The following are the detailed technical parameters and application guidelines of the CHINT (CHNT) NS2-32H 17-23A AC motor starter, compiled by combining official documents and actual scenarios, covering key dimensions such as core functions, electrical performance, control characteristics, and compatibility:
- Core Functions and Positioning
The NS2-32H belongs to a motor starter, which is mainly used for overload, phase failure, and short-circuit protection of three-phase asynchronous motors and for infrequent starting control. It is suitable for scenarios such as industrial equipment, pumps, and fans. Its core features include:
Setting current range of 17-23A: It is suitable for motors with a power of approximately 3kW (needs to be adjusted according to the actual load).
Tripping characteristics: It complies with the 10A class of the IEC 60947-2 standard and is suitable for loads with high starting currents (such as fans and water pumps).
Integrated protection function: There is no need for an additional thermal relay, simplifying the design of the control cabinet.
- Electrical and Mechanical Parameters
- Electrical Performance
| Parameter | Value/Range | Explanation |
| Rated voltage | AC 230/240V, 400/415V, 440V, 500V, 690V | Supports wide voltage input and adapts to different power grid environments. |
| Rated current | 17-23A (setting range) | Can be adjusted by a knob or button to match the current on the motor nameplate. |
| Overload protection | Trips within ≤ 2 hours at 1.05 times the rated current, and trips within ≤ 2 minutes at 1.5 times the rated current | Complies with the 10A class tripping curve to protect the motor from long-term overload. |
| Short-circuit protection | Instantaneous tripping (10 times the rated current) | Fast response at the hardware level to protect the equipment from short-circuit damage. |
| Phase failure protection | Trips when the three-phase current imbalance is ≥ 50% | Prevents the motor from burning out due to single-phase operation. |
| Rated insulation voltage | 690V | Supports insulation reliability in high-voltage environments. |
- Mechanical Specifications
Dimensions: 120×100×80mm (H×W×D), suitable for installation on a standard 35mm rail.
Weight: Approximately 0.8kg.
Protection level: IP20 (needs to be installed in the control cabinet).
Installation methods:
Front panel wiring: Connect the main circuit through screws (recommended).
Plug-in installation: Requires a special base (such as the CC series conversion connector, see).
III. Control and Interface Parameters
- Control Functions
Manual/Automatic reset:
Manual reset: Press the reset button (RST) to restore after tripping.
Automatic reset: Switch by adjusting the screw (manual reset by default, see).
Test function: Supports simulated overload testing to verify the effectiveness of the protection function.
- Interface Configuration
| Interface Type | Quantity/Specification | Purpose |
| Main circuit terminals | 3 poles (L1/L2/L3) | Connect the motor power supply wires. |
| Control circuit terminals | 2 (A1/A2) | Supply power to the coil (AC 230V/DC 24V optional). |
| Auxiliary contacts | 1NO + 1NC (needs to be purchased separately) | Status indication or interlocking control (such as fault signal output, see). |
- Environment and Certification
Operating temperature: -5°C to +40°C (without derating), and a 20% derating is required from +40°C to +60°C.
Altitude: No derating when ≤ 2000m, and derating is required when exceeding this altitude.
Certifications:
Domestic: CCC certification (see the certificate number).
International: CE certification (complying with EN 60947-2), and some models support UL certification (the specific model needs to be confirmed).
- Typical Applications and Configuration Examples
- Motor Protection Scenarios
Fan control:
Parameter setting: Set the setting current = motor nameplate current × 1.1 (considering the starting impact).
Cooperating equipment: Used in combination with CHINT NXC contactors (such as NXC-32), and simplify the wiring through the CC conversion connector (see).
Water pump control:
Function activation: Connect to the PLC through the auxiliary contacts to achieve fault alarm.
Special requirements: If the water pump starts and stops frequently, it is recommended to select the automatic reset mode.
- Matching with Frequency Converters
Compatibility:
Current matching: The output current of the frequency converter needs to be ≤ the setting current of the NS2-32H.
Harmonic processing: If the frequency converter causes current distortion, the setting current needs to be increased by 1.3-1.9 times (see).
Installation suggestions:
Position: Install on the output side of the frequency converter, close to the motor.
Interference suppression: Use twisted-pair wires to connect the control circuit to avoid high-frequency interference.
- Precautions and Selection Suggestions
- Selection Key Points:
Current range: Select according to the rated current of the motor (17-23A is suitable for a 3kW motor).
Tripping grade: The 10A class is suitable for loads with long starting times (such as fans). If quick tripping is required, the 10 grade can be selected.
- Installation Requirements:
Heat dissipation space: Reserve a 50mm gap at the top/bottom to avoid the influence of high temperature on the protection accuracy.
Wiring torque: Tighten the main circuit terminals to 4N·m to prevent poor contact.
- Fault Troubleshooting:
False tripping: Check the motor load, whether the wiring is loose, or reduce the starting current.
