ABB XT2N160 TMA 160 3p F F
Заказ №.: 1SDA061805R1 (1SDA067020R1)
Полная модель: XT2N 160 ТМА 160-1600 3p F F
Ряд: ABB Tmax XT Series Molded Case Circuit Breaker
- Core Parameters Summary
| Категория параметра | Подробные характеристики | Примечания |
| Основная информация | • Frame size: XT2 | For low-voltage power distribution in industry and buildings |
| • Frame current: 160А | ||
| • Rated current In: 160А | ||
| • Poles: 3П | ||
| • Breaking capacity: Тип Н (36kA @ 415V AC) | ||
| • Rated operating voltage Ue: 690В и, 500В Вашингтоне | ||
| • Standards: МЭК 60947-2, ГБ 14048.2 | ||
| Trip System | • Trip type: TMA thermal-magnetic (overload + защита от короткого замыкания) | Not suitable for earth fault protection; additional accessories required |
| • Overload protection (И): Adjustable, 160А | ||
| • Short-circuit protection (I3): Adjustable, 800~1600A | ||
| • Instantaneous short-circuit protection: Fixed at 10In (1600А) | ||
| • Protection curve: Соответствует МЭК 60947-2 | ||
| Монтаж & Связь | • Mounting type: Зафиксированный (Ф) | Standard DIN rail or screw mounting |
| • Connection: Front connection (Ф) | ||
| • Operation: Direct handle operation | ||
| • Dimensions: 90mm×130mm×82.5mm | ||
| • Weight: приблизительно. 1.574кг | ||
| • Protection degree: IP20 | ||
| Электрические характеристики | • Rated insulation voltage Ui: 800В | Suitable for AC-1, AC-2, АС-3, AC-4 duties |
| • Rated impulse withstand voltage Uimp: 8кВ | ||
| • Rated short-time withstand current Icw: 16kA/1s | ||
| • Rated frequency: 50/60Гц | ||
| • Wiring capacity: max. 95mm² copper, max. 70mm² aluminum |
- Detailed Protection Characteristics
2.1 Защита от перегрузки (Thermal)
Characteristic: Inverse time curve per IEC 60947-2
Adjustable range: 160А (fixed)
Trip time:
1.05В: No trip for long duration
1.3В: Trip within ≤1 hour
6В: Trip within 2~10 seconds
2.2 Защита от короткого замыкания (Magnetic)
Instantaneous trip: 800~1600A adjustable (I3)
Short-time delay: Not available (TMA has no short-time delay; TMD or electronic trip required)
Instantaneous short-circuit protection: Fixed at 10In (1600А), non-adjustable
- Mounting Dimensions & Physical Characteristics
| Dimension | Ценить | Unit |
| Ширина | 90 | мм |
| Высота | 130 | мм |
| Глубина | 82.5 | мм |
| Mounting hole spacing | 75 | мм |
| Terminal spacing | Стандартный | мм |
| Weight | 1.574 | кг |
| Package size | 145*130*208 | мм |
| Package weight | 1.2 | кг |
Mounting Requirements:
35mm standard DIN rail (В 60715) рекомендуется
Температура окружающей среды: -25°C ~ +70°C
Высота: ≤2000m (derating required above)
Защита: IP20 (front); must be installed in enclosure with IP30 or higher
- Замена & Extended Models in the Same Series
4.1 Direct Replacement Models
| Модель | Difference | Приложение |
| XT2N160 TMA 160 3P F F | Identical specifications | Прямая замена, no modification needed |
| XT2N160 TMA 160 3P P F | Plug-in mounting (П) | Frequent replacement or maintenance |
| XT2N160 TMA 160 3P F W | Rear connection (Вт) | Limited cabinet space |
4.2 Function-Extended Models
| Модель | Functional Upgrade | Order No. |
| XT2N160 Ekip LSI 160 3P F F | Electronic trip, LSI protection | 1SDA067071R1 |
| XT2N160 Ekip LSIG 160 3P F F | Electronic trip, LSIG protection (including earth fault) | 1SDA067072R1 |
| XT2N160 TMD 160 3P F F | Thermal-magnetic with short-time delay | 1SDA067035R1 |
4.3 Pole-Extended Models
4P version: XT2N160 TMA 160 4p F F (Заказ №.: 1SDA061806R1 / 1SDA067041R1)
Neutral pole rated current: 50% или 100% of phase current optional
4.4 Cross-Brand Reference
Шнайдер: NSX160N TMD160 3P F
Сименс: 3VT8116-1AA03-0AA0
Чинт: NM1-160S/3300 160A
- Recommended Accessories
| Accessory Type | Модель | Описание |
| Вспомогательный контакт | XT2-AS11 | 1НЕТ + 1Северная Каролина, for status indication |
| Alarm contact | XT2-AL11 | 1НЕТ + 1Северная Каролина, for fault alarm |
| Шунтовая поездка | XT2-SHT | Remote tripping, AC/DC 220V |
| Undervoltage release | XT2-UVT | Защита от пониженного напряжения, 220 В переменного тока |
| Rotary handle | XT2-CR | Door-mounted operation, improved safety |
| Extended rotary handle | XT2-CRE | For deep panels |
| Terminal cover | XT2-TC | Protect terminals, prevent electric shock |
| Label holder | XT2-LB | For marking breaker parameters |
- Applications & Примечания к выбору
6.1 Типичные применения
Industrial plants: Motor protection (≤160A), distribution feeder protection
Коммерческие здания: HVAC, освещение, pump control
Infrastructure: Small substations, data centers, PV systems
Others: OEM equipment, agricultural machinery, marine systems
6.2 Selection Guide
| Requirement | Рекомендуется | Not Recommended |
| Motor protection | ✓ (with proper setting) | Small motors (<10А); use MCB instead |
| Distribution protection | ✓ (sub-circuits) | Main incomer (use XT3/XT4 series) |
| Earth fault protection | ✗ (needs accessories) | ✓ (choose Ekip LSIG) |
| Frequent operation | ✗ (MCCB not suitable) | ✓ (контактор + реле) |
| Функция изоляции | ✓ (МЭК 60947-3) | – |
6.3 Selection Cautions
- Ensure rated current In matches load
- Breaking capacity must meet system short-circuit current (Н: 36kA @ 415V)
- Монтаж (fixed/plug-in) and connection (front/rear) must match panel design
- Auxiliaries, shunt/undervoltage trips ordered separately
- Not for DC short-circuit protection (use DC-rated model)
- Поиск неисправностей & Maintenance
7.1 Распространенные неисправности & Решения
| Symptom | Возможные причины | Решения |
| Frequent tripping | 1. Перегрузка | 1. Check load |
| 2. Short circuit | 2. Locate short circuit | |
| 3. Incorrect trip setting | 3. Reset settings | |
| 4. Высокая температура окружающей среды | 4. Improve ventilation | |
| Cannot close | 1. No power to undervoltage trip | 1. Check control power |
| 2. Shunt trip not reset | 2. Reset shunt trip | |
| 3. Mechanism fault | 3. Contact ABB service | |
| 4. Line fault | 4. Clear fault | |
| No output after closing | 1. Main contacts damaged | 1. Inspect/replace contacts |
| 2. Ослабленная проводка | 2. Tighten terminals | |
| 3. Trip unit fault | 3. Replace trip unit | |
| Aux contact no signal | 1. Auxiliary contact defective | 1. Replace auxiliary contact |
| 2. Неправильная проводка | 2. Check wiring | |
| 3. Improper switching | 3. Adjust contact position |
7.2 Рекомендации по техническому обслуживанию
Inspection: Every 6 months – check wiring and mechanism
Cleaning: Every 12 months – remove dust to maintain insulation
Operation test: Once per year – 3~5 manual ON/OFF cycles
Trip test: Once every 2 years – simulate overload and short circuit
Service life: Обычно 10 годы, depending on duty and environment
- Ordering & Упаковка
Standard package: 1 unit/box, including installation manual and certificate
MOQ: 1 единица
Warranty: 18 months from commissioning, или 24 months from delivery (whichever comes first)
Order code: 1SDA061805R1 (or 1SDA067020R1, varies by region)
Complete Model Guide for ABB Tmax XT2 Series (160A Frame)
Frame size: XT2 (160А)
Номинальное напряжение: 690В и, 500В Вашингтоне
поляки: 3П / 4П
Breaking classes: Н(36тот), С(50тот), ЧАС(70тот), л(100тот)
- Model Naming Convention
XT2 [Breaking Class] [Ток кадра] [Trip Type] [Текущий диапазон] [поляки] [Монтаж] [Связь]
Breaking class:
Н: 36kA @ 415V (стандартный)
С: 50kA @ 415V (enhanced)
ЧАС: 70kA @ 415V (high performance)
л: 100kA @ 415V (ultimate)
Frame current: 160 (fixed)
Trip type:
ТМА: Термомагнитный (overload + instantaneous, no short-time delay)
ДВНЧС: Термомагнитный (overload + short-time delay + instantaneous)
Ekip LSI: Electronic (overload + short-time delay + instantaneous)
Ekip LSIG: Electronic (overload + short-time delay + instantaneous + замыкание на землю)
Ekip I: Electronic (instantaneous only)
Current range: например, 160-1600 (TMA 160A)
поляки: 3П / 4П
Монтаж: Ф (Зафиксированный) / П (Plug-in)
Связь: Ф (Front) / Вт (Rear)
- XT2 Series Model List (by Breaking Class)
2.1 Standard Breaking (Н, 36тот)
| Model Prefix | Trip Type | Typical Model | Текущий диапазон | Приложение |
| XT2N160 | ТМА | XT2N160 TMA 160-1600 3P F F | 160А | General distribution, motors |
| ДВНЧС | XT2N160 TMD 100-1000 4P F W | 100А | Systems requiring short-time delay | |
| Ekip LSI | XT2N160 Ekip LSI R125 3P P F | 125А | Electronic protection, remote monitoring | |
| Ekip LSIG | XT2N160 Ekip LSIG R80 4P F F | 80А | Earth fault protection required |
Example Order No.: 1SDA061805R1 (XT2N160 TMA 160 3P F F)
2.2 Enhanced Breaking (С, 50тот)
| Model Prefix | Trip Type | Typical Model | Текущий диапазон | Приложение |
| XT2S160 | ТМА | XT2S160 TMA 63-630 3P F F | 63А | Industry, heavy-duty equipment |
| ДВНЧС | XT2S160 TMD 40-400 4P P W | 40А | Frequently started motors | |
| Ekip LSI | XT2S160 Ekip C Dip LSI R100 3P F F | 100А | Complex commercial distribution | |
| Ekip LSIG | XT2S160 Ekip LSIG R50 4P F F | 50А | Дата-центры, medical facilities |
Example Order No.: 1SDA067021R1 (XT2S160 TMA 160 3P F F)
2.3 High Performance Breaking (ЧАС, 70тот)
| Model Prefix | Trip Type | Typical Model | Текущий диапазон | Приложение |
| XT2H160 | ТМА | XT2H160 TMA 32-320 3P F F | 32А | Industrial systems with high short-circuit current |
| ДВНЧС | XT2H160 TMD 3.2-32 4P F F | 3.2А | Precision equipment, control circuits | |
