GV3P80 is a 3‑pole thermal‑magnetic motor circuit breaker from Schneider Electric TeSys GV3 series. It has an adjustment current range of 70–80A, suitable for 45kW (400В) / 55кВт (690В) three‑phase motors. It integrates triple protection (перегрузка, short‑circuit, phase failure) and isolation function, serving as a core protection component in industrial motor circuits.
- Модель Объяснение
GV3: TeSys GV3 motor circuit breaker series (frame size 3)
П: Thermal‑magnetic release (triple protection: перегрузка + short‑circuit + phase failure)
80: Rated current 80A, adjustable range 70–80A (continuously adjustable)
- Key Specifications (Full Data)
| Элемент | Спецификация |
| поляки | 3П (three‑phase) |
| Adjustment current range | 70–80A (continuously adjustable) |
| Тип поездки | Термомагнитный |
| Short‑circuit trip multiplier | 14×In (1120А) |
| Breaking capacity Icu | 65kA @ 230V; 50kA @ 400V; 6kA @ 690V |
| Номинальное рабочее напряжение Ue | 690В переменного тока 50/60 Гц |
| Insulation voltage Ui | 690В и |
| Impulse withstand voltage Uimp | 6кВ |
| Подходящая мощность двигателя | 45kW @ 400V; 55kW @ 690V; 22kW @ 230V |
| Терминалы | EverLink screw terminals (25–35mm² cable) |
| Монтаж | DIN-рейка (width 55mm), screw mountable |
| Degree of protection | IP20 (front) |
| Рабочая температура | -20°C ~ +60°C (derating factor: 0.8 at +60°C) |
| Механическая выносливость | 50,000 operating cycles |
| Электрическая выносливость | 20,000 циклы (category AC‑3) |
| Функция изоляции | Complies with IEC 60947‑1, can be used as safety isolator |
| Сертификаты | CCC, CE, UL, CSA, IEC 60947‑4‑1 |
| Масса | Приблизительно. 1.02 кг |
| Размеры (Ш×В×Г) | 55 × 105 × 78 мм |
- Основные функции & Преимущества
- Triple Protection
Thermal trip: Overload inverse‑time protection (simulates motor heating characteristics)
Magnetic trip: Short‑circuit instantaneous protection (fixed 14×In)
Защита от обрыва фазы: Automatic trip under three‑phase unbalance (IEC 60947‑4‑1)
- EverLink Terminal Technology
Maintenance‑free, anti‑loosening, oxidation‑resistant, suitable for large‑section cables, reduces wiring failure risks.
- Safety Design
Knob operation, lockable in OFF position (до 3 padlocks)
Clear current scale for precise adjustment
Complies with IEC isolation standards, usable as motor circuit isolator
- Wide Environmental Adaptability
Operating altitude: ≤3000m (no derating required)
Vibration resistance: 10–150Hz, 0.5mm amplitude
Shock resistance: 5Gn (11РС); 30Gn (1РС)
- Справочник по выбору (TeSys GV3 Series)
| Модель | Adjustment Current | Suitable Power (400В) | Trip Type | Функции |
| GV3P65 | 55–65A | 37кВт | Термомагнитный | Стандартный, EverLink terminals |
| GV3P80 | 70–80A | 45кВт | Термомагнитный | This model, max adjustment current |
| GV3L80 | 70–80A | 45кВт | Magnetic | Short‑circuit protection only |
| GV3ME80 | 40–80A | 45кВт | Термомагнитный | 3‑step adjustment (40–50/63–80), economy version |
| GV3P40 | 30–40A | 22кВт | Термомагнитный | For small‑medium motors |
- Приложения
Прямой запуск / star‑delta starting circuits for three‑phase asynchronous motors
Main circuit protection for fans, насосы, компрессоры, конвейеры, machine tools
Industrial automation lines, construction equipment motor control
Motor circuits requiring isolation and safety interlock (например, emergency stop loops)
Motors with frequent starting/stopping and fluctuating loads
- Replacement Options
- Schneider same series
GV3L80 (short‑circuit only, lower cost)
GV3ME80 (simplified adjustment, same mounting space)
- Competitor alternatives
Сименс: 3RV1041‑4JA10 (70–80A, 3П, термомагнитный)
АББ: MS165‑80 (70–80A, 3П, термомагнитный)
Chinese brands: Chint NM1‑125S, Delixi CDM1‑125 (motor protection curve matching required)
- Upgrade solution
Schneider GV4P08N (frame 4, higher breaking capacity, for motors above 55kW)
Selection Tips
- Select adjustment range at 1.1–1.25 × motor rated current
- Confirm breaking capacity meets system short‑circuit current requirements
- For isolation function, prefer models with certified isolation
- For limited wiring space, choose EverLink terminal models to reduce faults
Complete Model List of Schneider Electric TeSys GV Series Motor Circuit Breakers
Schneider TeSys GV series motor circuit breakers include six sub‑series: GV1, GV2, GV3, GV4, GV5, GV6, covering an adjustment range from 0.06A to 800A, suitable for 0.03kW to 400kW (400В) three‑phase motors, with thermal‑magnetic, magnetic, and economy thermal‑magnetic protection types.
