Chint CJ19-3211 is a dedicated capacitor switching contactor with built-in current-limiting resistors, 3-pole main contacts (32А), and 1NO+1NC auxiliary contacts, designed specifically for low-voltage reactive power compensation systems. Below is a comprehensive cross-reference table with equivalent models from major domestic and international brands:

Equivalent Models Comparison Table

БрендМодельRatingВспомогательные контактыKey FeaturesСовместимость
ЧинтCJ19-321132А, AC-6b, 690В1НО+1НЗBuilt-in current-limiting resistors, direct-acting double-breakpoint structureOriginal model, capacitor switching only
ВкусныйCDC19S-32/1132А, AC-6b, 690В1НО+1НЗSame CJ19 series design, improved contact materialПрямая замена, identical mounting and wiring
CDC9-32/11
TengenTGCC1-32/1132А, AC-6b, 690В1НО+1НЗEnhanced arc suppression, wider operating temperature range (-35°C~+70°C)Drop-in replacement, compatible with all CJ19 applications
PeopleR19-32/1132А, AC-6b, 690В1НО+1НЗIndustry-standard CJ19 design, cost-effective alternativeSame dimensions and electrical characteristics
АББUA30-30-1030А (equivalent to 32A), AC-6b, 690В1НЕТABB capacitor switching series, built-in surge suppressionSlight current difference (30A vs 32A), compatible for most 20kvar capacitor applicationsABB Group
UA30-30-111НО+1НЗ
Шнайдер ЭлектрикLC1D32K*32А, AC-6b, 690В1НО+1НЗTeSys D Green series, energy-efficient coilRequires separate current-limiting resistor if not K series
(K series for capacitor)
Сименс3RT2027-1AN2032А, AC-6b, 690В1НО+1НЗSIRIUS series, can be used with external current-limiting moduleStandard 3RT series requires additional components for capacitor switching
(with surge suppressor)
LovatoB32C1032А, AC-6b, 690В1НО+1НЗDedicated capacitor contactor, built-in pre-charging contactsDirect European alternative, compatible mounting holes

Key Technical Equivalence Notes

  1. Domestic Brand Replacements (Direct Drop-in)

Delixi CDC19S-32/11: Fully compatible with CJ19-3211, same mounting dimensions, terminal layout, and electrical specifications

Tengen TGCC1-32/11: Enhanced version with better thermal performance, designed to replace CJ19 series directly

People R19-32/11: Cost-effective alternative with identical functionality

  1. International Brand Considerations

ABB UA30-30-11: Preferred choice with 1NO+1NC auxiliary contacts, rated at 30A (close enough to 32A for most applications)

Schneider LC1D32KUE: Specifically designed for capacitor switching with built-in current-limiting resistors, ensure to select theK” ряд

Siemens 3RT2027: Requires external surge protection module for proper capacitor switching, as standard models lack built-in current-limiting resistors

  1. Critical Compatibility Factors
FactorRequirementWhy It Matters
Utilization CategoryAC-6b (capacitor switching)Standard AC-3 contactors will fail prematurely with capacitor inrush currents
Текущий рейтинг32А (or 30A for ABB)Must match capacitor bank current (typically 20kvar at 400V)
Вспомогательные контакты1НО+1НЗEssential for interlocking and status feedback in compensation systems
Mounting TypeScrew-fixed (not DIN rail for CJ19)Ensure panel cutouts match (standard 4-hole mounting)
Напряжение катушкиAC220V/380V (matching control circuit)Incorrect voltage will damage the coil or prevent operation

Application Recommendations

  1. For Reactive Power Compensation Systems:

Prefer domestic brands (Вкусный, Tengen, People) for direct compatibility and cost-effectiveness

For European systems, ABB UA30-30-11 is the most equivalent international model

  1. When Replacing Existing CJ19-3211:

Verify auxiliary contact configuration (1НО+1НЗ) before purchasing

Ensure new contactor has built-in current-limiting resistors (critical for capacitor protection)

Match coil voltage (AC220V/380V) with existing control circuit

  1. Installation Notes:

All equivalent models use the same screw-fixed mounting (M4/M5 bolts, torque 2.5~3.5N·m)

Main circuit wiring requires 4mm² copper cables, control circuit uses 1.5mm² cables

Maintain proper spacing (10cm) for heat dissipation, separate main and control circuits to avoid interference