS | DVP series, supports Delta WPLSoft software, high cost-performance ratio |
- Alternative Selection Decision Guide
4.1 Selection by Installation Requirements
| Installation Scenario | Recommended Model | Reason |
| Direct installation to the right of CPU | FX5-4DA/FX5-2DA/FX5-8DA | No additional cables needed, fastest communication speed (system bus) |
| Remote installation (>1m from CPU) | FX5-4DA-ADP | Connected via ADP bus cable, up to 10m maximum distance |
| Limited cabinet space | FX5-4DA-ADP/FX5-2DA | Adapter type for flexible installation; 2-channel model only 25mm wide |
| Multi-module expansion (>4 unitati) | FX5-4DA-ADP | Supports more expansions without occupying CPU-side installation space |
4.2 Selection by Performance Requirements
| Performance Indicator | Recommended Model | Reason |
| High-speed dynamic response (<1ms) | FX5-4DA/FX5-2DA/FX5-8DA/FX5-4DA-P | 80s per channel, suitable for servo control and fast process regulation |
| High-precision control (<卤0.1%) | FX5-4DA-P | 0.05%FS accuracy, meeting requirements of laboratory and medical equipment |
| Multi-channel synchronous output | FX5-8DA | 8-channel simultaneous output, suitable for large-scale production line control |
| Cost-effective solution | FX5-4DA-ADP/FX3U-4DA | Lower price for adapter type; high cost-performance ratio for older series models |
4.3 Selection by Functional Requirements
| Functional Requirement | Recommended Model | Reason |
| Mixed input/output | FX5-4A-ADP/FX5-8AD-4DA | Provides both input and output channels simultaneously, simplifying system configuration |
| No I/O point occupation | FX5-4DA-ADP | Adapter type does not occupy PLC I/O points, saving resources |
| Built-in solution | FX5U-4DA | Integrated into CPU, reducing external modules and improving reliability |
| Food/Medical Industry | FX5-4DA-P | High precision + food-grade certification, meeting industry-specific requirements |
- Notes on Replacement
- Compatibility Confirmation:
Mitsubishi same-series models are directly compatible with FX5U/FX5UC/FX5UJ CPUs
Verify communication protocols and physical connections for cross-series/cross-brand models
BFM address allocation differs between FX5-4DA-ADP and FX5-4DA, requiring corresponding program adjustments
- Parameter Configuration Adjustment:
Conversion speed difference: FX5-4DA-ADP (2.5ms) is slower than FX5-4DA (80μs), requiring control algorithm adjustments
Accuracy difference: Some alternative models may have slightly different accuracy, requiring recalibration
Output load matching: Ensure the output load range of the alternative model matches the actuator
- Instalare & Cablaj:
Adapter type requires dedicated FX5-ADP-BUS cable
Analog output wiring must use shielded twisted pair with single-end grounding of the shield
Terminal definitions vary across different brand modules; refer to manuals for verification
Mitsubishi FX5-4DA has a wide range of alternative models. Priority is recommended for Mitsubishi same-series products such as FX5-4DA-ADP (remote installation), FX5-2DA (fewer channels), FX5-8DA (more channels), and FX5-4DA-P (high precision), which are seamlessly compatible with FX5U CPUs and fully leverage system performance. Among cross-brand alternatives, Siemens SM 1232, Schneider TM2DAI4, and domestic Tanshuo FX5-4DA-ADP are excellent choices, which can be flexibly selected based on specific application scenarios and budgets.