Product Overview & Model Explanation

ACS 310-01E-02A4-2 is a general-purpose inverter from the ABB ACS310 series with single-phase 230 V input and three-phase output. It is mainly designed for variable-torque applications such as fans and pumps, with IP20 protection and C3 EMC filter compatibility.

Model Code Breakdown (ABB ACS310 Naming Convention)

КодЗначениеОписание
ACS 310Basic seriesACS310 = general-purpose inverter, optimized for fan & pump variable-torque loads
01ЭРамка & enclosure01 = Frame R1; E = IP20, no built-in filter (external filter required)
02A4Rated output & Напряжение02A = rated output current 2.4 А (0.37 кВт); 4 = voltage class (200–240 V)
2Input phase2 = single-phase input (200–240 V), three-phase 200–240 V output
  1. Core Technical Specifications

2.1 Electrical Data

ЭлементСпецификация
Input powerSingle-phase 200–240 V AC, 50/60 Гц, ±10% tolerance
OutputThree-phase 0–240 V AC, 0–500 Hz, 0.37 кВт / 2.4 А, 150% overload for 60 с
Control modeV/f control (flux vector optional), built-in PID and PFC (pump/fan control)
Digital I/O2 цифровые входы, 1 relay output (250 V AC/2 A, 30 V DC/2 A)
Analog I/O1 analog input (0–10 V or 4–20 mA), 1 analog output (0–20 mA)
CommunicationBuilt-in Modbus EIA-485, Modbus RTU supported
EMCCategory C3 (industrial environment), external filter required

2.2 Механические характеристики

ЭлементСпецификация
РамкаR1 (132 × 175 × 155 мм, W × H × D)
МонтажWall or cabinet mounting, вертикальная установка; ≥100 mm clearance top & bottom
ЗащитаIP20
ТемператураOperating: -10 °С до +40 °С (derate above 40 °С); Storage: -40 °С до +70 °С
WeightПриблизительно. 1.5 кг
CoolingNatural convection (no fan)
  1. Key Functions & Applications

3.1 Fan & Pump Special Functions

Built-in multi-pump control (up to 4 насосы), alternation and automatic backup

Pipe cleaning and priming functions for system commissioning and maintenance

Sleep / wake-up function for significant energy saving

Anti-blockage and dry-run protection for pumps

Motor noise smoothing to reduce noise

3.2 Типичные применения

ПриложениеSuitable EquipmentKey Benefits
HVAC systemsCentrifugal fans, насосы, cooling tower fans30–50% energy saving, stable, low noise
Water treatmentBooster pumps, submersible pumps, sewage pumpsDry-run protection, multi-pump control
Industrial circuitsCooling pumps, lubrication pumpsLonger service life, lower maintenance
Small machineryКонвейеры, mixers, маленькие компрессорыEasy to use, экономически эффективный
  1. Series Models & Alternatives

4.1 ACS310 Series (Frame R1, 200–240 V single-phase)

МодельRated PowerНоминальный токMain DifferenceПриложение
ACS310-01E-02А4-20.37 кВт2.4 АBasic modelМаленькие вентиляторы, micro pumps
ACS310-01E-04A7-20.75 кВт4.7 АHigher powerSmall/medium fans & насосы
ACS310-01E-07A5-21.5 кВт7.5 АHigher powerMedium fans & насосы
ACS310-01E-09A8-22.2 кВт9.8 АHigher powerБольшие вентиляторы & насосы

4.2 Recommended Alternatives

AlternativeMain DifferenceПриложение
ACS310-03E-02A4-4Three-phase 380–480 V input, 0.37 кВтIndustrial three-phase systems
ACS355-01E-02А4-2Full-featured, built-in EMC filterHigher EMC & functional requirements
ACS580-01-03A3-4Vector control, 180% overloadHigh dynamic & прецизионный контроль
  1. Аксессуары & Options
AccessoryКод типаОписание
Control panelCDP312RBasic control and parameter setting
Advanced panelCDP312R-ETHWith Ethernet, remote monitoring
EMC filter3AFE68300909C3 EMC filter for industrial environment
Brake unitACS-BU-01For frequent start/stop and braking
I/O extension3AXD500000387624 DI + 2 DO expansion
Comm module3AXD50000038763Profibus-DP interface
  1. Установка & Поиск неисправностей

6.1 Installation Notes

  1. Electrical installation

Input must be protected by a circuit breaker and fuse matching 2.4 А

Output cable: shielded, max. 50 m to prevent motor overvoltage

Separate control wiring from power wiring by ≥100 mm

  1. Mechanical installation

Mount vertically with sufficient ventilation

Derate 1% per °C above 40 °С

Avoid high vibration, dust, moisture, corrosive gas

6.2 Fault Codes

КодОписаниеPossible CauseSolution
F001Перегрузка по токуShort circuit, motor overload, wrong settingsCheck wiring, reduce load, reset parameters
F002OvervoltageHigh supply voltage, fast decelerationCheck supply, adjust deceleration time
F003Пониженное напряжениеLow voltage, потеря фазыCheck input power
F004OvertemperaturePoor ventilation, blocked heatsinkImprove cooling, clean heatsink
F005Motor overloadExcess load, stallReduce load, check motor
F006Earth faultOutput grounded, motor insulation faultCheck cable and motor
  1. Выбор & Application Advice
  2. By load type

Fan/pump variable-torque loads: ACS310 series recommended

Constant-torque loads (conveyors, mixers): ACS355 or ACS580

  1. By power

≤ 0.37 кВт: ACS310-01E-02А4-2

0.37–2.2 kW: ACS310-01E series

> 2.2 кВт: ACS310-03E three-phase series

  1. Energy-saving analysis

Fans and pumps can save 30–50% energy with VFD control

Use ABB DriveSize for accurate selection and energy calculation

As an entry-level model of the ABB ACS310 series, the ACS 310-01E-02A4-2 features compact design, easy operation, and fan/pump‑optimized functions, making it an ideal choice for small industrial and commercial applications. For advanced control or higher performance, upgrade to ACS355 or ACS580 series.