- GV1 Series (Miniature, прекращено, replaced by GV2ME)
GV1ME01: 0.1–0,16А
GV1ME02: 0.16–0.25A
GV1ME03: 0.25–0.4A
GV1ME04: 0.4–0.63A
GV1ME05: 0.63–1.0A
GV1ME06: 1.0–1.6A
GV1ME07: 1.6–2.5A
GV1ME08: 2.5–4.0A
- GV2 Series (Маленький, 0.06–16A, 0.03–15kW/400V)
2.1 GV2P (Термомагнитный, полная защита, knob)
| Модель | Adjustment Current | Suitable Power (400В) |
| GV2P01 | 0.1–0,16А | 0.06кВт |
| GV2P02 | 0.16–0.25A | 0.12кВт |
| GV2P03 | 0.25–0.4A | 0.2кВт |
| GV2P04 | 0.4–0.63A | 0.37кВт |
| GV2P05 | 0.63–1.0A | 0.55кВт |
| GV2P06 | 1.0–1.6A | 0.75кВт |
| GV2P07 | 1.6–2.5A | 1.5кВт |
| GV2P08 | 2.5–4.0A | 2.2кВт |
| GV2P10 | 4.0–6.3A | 3кВт |
| GV2P14 | 6.3–10A | 4кВт |
| GV2P16 | 10–16A | 7.5кВт |
2.2 GV2L (Magnetic, short‑circuit only, knob)
| Модель | Adjustment Current | Suitable Power (400В) |
| GV2L01 | 0.1–0,16А | 0.06кВт |
| GV2L02 | 0.16–0.25A | 0.12кВт |
| GV2L03 | 0.25–0.4A | 0.2кВт |
| GV2L04 | 0.4–0.63A | 0.37кВт |
| GV2L05 | 0.63–1.0A | 0.55кВт |
| GV2L06 | 1.0–1.6A | 0.75кВт |
| GV2L07 | 1.6–2.5A | 1.5кВт |
| GV2L08 | 2.5–4.0A | 2.2кВт |
| GV2L10 | 4.0–6.3A | 3кВт |
| GV2L14 | 6.3–10A | 4кВт |
| GV2L16 | 10–16A | 7.5кВт |
| GV2L20 | 14–20А | 11кВт |
| GV2L22 | 18–25A | 15кВт |
2.3 GV2ME (Economy thermal‑magnetic, pushbutton, 3‑step)
| Модель | Adjustment Current | Suitable Power (400В) |
| GV2ME01 | 0.1–0,16А | 0.06кВт |
| GV2ME02 | 0.16–0.25A | 0.12кВт |
| GV2ME03 | 0.25–0.4A | 0.2кВт |
| GV2ME04 | 0.4–0.63A | 0.37кВт |
| GV2ME05 | 0.63–1.0A | 0.55кВт |
| GV2ME06 | 1.0–1.6A | 0.75кВт |
| GV2ME07 | 1.6–2.5A | 1.5кВт |
| GV2ME08 | 2.5–4.0A | 2.2кВт |
| GV2ME10 | 4–6.3A | 3кВт |
| GV2ME14 | 6.3–10A | 4кВт |
| GV2ME16 | 10–16A | 7.5кВт |
2.4 GV2LE (Magnetic with electronic trip, special applications)
GV2LE01 ~ GV2LE22: matching current ratings as GV2L, with electronic trip
- GV3 Series (Середина, 9–80A, 5.5–45kW/400V, 55mm width)
3.1 GV3P (Термомагнитный, полная защита, EverLink)
| Модель | Adjustment Current | Suitable Power (400В) |
| GV3P13 | 9–13A | 5.5кВт |
| GV3P18 | 13–18A | 11кВт |
| GV3P25 | 18–25A | 15кВт |
| GV3P32 | 23–32A | 18.5кВт |
| GV3P40 | 30–40A | 22кВт |
| GV3P50 | 40–50A | 30кВт |
| GV3P65 | 55–65A | 37кВт |
| GV3P73 | 65–73A | 45кВт |
| GV3P80 | 70–80A | 45кВт |
3.2 GV3L (Magnetic, short‑circuit only)
GV3L25: 18–25A
GV3L32: 23–32A
GV3L40: 30–40A
GV3L50: 40–50A
GV3L65: 55–65A
GV3L80: 70–80A
3.3 GV3ME (Economy thermal‑magnetic, 3‑step)
| Модель | Adjustment Current | Suitable Power (400В) |
| GV3ME40 | 40–50A | 30кВт |
| GV3ME63 | 50-63А | 37кВт |
| GV3ME80 | 40–80A (3 steps: 40–50/63–80) | 45кВт |
- GV4 Series (Большой, 25–115A, 15–55kW/400V, 81mm width)
4.1 GV4P (Термомагнитный, полная защита)
| Модель | Adjustment Current | Suitable Power (400В) |
| GV4P25 | 25–32A | 18.5кВт |
| GV4P40 | 32–40A | 22кВт |
| GV4P50 | 40–50A | 30кВт |
| GV4P63 | 50-63А | 37кВт |
| GV4P80 | 63–80A | 45кВт |
| GV4P100 | 80–100A | 55кВт |
| GV4P115 | 100–115A | 55кВт |
4.2 GV4L / GV4LE (Magnetic type)
GV4L25 ~ GV4L115: matching current ratings as GV4P
GV4LE25 ~ GV4LE115: magnetic with electronic trip
4.3 Special GV4 Models
GV4PB80S: UL489 approved, 63–80A
GV4P02N: 2‑pole thermal‑magnetic, special applications
- GV5 / GV6 Series (Extra‑large, 100–800A, 55–400kW/400V)
GV5P100: 80–100A
GV5P125: 100–125A
GV5P160: 125–160A
GV5P200: 160–200A
GV6P250: 200–250A
GV6P315: 250–315A
GV6P400: 315–400A
GV6P500: 400–500A
GV6P630: 500–630A
GV6P800: 630–800A
- Правила именования моделей
| Letter/Number | Значение |
| GV | TeSys GV series motor circuit breaker |
| 1/2/3/4/5/6 | Frame size (1 = smallest, 6 = largest) |
| П | Thermal‑magnetic trip (перегрузка + short‑circuit + phase failure) |
| л | Magnetic trip (short‑circuit only) |
| ME | Economy thermal‑magnetic trip (3‑step, cost‑optimized) |
| ТО | Magnetic trip with electronic functions |
| Number | Текущий рейтинг (например, 80 = 70–80A) |
- Quick Selection Guide
- Select adjustment range at 1.1–1.25 × motor rated current
- For full protection (перегрузка + short‑circuit + phase failure): choose P series
- If thermal protection exists (например, VFD): choose L series (short‑circuit only)
- Cost‑sensitive, simple adjustment: choose ME series (3‑step)
- Small motors (≤15kW): GV2; середина (15–45kW): GV3; большой (≥55kW): GV4–GV6
- Примечания
- All models are 3‑pole (3П) for three‑phase asynchronous motors
- Protection characteristics comply with IEC 60947‑4‑1
- Отключающая способность: GV2/GV3 100kA@400V; GV4 65kA@400V
- Монтаж: 35мм стандартная DIN-рейка
- Degree of protection: IP20 (front operating part)