Chint NXB63-1P/D10 is a миниатюрный автоматический выключатель suitable for residential, industrial, and commercial scenarios. It is mainly used for overload protection, защита от короткого замыкания, and isolation of electrical circuits.
я. Analysis of Core Parameters
1. Model Meaning
– **NXB-63**: Series name, with a frame current of 63A, suitable for circuits with a rated current ≤ 63A.
– **1P**: Single-pole design, which only controls the live wire and occupies 1 модуль (18мм в ширину).
– **D10**: D-type tripping curve with a rated current of 10A. The D-type curve is applicable to **loads with high inrush current**, такие как моторы, transformers, and solenoid valves. Its instantaneous tripping range is **10-20 times the rated current** (то есть, rapid tripping occurs when the current is 100-200A), which can effectively avoid false tripping during motor startup.
2. Электрические характеристики
– **Rated Voltage**: 230 В переменного тока (suitable for single-phase circuits).
– **Breaking Capacity**: 6тот (соответствует GB/T 10963.1 и МЭК 60898-1 стандарты), capable of safely interrupting the circuit when the short-circuit current is ≤ 6kA.
– **Service Life**: Mechanical life of 20,000 operations and electrical life of 10,000 операции, meeting the requirements of long-term use.
3. Сертификаты и стандарты
– It has passed the CCC certification (China Compulsory Certification) and complies with the CE standard (for some export models), ensuring product quality and safety.
II. Application Scenarios and Selection Recommendations
1. Типичные применения
– **Power Equipment Protection**: Such as small motors (power ≤ 2.2kW; a 10A circuit breaker is suitable for approximately a 2.2kW three-phase motor or a 1.5kW single-phase motor), air-conditioning compressors, water pumps, и т. д..
– **Industrial Control Circuits**: Protecting equipment prone to surge currents, such as solenoid valves and transformers.
– **Residential Power Distribution**: Can be used for branches of high-power electrical appliances (например, ovens, электрические водонагреватели), but it should be noted that in single-phase circuits, it needs to be used with a neutral terminal block.
2. Selection Notes
– **Load Current Matching**: Ensure that the normal operating current of the circuit is ≤ 10A, and the peak starting current of the motor does not exceed the tripping curve range (100-200А).
– **Breaking Capacity Adaptation**: Select the breaking capacity according to the short-circuit current level at the installation location. If the short-circuit current may exceed 6kA, it is necessary to upgrade to the **NXB-63H series** (with a breaking capacity of 10kA).
– **Installation Compatibility**: The NXB-63 series is compatible with the DZ47 series in terms of DIN rail installation dimensions (18mm per pole). Однако, the terminal design of the NXB series is more compact and can accommodate thicker wires (например, 4мм²).
III. Price and Market Supply
1. Ценовой диапазон
– The retail price per unit is approximately **5-20 RMB**, which varies depending on the procurement channel:
– E-commerce platforms (например, 1688, Lichuang Mall): Примерно 5-6 юаней за единицу.
– Offline distributors or brand flagship stores: Примерно 15-20 юаней за единицу.
– Discounts are available for bulk purchases (например, a box of 20 units), and the unit price can be reduced to 4-5 юаней.
2. Inventory and Alternative Models
– **Inventory Status**: In 2025, the market supply is sufficient, and mainstream platforms have spot goods available.
– **Alternative Solutions**: For higher breaking capacity, the **NXB-63H 1P D10** (with a breaking capacity of 10kA and a price of approximately 10-15 юаней за единицу) можно выбрать; for leakage protection, it can be matched with the **NXBLE-63 series residual current circuit breaker** (например, 1P+N C10 30mA).
IV. Installation and Usage Tips
1. Этапы установки
– Ensure operation is performed after power-off. Clip the circuit breaker onto the 35mm standard DIN rail and tighten the terminal blocks (it is recommended to use a screwdriver with a torque ≤ 0.5N·m).
– A single-pole circuit breaker only controls the live wire; the neutral wire must be connected through a neutral terminal block to prevent electrical appliances from being charged due to neutral wire disconnection.
2. Рекомендации по техническому обслуживанию
– Regularly check for signs of oxidation or overheating on the contacts, and operate the circuit breaker 2-3 times a year to maintain mechanical flexibility.
– If frequent tripping occurs, it is necessary to check whether the load is overloaded, or if there is a line short-circuit or ground fault.
3. Safety Precautions
– Replacing the circuit breaker while it is energized is strictly prohibited; the operation must be performed by a professional electrician.
– Avoid installation in humid environments; if outdoor use is required, a supporting waterproof distribution box must be used.
В. Comparison with Competitors
| Модель | Кривая срабатывания | Разрывная способность | Цена (RMB/Unit) | Сценарии применения |
| Chint NXB63-1P/D10 | D-тип | 6тот | 5-20юаней | High inrush current loads (например, motors) |
| Schneider iC65N 1P D10 | D-тип | 6тот | 15-30юаней | High-end residences, precision equipment |
| Delixi CDB6-1P/D10 | D-тип | 6тот | 6-12юаней | Residential and small industrial scenarios |
Краткое содержание
With its high cost-effectiveness, reliable D-type tripping protection, and wide compatibility, the Chint NXB63-1P/D10 has become the preferred choice for power circuit protection. During selection, the breaking capacity should be reasonably chosen based on load characteristics and short-circuit current, and attention should be paid to installation specifications to ensure safety. For leakage protection, it is recommended to use it with the NXBLE series residual current circuit breaker.
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи