Вичат: +86-13184948252 WhatsApp: 0086-13811255435 Электронная почта: kent@bestcontactor.com

О Контакт |

CHINT NXMLE-630S/4300A-630A - Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи

автоматический выключатель/

CHINT NXMLE-630S/4300A-630A

Model Explanation Model Part Description NXMLE CHINT Kunlun Series Residual Current Operated Circuit Breaker (MCCB with earth leakage protection) 630 Frame rating current 630A S Breaking capacity class S (25kA at AC400V/415V, ultimate breaking capacity 50kA) 4300A 4P (трехфазный четырехпроводной, 3П+Н), thermal-magnetic trip unit, standard version without accessories 630A Rated operational current 630A Key Parameters ...

  • Подробная информация о продукте

Model Explanation

Model PartОписание
NXMLECHINT Kunlun Series Residual Current Operated Автоматический выключатель (MCCB with earth leakage protection)
630Frame rating current 630A
СBreaking capacity class S (25kA at AC400V/415V, ultimate breaking capacity 50kA)
4300А4П (трехфазный четырехпроводной, 3П+Н), thermal-magnetic trip unit, standard version without accessories
630АRated operational current 630A
  1. Ключевые параметры
Категория параметраЦенитьПримечания
Основные параметры
ТипMoulded Case Circuit Breaker with Earth Leakage Protection (Residual Current Circuit Breaker)Provides overload, short-circuit and earth leakage protection
поляки4П (3П+Н)Three phases + neutral
Trip typeТермомагнитный (Curve C)For power distribution protection
Номинальное напряжение изоляции Ui800В и
Номинальное рабочее напряжение Ue400V/415V AC (4П)
Rated frequency50/60Гц
Current Parameters
Frame current Inm630А
Номинальный ток In630А
Residual operating current Iホ馬100/200/300mA adjustableSelectable per requirements
Residual current tripping time0.3с (стандартный)Fast personal safety protection
Разрывная способность
Rated service breaking capacity Ics25тот (AC400V)Class S
Ultimate short-circuit breaking capacity Icu50тот (AC400V)
Функции защитыLong-time overload, short-time delay, instantaneous short-circuit, earth leakage protectionFull protection for circuits and equipment
  1. Mounting Dimensions
Mounting TypeРазмеры (W×H×D, мм)Примечания
Зафиксированный (front/rear connection)280×280×100Standard 4P dimensions
Plug-in type280×280×120Including plug-in base
Mounting modeЗафиксированный / Plug-in
Connection typeFront / Rear connectionRear connection requires special kit
Terminal sizeM12 hex socket screwFor large cross-section cables
  1. Applications
  2. Low-voltage distribution systems: Main or branch protection for three-phase four-wire circuits up to 630A
  3. Industrial equipment protection: Protect motors, transformers and other electrical devices against overload, short-circuit and earth leakage
  4. Building electrical: Main and sub-distribution boards in commercial buildings and industrial plants
  5. Personal safety: Indirect contact protection against fatal electric shock
  6. Electrical fire prevention: Protection against earth fault current induced electrical fires
  7. Operating Notes
  8. Ambient conditions:

Температура окружающей среды: -25℃ ~ 70℃

Высота: ≤ 2000m (derate if exceeded)

Влажность: ≤ 95% (non-condensing)

Avoid flammable, explosive or highly corrosive environments

  1. Требования к проводке:

Strictly separate N line and phase lines; N line must pass through the leakage detection transformer

Terminals must be securely tightened to avoid overheating

Cable cross-section suitable for 630A (≥ 185mm² copper recommended)

  1. Selection matching:

Residual current: 300mA for general distribution, 30mA for personal protection (special model)

Breaking capacity must match system short-circuit current; Class S suitable for general industry

  1. Maintenance:

Test monthly using the test button

Regularly check terminals for overheating

Keep clean to ensure heat dissipation

  1. Поиск неисправностей
SymptomВозможные причиныРешения
Trips immediately after closing1. Short circuit1. Locate short circuit
2. Residual current too low2. Adjust to suitable Iホ馬
3. Trip unit fault3. Replace trip unit
Fails to trip on overload1. Thermal trip failure1. Replace thermal trip
2. Over-current setting too high2. Reset current setting
Fails to trip on earth leakage1. Leakage module fault1. Replace leakage module
2. N line not through CT2. Rewire correctly
3. Test button fault3. Replace test button
Excessive heating during operation1. Loose connections1. Tighten terminals
2. Перегрузка2. Reduce load
3. Poor ventilation3. Improve cooling
  1. Brand Alternatives
БрендАльтернативная модельСовместимость
ШнайдерNSX630S TM630D 4P 3D (with Vigi module)Same breaking capacity and rated current, similar dimensions
АББTmax T6H630 PR221DS-LSI R630 4P (with RC221)Matching protection, separate leakage module required
Сименс3VL630N630 4P (with 30mA leakage add-on)Same frame and rated current, compatible mounting
ВкусныйCDM3L-630S/4300A-630ADirect Chinese alternative, identical dimensions and parameters
Changshu SwitchCM3L-630S/4300A-630AMatching technical data, compatible mounting
  1. Краткое содержание

CHINT NXMLE‑630S/4300A‑630A is a high-performance 4P earth leakage MCCB for 630A three‑phase four‑wire distribution systems. It provides overload, short‑circuit and earth leakage protection, with Class S breaking capacity suitable for general industrial applications. Its thermal‑magnetic trip (Curve C) is ideal for distribution, effectively protecting equipment and personnel. Correct selection of residual current and proper installation are essential; regular maintenance ensures long service life and reliable protection.

CHINT NXMLE-630S/4300A-630A Mounting Dimensions

  1. Overall Mounting Dimensions

Mounting dimensions vary slightly by installation type. Official standard values:

Mounting TypeГабаритные размеры (W×H×D, мм)Panel Cutout (мм)Примечания
Зафиксированный (front/rear)280×280×100245×245 (bolt centers)Standard 4P, front/rear fixed same
Plug-in280×280×120245×245 (base centers)Includes base depth
Rear connection (special)280×280×100245×245Requires rear connection kit
  1. Key Dimension Details
  2. Ширина (Вт): 280mm – Standard 4P MCCB width, compatible with mainstream switchgear
  3. Высота (ЧАС): 280mm – Including operating handle, consistent with Kunlun 630A frame
  4. Глубина (Д):

Фиксированный тип: 100мм

Plug-in type: 120мм (тело + base)

  1. Mounting bolts: M12 hex socket for high-current 630A application
  2. Mounting plate thickness: ≥ 6mm recommended for strength and cooling
  3. Minimum clearances: ≥25mm left/right, ≥50mm top/bottom for operation and ventilation
  4. Mounting Methods
  5. Fixed mounting: Most common, bolted directly to panel; front or rear connection
  6. Plug-in mounting: Uses dedicated base for fast replacement, suitable for frequent maintenance
  7. Rear connection: Terminals on rear side, saves front panel space and improves layout
  8. Installation Notes

Install vertically or horizontally, tilt angle ≤ 15°

Correctly separate N and phase lines; N must pass through leakage transformer

Check and tighten all terminals after installation

Allow sufficient ventilation to prevent overheating

Предыдущий:

Оставить ответ

Оставить сообщение