Schneider A9L16482: Acti9 iPRD1 12.5r 3P+N Surge Protective Device
A9L16482 is a Type 1+2 combinate surge protective device (SPD) din seria Acti9 de la Schneider Electric, specially designed for 3P+N three‑phase four‑wire systems. It provides comprehensive lightning and surge protection with remote signaling function, suitable for power input points of residential and small commercial buildings.
- Core Parameters Summary
| Articol | Caietul de sarcini |
| Model | A9L16482 (Acti9 iPRD1 12.5r) |
| Protection Type | Tip 1+2 SPD combinat (protects against direct and indirect lightning strikes) |
| Configurația stâlpului | 3P+N (3 phases + neutral) |
| Tensiune nominală (Uc) | 350V și (phase‑to‑phase), 255V și (neutral‑to‑earth) |
| Curent maxim de descărcare (Imax) | 50cel (8/20μs waveform) |
| Nivel de protecție a tensiunii (Sus) | 1.5kV (phase‑to‑phase), 1kV (neutral‑to‑earth) |
| Technology | MOV (Varistor cu oxid de metal) + GDT (Tub de descărcare de gaz) hybrid technology |
| Dimensiuni | 4 modules wide (72mm), height 89mm, depth 69mm |
| Greutate | 0.649 kg |
| Capacitatea cablajului | Solid wire 10–35mm², stranded wire 10–25mm² |
| Earthing System | Compatible with TN‑S and TT systems |
| Funcție de la distanță | With remote signaling contacts, connectable to monitoring systems |
- Caracteristici tehnice
- Tip integrat 1+2 Protecţie
No need for an extra Type 1 SPD; one unit provides full lightning protection
Suitable for installation in the main distribution board at the building incomer as the first level of surge protection
- Hybrid Protection Technology
GDT: Handles high‑energy direct lightning strikes, with high insulation resistance and low leakage current
MOV: Fast response to induced lightning and switching overvoltages for fine protection
Combined to achieve a wide range of surge current absorption capacity
- Funcția de monitorizare de la distanță
Built‑in status monitoring circuit, outputs operating status via remote signaling contacts
Connectable to PLC or building automation systems for real‑time SPD status monitoring
Automatically sends alarm signals in case of failure for timely maintenance and replacement
- Safety Design
Overcurrent protection to prevent overheating in case of SPD failure
Mechanical status indicator window for clear normal/fault indication
Complies with IEC 61643‑11 and EN 61643‑11
- Applications & Installation Recommendations
Recommended Applications
Main distribution boards of residential and small commercial buildings (as first‑level protection)
Power distribution systems near the power input
Intelligent building systems requiring remote monitoring of surge protection status
Three‑phase four‑wire distribution networks with TN‑S and TT earthing systems
Note de instalare
- Install after a 3P+N circuit breaker, close to the power input
- Connecting cables should be as short and straight as possible (≤50cm recommended) to reduce inductive effects
- Use copper conductor ≥16mm² for earthing; earthing resistance shall comply with local regulations
- Remote signaling contacts can be connected to DC 24V or AC 230V monitoring circuits
- Cooperate with downstream SPDs (Tip 2/3) to form a multi‑level protection system
- Selecţie & Replacement Information
Selection Criteria
System voltage: 350V AC suitable for 400V systems (phase‑to‑phase voltage)
Expected surge current: 50kA suitable for most building power incomers
Earthing system: confirm TN‑S or TT
Monitoring requirement: whether remote status monitoring is needed
Replacement Models
| Model | Main Difference | Application |
| A9L16481 | Without remote signaling | Basic protection without monitoring |
| A9L16483 | Higher rated current | Higher‑power distribution systems |
| A9L16484 | Different protection level | Applications with special accuracy requirements |
- Întreţinere & Warranty
Warranty period: 18 luni
Regularly check the status indicator (green = normal, red = fault)
Inspection and recording are recommended after the SPD operates (even if not damaged)
Replace immediately in case of failure to avoid loss of protection
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare