This is an ABB SACE Tmax T6N 800A MCCB equipped with a TMA800/4000-8000 adjustable thermomagnetic release, 3-столб, fixed mount, front connection, with N-type breaking capacity (36kA@400V). It is used as a main switch in industrial main circuits, heavy-duty motor protection, and power distribution systems.
- Full Model Code Breakdown
| Section | Marking | Описание | Technical Note |
| 1 | T6 | Frame size | Tmax T series MCCB, max frame current 800A, компактный дизайн (depth 103.5mm) |
| 2 | Н | Класс отключающей способности | N‑type standard breaking capacity: 36kA@400V/415V, 25kA@500V, 20kA@600V |
| 3 | 800 | Frame rated current | Maximum rated current of the автоматический выключатель frame: 800А |
| 4 | TM/TMA | Тип выпуска | Thermomagnetic Adjustable release – both overload (thermal) and short‑circuit (magnetic) protection are adjustable |
| 5 | 800 | Номинальный ток (В) | Continuous operating current: 800А |
| 6 | 40000‑8000 | Instantaneous trip range | I3 = 4000–8000A, adjustable short‑circuit instantaneous protection |
| 7 | Ф | Mounting type | Зафиксированный (non‑withdrawable) |
| 8 | Ф | Connection type | Front connection |
| 9 | 3П | поляки | 3‑pole circuit breaker for three‑phase systems |
- Ключевые технические параметры
| Элемент | Ценить | Примечания |
| Product type | SACE Tmax T6N 800A MCCB | Factory code: 1SDA060214R1 |
| Номинальное напряжение изоляции (Уи) | 1000В | Maximum continuous voltage for insulation parts |
| Rated impulse withstand voltage (Умп) | 8кВ | Capability to withstand transient high voltage |
| Rated operating voltage (Уэ) | 690В и | Max operating voltage |
| Частота | 50/60Гц | For standard mains systems |
| Trip characteristic | Adjustable thermomagnetic | Перегрузка (inverse time), short‑circuit (instantaneous) |
| Ultimate breaking capacity (Ику) | 36kA@400V | N class |
| 25kA@500V | ||
| 20kA@600V | ||
| Service breaking capacity (Икс) | 100% Ику | Reusable after tripping |
| Номинальный ток (В) | 800А | Maximum continuous current |
| Instantaneous trip range | 4000–8000A | I3 = 5–10In, регулируемый |
| Размеры (мм) | В×Ш×Г: 268×210×103.5 | Uniform depth for panel layout |
| Weight | приблизительно. 9кг | Стандартный |
| Степень защиты | IP30 | МЭК 60529 |
- Типичные применения
- Промышленное распределение электроэнергии
Main or sub-switch for 3-phase 800A circuits in factories, workshops, data centers.
- Large motor protection
Three-phase induction motors up to approx. 400кВт (380В)
Critical motor circuits requiring adjustable overload and short-circuit protection
- Building electrical
Main switchboards in commercial and high-rise buildings
Power circuits for HVAC, насосы, and large equipment
- Возобновляемая энергия
Main switches in combiner boxes for PV and wind power systems
DC-side protection for energy storage (DC version required)
- Other heavy industries
Mining, ports, railways, and applications requiring high reliability and adjustable protection.
- Replacement Models
4.1 ABB Upgrades / Replacements
| Запасная модель | Основное отличие | Приложение |
| T6S800 TMA800/4000‑8000 FF 3P | Breaking capacity upgraded to S class (50kA@400V) | Systems with higher short‑circuit current near transformers |
| T6L800 TMA800/4000‑8000 FF 3P | Breaking capacity upgraded to L class (70kA@400V) | Heavy industrial grids and large plants |
| T6N800 PR221DS‑LSI 800 FF 3P | Electronic LSI release (Long / Short / Мгновенный) | Complex systems requiring precise grading and selectivity |
| XT6N800 TMA800/4000‑8000 FF 3P | New‑generation Tmax XT, same dimensions, improved performance | System upgrades and new installations |
4.2 Cross-Brand Equivalents
| Бренд | Модель | Ключевые параметры соответствия | Примечания |
| Шнайдер | NSX630N TM800D 3P | In=800A, Icu=36kA, thermomagnetic | NSX max frame 630A; 800A is special rating |
| Сименс | 3VA6880‑6EL32‑0AA0 | In=800A, Icu=36kA, 3П, thermomagnetic | 3VA series, аналогичная производительность |
| Mitsubishi | NF800‑CW 3P | In=800A, Icu=35kA, thermomagnetic | Japanese standard, suitable for Japanese equipment |
| Delta | PM800H‑3P | In=800A, Icu=36kA, thermomagnetic | Cost‑effective industrial MCCB |
- Выбор & Application Notes
- Breaking capacity matching
Ensure short-circuit current ≤ 36kA@400V; otherwise use T6S/T6L.
Icu is only 20kA at 600V – use with caution.
- Release settings
Перегрузка (thermal): set to 1.0–1.1 × load rated current
Мгновенный (magnetic): set to 5–10 × In to avoid nuisance tripping while maintaining selectivity.
- Монтаж & wiring
Зафиксированный, front connection; allow depth ≥ 103.5mm.
Use copper busbar/cable rated for 800A; ≥240mm² copper recommended.
- Maintenance & replacement
Regularly verify release settings.
Inspect contacts after short-circuit tripping; replace if needed.
For upgrades, prefer T6S/T6L or XT6N to keep dimensions compatible.
- Заключение
ABB T6N800-TM800-40000-8000-F-F-3P is a high-performance 800A MCCB with compact size, adjustable thermomagnetic protection, and standard breaking capacity. It is ideal for high-current three-phase circuits in industrial automation. Selection should consider system short-circuit current, требования защиты, and installation space. For better accuracy and selectivity, use higher-breaking versions or electronic releases.
Schneider Replacement for ABB T6N800-TM800-40000-8000-F-F-3P
Key Summary: The ABB T6N800 is an MCCB; Schneider’s NSX series is the best match. If you require an MT air circuit breaker (АКВ), suitable models are also available. Full solutions and technical comparisons below.
- Product Type Comparison
| Тип | АББ | Schneider Corresponding Series | Основное отличие |
| MCCB | T6N800 | NSX Series | Компактный, 36–150kA, for sub‑circuits |
| АКВ | No equivalent in Tmax T6 | MT Series | Larger, 50–200kA, for main incomers |
- Schneider MT ACB Replacement
2.1 Recmmended Model: MT08N1 3P F MIC2.0+LR 800A
Model explanation:
MT08: Frame size 800A
N1: Breaking capacity 50kA@400V (higher than T6N 36kA)
3П: 3-столб
Ф: Fixed mount
MIC2.0+LR: Thermomagnetic protection (Long + Мгновенный)
800А: Номинальный ток
Parameter matching:
| Элемент | ABB T6N800 | Schneider MT08N1 | Match Level |
| Номинальный ток (В) | 800А | 800А | Perfect |
| Монтаж | Зафиксированный | Зафиксированный | Perfect |
| поляки | 3П | 3П | Perfect |
| Отключающая способность (Ику) | 36kA@400V | 50kA@400V | Higher |
| Тип выпуска | Thermomagnetic (ТМА) | Thermomagnetic (LR) | Functional match |
| Instantaneous range | 4000–8000A (5–10В) | 5–10In adjustable | Perfect |
Order No: 63006 (MT08N1 3P F MIC2.0 800A)
2.2 Альтернативы (Higher Breaking)
MT08N2 3P F MIC2.0+LR 800A: 50kA@400V, wider current range
MT08H1 3P F MIC2.0+LR 800A: 65kA@400V for heavy short-circuit systems
- Better Schneider NSX MCCB Replacement
3.1 Рекомендуемая модель: NSX800F TMD 800 3P3D F
Model explanation:
NSX800: Frame 800A
Ф: 36kA@400V (identical to T6N)
ДВНЧС: Thermomagnetic release (distribution type)
800: Rated current 800A
3П3Д: 3-столб
Ф: Зафиксированный, front connection
Parameter matching:
| Элемент | ABB T6N800 | Schneider NSX800F | Match Level |
| Тип | MCCB | MCCB | Perfect |
| В | 800А | 800А | Perfect |
| Ику | 36kA@400V | 36kA@400V | Perfect |
| Монтаж | Зафиксированный | Зафиксированный | Perfect |
| Связь | Front | Front | Perfect |
| поляки | 3П | 3П | Perfect |
| Выпускать | ТМА | ДВНЧС | Perfect |
| Мгновенный | 5–10В | 5–10В | Perfect |
Order No: C80F3TM800
3.2 Higher-Breaking Alternatives
NSX800N TMD 800 3P3D F: 50kA@400V, order No C80N3TM800
NSX800H TMD 800 3P3D F: 70kA@400V for heavy industry
- Replacement Selection Notes
- Product type choice
For direct replacement of an MCCB, choose NSX for identical form factor.
For upgrading to a main incomer, use MT ACB (note larger dimensions).
- Release settings
Long-delay (И): 1.0–1.1 × rated current
Мгновенный (Ii): 5–10 × In (4000–8000A) to match original ABB behavior.
- Отключающая способность
MT08N1, NSX800N/H exceed 36kA for improved safety.
NSX800F is sufficient if Isc ≤ 36kA.
- Mounting space
MT ACB depth ~300mm (much larger than T6N 103.5mm)
NSX matches T6 dimensions for easy retrofit.
- Краткое содержание
Top Recommendation: Schneider NSX800F TMD 800 3P3D F (order No C80F3TM800).
Perfectly matches the ABB T6N800 in type, current, mounting, отключающая способность, and characteristics, with near-identical dimensions for easy replacement.
Alternative: If ACB is required, use MT08N1 3P F MIC2.0+LR 800A (order No 63006), which provides higher breaking capacity but requires more space.
Let me know if you want a simplified 1-page English datasheet version for customers or bidding.
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи


















NH42-63-318x560.png)



