Chint CJ19-3211 is a dedicated capacitor switching contactor with built-in current-limiting resistors, 3-pole main contacts (32А), and 1NO+1NC auxiliary contacts, designed specifically for low-voltage reactive power compensation systems. Below is a comprehensive cross-reference table with equivalent models from major domestic and international brands:
Equivalent Models Comparison Table
| Бренд | Модель | Rating | Вспомогательные контакты | Key Features | Совместимость |
| Чинт | CJ19-3211 | 32А, AC-6b, 690В | 1НО+1НЗ | Built-in current-limiting resistors, direct-acting double-breakpoint structure | Original model, capacitor switching only |
| Вкусный | CDC19S-32/11 | 32А, AC-6b, 690В | 1НО+1НЗ | Same CJ19 series design, improved contact material | Прямая замена, identical mounting and wiring |
| CDC9-32/11 | |||||
| Tengen | TGCC1-32/11 | 32А, AC-6b, 690В | 1НО+1НЗ | Enhanced arc suppression, wider operating temperature range (-35°C~+70°C) | Drop-in replacement, compatible with all CJ19 applications |
| People | R19-32/11 | 32А, AC-6b, 690В | 1НО+1НЗ | Industry-standard CJ19 design, cost-effective alternative | Same dimensions and electrical characteristics |
| АББ | UA30-30-10 | 30А (equivalent to 32A), AC-6b, 690В | 1НЕТ | ABB capacitor switching series, built-in surge suppression | Slight current difference (30A vs 32A), compatible for most 20kvar capacitor applicationsABB Group |
| UA30-30-11 | 1НО+1НЗ | ||||
| Шнайдер Электрик | LC1D32K* | 32А, AC-6b, 690В | 1НО+1НЗ | TeSys D Green series, energy-efficient coil | Requires separate current-limiting resistor if not K series |
| (K series for capacitor) | |||||
| Сименс | 3RT2027-1AN20 | 32А, AC-6b, 690В | 1НО+1НЗ | SIRIUS series, can be used with external current-limiting module | Standard 3RT series requires additional components for capacitor switching |
| (with surge suppressor) | |||||
| Lovato | B32C10 | 32А, AC-6b, 690В | 1НО+1НЗ | Dedicated capacitor contactor, built-in pre-charging contacts | Direct European alternative, compatible mounting holes |
Key Technical Equivalence Notes
- Domestic Brand Replacements (Direct Drop-in)
Delixi CDC19S-32/11: Fully compatible with CJ19-3211, same mounting dimensions, terminal layout, and electrical specifications
Tengen TGCC1-32/11: Enhanced version with better thermal performance, designed to replace CJ19 series directly
People R19-32/11: Cost-effective alternative with identical functionality
- International Brand Considerations
ABB UA30-30-11: Preferred choice with 1NO+1NC auxiliary contacts, rated at 30A (close enough to 32A for most applications)
Schneider LC1D32KUE: Specifically designed for capacitor switching with built-in current-limiting resistors, ensure to select the “K” ряд
Siemens 3RT2027: Requires external surge protection module for proper capacitor switching, as standard models lack built-in current-limiting resistors
- Critical Compatibility Factors
| Factor | Requirement | Why It Matters |
| Utilization Category | AC-6b (capacitor switching) | Standard AC-3 contactors will fail prematurely with capacitor inrush currents |
| Текущий рейтинг | 32А (or 30A for ABB) | Must match capacitor bank current (typically 20kvar at 400V) |
| Вспомогательные контакты | 1НО+1НЗ | Essential for interlocking and status feedback in compensation systems |
| Mounting Type | Screw-fixed (not DIN rail for CJ19) | Ensure panel cutouts match (standard 4-hole mounting) |
| Напряжение катушки | AC220V/380V (matching control circuit) | Incorrect voltage will damage the coil or prevent operation |
Application Recommendations
- For Reactive Power Compensation Systems:
Prefer domestic brands (Вкусный, Tengen, People) for direct compatibility and cost-effectiveness
For European systems, ABB UA30-30-11 is the most equivalent international model
- When Replacing Existing CJ19-3211:
Verify auxiliary contact configuration (1НО+1НЗ) before purchasing
Ensure new contactor has built-in current-limiting resistors (critical for capacitor protection)
Match coil voltage (AC220V/380V) with existing control circuit
- Installation Notes:
All equivalent models use the same screw-fixed mounting (M4/M5 bolts, torque 2.5~3.5N·m)
Main circuit wiring requires 4mm² copper cables, control circuit uses 1.5mm² cables
Maintain proper spacing (10cm) for heat dissipation, separate main and control circuits to avoid interference