No tripping: Test whether the protection function fails and replace the equipment if necessary.
VII. Accessories and Alternative Solutions
- Optional Accessories
Auxiliary contact module: AX-6 (1NO + 1NC), used for remote monitoring of the fault status.
Conversion connector: CC-3(NS2), quickly connect the contactor and the starter (see).
Waterproof installation box: Improve the protection level to IP55, suitable for humid environments.
- Alternative Models
Upgrade solution: If higher breaking capacity is required, the NS2-80H (80A, see) can be selected.
Economical choice: NS2-32 (without auxiliary contacts), with a cost reduction of approximately 30%.
The overload protection action time of the CHINT NS2-32H 17-23A thermal overload relay strictly follows the 10A class tripping curve of the IEC 60947-2 standard, and the matching of its core parameters with the actual application scenarios is as follows:
- Core Parameters of the Overload Protection Action Time
According to the IEC 60947-2 standard and CHINT’s official technical documents, the action time characteristics of the NS2-32H are as follows:
| Overload Multiple | Action Time Range | Typical Application Scenarios |
| 1.05 times | ≥ 2 hours without tripping | Long-term load fluctuations during normal motor operation |
| 1.2 times | ≤ 2 hours to trip | Light load overload (such as increased resistance caused by dust accumulation on the fan blades) |
| 1.5 times | ≤ 2 minutes to trip | Medium load overload (such as increased current after wear of the water pump impeller) |
| 6 times | ≤ 10 seconds to trip | Stalling or mechanical jamming (such as foreign matter blocking the conveyor belt) |
- Dynamic Characteristics in Practical Applications
- Inverse Time Characteristic
The action time of the NS2-32H has a non-linear relationship with the overload current, specifically manifested as:
The larger the overload multiple, the shorter the action time. For example:
– When the current reaches 2 times the rated value (34-46A), the action time is approximately 30 seconds.
– When the current reaches 3 times the rated value (51-69A), the action time is shortened to 10 seconds.
Cold start characteristic: When overloading starts from a cold state, the action time will be slightly longer than that in a hot state (after running for a certain period of time), and the specific difference is approximately 10-15%.
- Influence of Ambient Temperature
High-temperature environment (such as +50°C): The action time may be shortened by 20-30%, and the setting current needs to be appropriately reduced.
Low-temperature environment (such as -5°C): The action time may be extended by 10-15%, but it does not affect the effectiveness of the protection function.
- Influence of Wiring and Installation
Too thin wires: An increase in the resistance of the connecting wires will cause the action time to be advanced. It is recommended to use multi-strand copper wires of 2.5mm² or above.
Poor heat dissipation: Insufficient installation spacing (such as the top/bottom gap < 50mm) will cause the action time to be shortened, and it is necessary to ensure good ventilation in the control cabinet.
III. Key Parameter Verification and Testing Methods
- Manual Testing
Simulated overload: Raise the current to 1.5 times the setting current (25.5-34.5A) through an external voltage regulator, and observe whether the tripping time is ≤ 2 minutes.
Phase failure test: Disconnect any one-phase power supply and verify whether the tripping time is ≤ 2 seconds (phase failure protection characteristic).
- Tool Verification
Clamp ammeter: Record the overload current waveform in conjunction with an oscilloscope, and confirm that the deviation of the action time from the theoretical value is ≤ ±10%.
Thermal relay tester: Special equipment such as CHNT-THR is recommended, which can accurately simulate the action time under different overload multiples.
- Parameter Matching for Typical Application Scenarios
| Fault Phenomenon | Possible Cause | Solution |
| Frequent false tripping | The setting current is too low | Re-measure the actual current of the motor and adjust it. |
| No tripping under overload | Aging of the bimetallic strip | Replace the thermal overload relay. |
| No protection for phase failure | Fault in the phase failure detection circuit | Check the wiring of the auxiliary contacts or replace the module. |
- Precautions and Selection Suggestions
- Cooperation with Contactors:
Recommended model: CHINT NXC-32 contactor (requires quick installation through the CC conversion connector).
Cooperation key points: The breaking capacity of the contactor needs to be ≥ the starting current of the motor (usually 6-8 times the rated current).
- Alternative Solutions:
Upgraded model: If higher accuracy is required, the NS2-32H + AX-6 auxiliary contact module (supporting remote transmission of fault signals) can be selected.
Economical choice: If short-circuit protection is not required, it can be replaced with the NR2 series thermal relay (with a cost reduction of approximately 40%).
- Typical Fault Troubleshooting
| Fault Phenomenon | Possible Cause | Solution |
| Frequent false tripping | The setting current is too low | Re-measure the actual current of the motor and adjust it. |
| No tripping under overload | Aging of the bimetallic strip | Replace the thermal overload relay. |
| No protection for phase failure | Fault in the phase failure detection circuit | Check the wiring of the auxiliary contacts or replace the module. |





