| Ekip LSI | XT2H160 Ekip Dip LSI R63 3P P F | 63А | Generators, substations | |
| Ekip LSIG | XT2H160 Ekip LSIG R25 4P F F | 25А | PV, renewable energy |
Example Order No.: 1SDA067587R1 (XT2H160 TMD 3.2-32 3P F F)
2.4 Ultimate Breaking (л, 100тот)
| Model Prefix | Trip Type | Typical Model | Текущий диапазон | Приложение |
| XT2L160 | ТМА | XT2L160 TMA 100-1000 4P F F | 100А | Heavy industry with very high fault level |
| ДВНЧС | XT2L160 TMD 160-1600 3P F W | 160А | Large motor control centers | |
| Ekip LSI | XT2L160 Ekip LSI R160 3P P F | 160А | Metallurgy, chemical, hazardous areas | |
| Ekip LSIG | XT2L160 Ekip LSIG R125 4P F F | 125А | Petrochemical, mining |
Example Order No.: 1SDA067667R1 (XT2L160 TMA 100-1000 4P F F)
- Trip Unit Comparison
| Trip Type | Защита | Adjustable Parameters | Typical Load | Price Level |
| ТМА | Перегрузка + Мгновенный | И, I3 | Motors, general distribution | Economy |
| ДВНЧС | Перегрузка + Short-time + Мгновенный | И, Исд, tsd, I3 | Transformers, capacitors | Medium |
| Ekip LSI | Перегрузка + Short-time + Мгновенный | Full range, коммуникация | Critical distribution | Medium-High |
| Ekip LSIG | Перегрузка + Short-time + Мгновенный + Earth Fault | Full range, коммуникация, logging | Sensitive loads, safety | Высокий |
| Ekip I | Instantaneous only | I3 | Short-circuit intensive devices | Economy |
- Special Models & Options
4.1 4P Neutral Configurations
Стандартный: Neutral = 50% фаза (general distribution)
Heavy: Neutral = 100% фаза (non-linear loads: VFD, UPS)
Пример: XT2N160 TMA 160 4P F F (100% neutral)
4.2 Plug-in Mounting (П)
Fast replacement, подходит для критического оборудования
Пример: XT2S160 TMD 80 3P P F
4.3 Rear Connection (Вт)
Saves cabinet space, compact panels
Пример: XT2H160 Ekip LSI R63 3P F W
4.4 Совместимость аксессуаров (Full Series)
| Accessory | Модель | Описание |
| Вспомогательный контакт | XT2-AS11 | 1НО+1НЗ, status indication |
| Alarm contact | XT2-AL11 | 1НО+1НЗ, сигнализация неисправности |
| Шунтовая поездка | XT2-SHT | Remote tripping, AC/DC 220V |
| Undervoltage release | XT2-UVT | Защита от пониженного напряжения, 220 В переменного тока |
| Rotary handle | XT2-CR | Door operation, safety |
- Quick Selection Table
| Приложение | Recommended Class | Trip Type | поляки | Mount/Conn |
| General industrial | N/S | TMA/TMD | 3П | F/F |
| Motor protection | N/S | ТМА | 3П | F/F |
| Commercial lighting | Н | ТМА | 3P/4P | F/F |
| Data center | H/L | Ekip LSIG | 4П | F/W |
| PV system | H/L | Ekip LSIG | 4П | F/F |
| Frequent maintenance | Any | Any | 3P/4P | P/F |
- Замена & Upgrade Path
6.1 Same-Frame Upgrade
Отключающая способность: XT2N → XT2S → XT2H → XT2L (dimensions unchanged)
Trip unit: TMA → TMD → Ekip LSI → Ekip LSIG
Mount/connection: F/F → P/F or F/W
6.2 Cross-Frame Upgrade
XT2 (160А) → XT3 (250А) → XT4 (250A enhanced) → XT5 (630А)
Note dimension and parameter changes
All XT2 series models comply with IEC 60947-2 and GB 14048.2.
Fixed dimensions: 90mm × 130mm × 82.5mm for easy system expansion and maintenance.
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи