Model A9L40600 SchneiderModel Analysis and Technical Parameters A9L40600 is the complete order number of a low-voltage surge protection product (Surge Arrester) under Schneider Electric‘s Acti9 Series. It belongs to the iPRD40 modular surge arrester series and is mainly used for Type 2 surge protection in power distribution systems. Model Segment Analysis Code Segment ...

  • Подробная информация о продукте

Model A9L40600 SchneiderModel Analysis and Technical Parameters

A9L40600 is the complete order number of a low-voltage surge protection product (Surge Arrester) under Schneider Electric‘s Acti9 Series. It belongs to the iPRD40 modular surge arrester series and is mainly used for Type 2 surge protection in power distribution systems.

  1. Model Segment Analysis
Code SegmentDescriptionCorresponding Product Attribute
A9Schneider Acti9 Series IdentifierA standardized low-voltage component series for terminal power distribution, including circuit breakers, surge arresters, и т. д..
L40Product Type Sub-codeRepresents the iPRD40 series modular surge arrester. “л” generally indicates surge protection products, и “40” corresponds to the 40kA maximum discharge current rating.
600Structural Feature and Configuration CodeCorresponding to 3P+N (three-phase + neutral) pole configuration, 350V rated voltage, and equipped with a pluggable trip module
  1. Summary of Core Product Attributes
ЭлементSpecification Parameter
Brand and SeriesSchneider Acti9 iPRD40 Series
Тип продуктаТип 2 modular surge arrester (with pluggable trip unit)
Pole Configuration3P+N (three-phase + neutral)
Номинальное напряжение (Uc)350В и (suitable for domestic 400V three-phase systems)
Maximum Discharge Current (Imax)40тот (8/20μs waveform)
Класс защитыТип 2 (secondary surge protection for power distribution systems)
Technical PrincipleCombined technology of MOV (Metal Oxide Varistor) + GDT (Gas Discharge Tube)
Applicable Earthing SystemTN-S, TT systems (not applicable to TN-C, IT systems)
  1. Detailed Technical Parameter Table
Parameter CategorySpecific ValueПримечания
Electrical Parameters
Номинальное рабочее напряжение350В и50/60Гц
Maximum Discharge Current40тот (8/20μs)Core indicator of surge protection
Nominal Discharge Current20тот (8/20μs)
Voltage Protection Level (Up)≤ 1.5kVMeasured at In=10kA
Response Time≤ 25nsMOV+GDT combined technology ensures fast response
Mechanical and Installation Parameters
Module Width4 модули (72мм)Suitable for 35mm DIN standard rail
Размеры85мм (ЧАС) × 72mm (Вт) × 69mm (Д)
TerminalSuitable for 2.5~35mm² copper conductorsRecommended torque: 8~10N·m
Класс защитыIP20Suitable for installation inside power distribution cabinets
Environmental and Service Life Parameters
Рабочая температура-25°C ~ +60°C
Storage Temperature-40°C ~ +85°C
Механический срок службы 10,000 раз (plug-in operation)
Electrical Service LifeСоответствует МЭК 61643-11 стандартныйThe pluggable module can be replaced when surge protection components age
Certification and Standards
Compliant StandardsМЭК 61643-11, GB 18802.1Certified with CE and CCC
  1. Core Functions and Working Principle
  2. Surge Suppression Mechanism: Adopts MOV+GDT hybrid technology. MOV is responsible for fast response (≤25ns) to suppress most surges, while GDT provides higher surge withstand capacity and lower leakage current.
  3. Fault Indication Function: The pluggable module is equipped with a visual status indicator (green = normal, red = fault) for quick identification of protection status.
  4. Thermal Trip Protection: Built-in thermal trip device automatically trips when surge energy is excessive or components age, preventing overheating damage to the arrester.
  5. Replaceable Design: Only the pluggable trip module needs to be replaced after a fault, eliminating the need for overall replacement and reducing maintenance costs.
  6. Типичные сценарии применения
Application FieldSpecific Application ScenarioProtection Target
Коммерческие зданияMain/distribution power cabinets in office buildings, shopping malls, отелиProtect critical loads such as air conditioners, elevators, and lighting systems
Industrial PlantsProduction line control circuits, PLC systems, front-end of frequency convertersPrevent damage to precision electronic equipment caused by lightning strikes or grid fluctuations
Data CentersUPS input/output terminals, front-end of server cabinet PDUsEnsure continuous and stable operation of IT equipment and avoid data loss
InfrastructureCritical power distribution circuits in hospitals and transportation hubsProtect life-safety related equipment and control systems
Photovoltaic SystemsAC side output terminals of invertersSuppress surges generated by photovoltaic systems and grid feedback surges
  1. Installation and Operation Precautions
  2. Installation Location:

As Type 2 protection, it should be installed in the main or distribution power cabinet, after the main circuit breaker.

Recommended to be installed close to the protected equipment, with the line length not exceeding 10 метры.

  1. Требования к проводке:

Phase lines (Л1/Л2/Л3) and neutral line (Н) must be wired correctly according to the markings.

The protective earthing (ЧП) wire should be as short and thick as possible. It is recommended to use ≥16mm² copper conductors with a length not exceeding 50cm.

All terminals must be tightened to the recommended torque (8~10N·m) to prevent overheating due to poor contact.

  1. Matching Requirements:

A 16A~32A miniature circuit breaker or fuse must be installed upstream as overcurrent protection to prevent short circuits caused by surge arrester faults.

Not applicable to IT and TN-C earthing systems, only suitable for TN-S and TT systems.

  1. Maintenance Points:

Regularly check the status indicator (green = normal, red = fault).

Replace the pluggable trip module in a timely manner after a fault; do not perform plug-in operations with power on.

It is recommended to conduct a surge protection performance test every 2 годы.

  1. Reference of Related Models in the Same Series
МодельНомер полюсаMaximum Discharge CurrentНоминальное напряжениеApplication Scenario
A9L402001P+N40тот350V.Тип 2 surge protection for single-phase power distribution systems
A9L404002P+N40тот350V.Two-phase power distribution systems (например, lighting systems)
A9L406003P+N40тот350V.Three-phase power distribution systems (mainstream model)
A9L156003P+N15тот350V.Places with low surge risk

 