EBS203C-200A-3P is a 3-pole, 200A rated earth-leakage автоматический выключатель в литом корпусе (MCCB/ELCB) manufactured by LS Electric (formerly LS Industrial Systems / LG Industrial Systems). It provides overcurrent, short-circuit and earth-leakage protection for three-phase electrical circuits.
📌 Model Explanation
EBS203C: EBS series earth-leakage MCCB; 200 = frame size (AF), 3 = number of poles (3П), C = thermal-magnetic trip type (ТМ).
200А: Номинальный рабочий ток 200 amperes.
3П: 3 столбы, suitable for three-phase three-wire systems.
⚙️ Key Specifications
| Элемент | Спецификация |
| Frame size (AF) | 200AF~399AF |
| Rated short‑circuit breaking capacity (Ику) | 85kA at AC220V; 37kA at AC400V |
| Номинальное напряжение | AC220/460V |
| Функции защиты | Перегрузка, короткое замыкание, утечка на землю (100/200/500mA optional) |
| Тип поездки | Thermal‑magnetic trip (ТМ), instantaneous trip rating 12×In |
| Размеры (В×Ш×Г) | 165×105×87mm |
| Масса | Приблизительно. 1.2кг |
| Сертификаты | CE, CCC |
🛠️ Applications & Совместимость
Typical applications: Промышленное распределение электроэнергии, production line equipment, power and lighting circuits, suitable for three-phase applications requiring reliable earth-leakage and short-circuit protection.
Рекомендация: Can be used with Meta-MEC series products for selective protection and coordination to improve system reliability.
🔄 Equivalent & Series Models
Same series: EBS203C-100A/125A/150A/175A, EBS204C (4-столб), и т. д..
Alternative references: ABB Tmax series, Schneider NSX series, Chint NM8L series and other equivalent earth-leakage MCCBs. Breaking capacity and mounting dimensions must be matched.
📦 Supply & Приобретение
Бренд: LS Electric (LSIS), originally manufactured in South Korea.
Purchasing channels: Authorized LS Electric distributors in China, industrial platform www.bestcontactor.com. Typical price is around one thousand RMB; negotiable for bulk orders.
The core difference between EBS203C-200A-3P and EBS203C-200A-4P (стандартная модель: EBS204C-200A) lies in the number of poles and the control method of the neutral (Н) conductor, which directly affects wiring, protection scope and application scenarios.
- Structural Differences
EBS203C-200A-3P (3-столб)
Структура: 3 line/incoming terminals, controlling only L1, Л2, L3 (three-phase live conductors).
Нейтральный (Н): Does not pass through the breaker; directly connected.
Защита: Обеспечивает перегрузку, short-circuit and earth-leakage protection only for three-phase live conductors.
EBS204C-200A-4P (4-столб)
Структура: 4 line/incoming terminals, controlling L1, Л2, L3 + Н (three-phase live conductors + нейтральный).
Нейтральный (Н): Passes through the breaker and switches simultaneously with phase conductors.
Защита: Protects three-phase live conductors + neutral and can disconnect a faulty neutral line.
- Key Parameter Comparison
| Элемент | EBS203C‑200A‑3P | EBS204C‑200A‑4P |
| Рамка / Текущий | 200AF, 200А, thermal‑magnetic type C | Идентичный |
| Отключающая способность | 37kA at AC400V; 85kA at AC220V | Идентичный |
| Функции защиты | Перегрузка, короткое замыкание, утечка на землю | Идентичный |
| поляки | 3П (3полюс) | 4П (4полюс) |
| Нейтральный (Н) | Bypasses the breaker | Switched with phases |
| Ширина | Narrower (приблизительно. 105мм) | Wider (приблизительно. 140мм) |
| Applicable system | Three‑phase three‑wire (IT, TN‑C without PEN) | Three‑phase four‑wire (ТН‑С, TN‑C‑S, ТТ) |
III. Functional & Safety Differences
- Switching range
3П: Switches phases only. Neutral remains live, posing electric shock risk during maintenance.
4П: Switches both phases and neutral. Fully isolates power, safer and compliant with standards.
- Earth-leakage protection effectiveness
3П: Only detects three-phase current imbalance. Cannot protect against neutral faults (например, neutral-to-earth short circuit).
4П: Monitors total current of four poles (L1-L2-L3-N), trips on neutral leakage for complete protection.
- System compatibility
3П: Suitable for pure three-phase loads (моторы, насосы) with no single-phase loads and no neutral in the panel.
4П: Suitable for mixed three-phase + single-phase systems (коммерческий, промышленный, распределение зданий); neutral disconnection required for safety.
- Руководство по выбору
Choose 3P (EBS203C):
Loads are pure three-phase motors, компрессоры, heaters, и т. д., with no 220V single-phase circuits.
Neutral in the distribution box does not pass through this breaker; space is limited.
Choose 4P (EBS204C):
System is TN-S / TN-C-S (separate N and PE conductors).
Circuit supplies single-phase loads (освещение, розетки, control circuits); neutral must be switched.
Required by safety standards (обслуживание, earth-leakage protection, earthing systems).
Краткое содержание
3P = space-saving, cost-effective → dedicated for three-phase power
4P = safer, more complete → required for mixed power distribution
LS Electric EBS Series Earth-Leakage MCCBs (ЭЛЦБ): Model List & Cross-Brand Cross-Reference
- EBS Series Model System & Full List
Core features of EBS series: Earth-leakage molded case circuit breakers on LS Electric’s (formerly LS / LG Industrial Systems) Metasol platform, with built-in earth-leakage protection modules, providing triple protection against overload, short-circuit and residual current (утечка на землю) for low-voltage distribution systems.
- Model Naming Convention
EBS □□□ – □□□A – □P
EBS: Код серии (earth-leakage MCCB)
1st digit: Frame size (5=50AF, 10=100AF, 20=200AF, 40=400AF)
2nd digit: Количество полюсов (3=3P, 4=4P)
3rd letter: Класс отключающей способности (C=standard, S=high)
□□□A: Номинальный ток (В)
□P: Количество полюсов (3П/4П, consistent with 2nd digit)
- Complete Model List by Frame Size
1) 50AF Frame (EBS53C / EBS54C)
| поляки | Номинальный ток | Полная модель | Разрывная способность (AC400В) |
| 3П | 10A/16A/20A/25A/32A/40A/50A | EBS53C‑10A~50A | 18тот |
| 4П | 10A/16A/20A/25A/32A/40A/50A | EBS54C‑10A~50A | 18тот |
2) 100AF Frame (EBS103C / EBS104C)
| поляки | Номинальный ток | Полная модель | Разрывная способность (AC400В) |
| 3П | 63A/75A/100A | EBS103C‑63A/75A/100A | 37тот |
| 4П | 63A/75A/100A | EBS104C‑63A/75A/100A | 37тот |
3) 200AF Frame (EBS203C / EBS204C)
| поляки | Номинальный ток | Полная модель | Разрывная способность (AC400В) |
| 3П | 125A/150A/175A/200A/225A/250A | EBS203C‑125A~250A | 37тот |
| 4П | 125A/150A/175A/200A/225A/250A | EBS204C‑125A~250A | 37тот |
4) 400AF Frame (EBS403C / EBS404C)
| поляки | Номинальный ток | Полная модель | Разрывная способность (AC400В) |
| 3П | 250A/300A/350A/400A | EBS403C‑250A~400A | 50тот |
| 4П | 250A/300A/350A/400A | EBS404C‑250A~400A | 50тот |
- Earth-Leakage Parameters (Whole Series)
Residual operating current (IΔn): 30mA/100mA/300mA/500mA optional (default 30mA for personal protection)
Время работы: ≤0.3s (IΔn=30mA), ≤0,1 с (IΔn≥100mA)
Protection type: Тип А (переменного тока + пульсирующая утечка постоянного тока), suitable for modern electronic loads
- Cross-Brand Equivalent Table for EBS Series
Below are equivalent models from major brands with matching core parameters (frame, номинальный ток, столбы, отключающая способность) for replacement reference.
| LS EBS Model | ABB Tmax XT | Schneider NSX | Chint NM8L | Delixi CDM1L |
| EBS53C‑50A‑3P | XT1N160 TMD50 3P RCCB | NSX100N TM50D 3P Vigi | NM8L‑100S/3300 50A | CDM1L‑100C/3300 50A |
| EBS103C‑100A‑3P | XT1N160 TMD100 3P RCCB | NSX100N TM100D 3P Vigi | NM8L‑100S/3300 100A | CDM1L‑100C/3300 100A |
| EBS203C‑200A‑3P | XT2N250 TMD200 3P RCCB | NSX250N TM200D 3P Vigi | NM8L‑250S/3300 200A | CDM1L‑250C/3300 200A |
| EBS204C‑200A‑4P | XT2N250 TMD200 4P RCCB | NSX250N TM200D 4P Vigi | NM8L‑250S/4300 200A | CDM1L‑250C/4300 200A |
| EBS403C‑400A‑3P | XT4N630 TMD400 3P RCCB | NSX630N TM400D 3P Vigi | NM8L‑630S/3300 400A | CDM1L‑630C/3300 400A |
Key Notes for Replacement
- Breaking capacity matching: Select alternatives with breaking capacity ≥ original EBS model to ensure short-circuit protection reliability.
- Earth-leakage module compatibility:
ABB requires RC221/RC222 earth-leakage accessories
Schneider requires Vigi modules (built-in / add-on)
Domestic NM8L/CDM1L have built-in earth-leakage modules, no extra parts needed
- Mounting dimension check: Width may vary between brands (например, EBS203C-200A-3P: 105мм; Schneider NSX250: 108мм), affecting panel layout.
- Wiring type: Ensure replacement supports original mounting (fixed / plug-in) and connection (передний / rear wiring).
III. Key Differences: EBS203C-200A-3P vs EBS204C-200A-4P
| Элемент | EBS203C‑200A‑3P (3полюс) | EBS204C‑200A‑4P (4полюс) |
| поляки & Терминалы | 3 main terminals (Л1/Л2/Л3) | 4 main terminals (L1/L2/L3/N) |
| Neutral control | Neutral bypasses breaker | Neutral switched with phases |
| Protection scope | Перегрузка, короткое замыкание, leakage on phases only | Full protection on phases + нейтральный (including neutral leakage) |
| Ширина | 105мм | 140мм |
| Applicable system | 3‑phase 3‑wire (IT, TN‑C without PEN) | 3‑phase 4‑wire (ТН‑С, TN‑C‑S, ТТ) |
| Safety level | Phases switched only; extra isolation needed | Full isolation; higher safety |
- Выбор & Procurement Advice
- Выбор полюса
Pure three-phase power loads (моторы, компрессоры) → choose 3P (EBS203C)
Mixed three-phase + single-phase loads (освещение, розетки) → choose 4P (EBS204C) to meet safety standards
- Earth-leakage current selection
Personal protection (схемы розеток) → IΔn = 30mA
Электрическая противопожарная защита (power/lighting mains) → IΔn = 100mA / 300мА
- Purchasing channels
Authorized domestic distributors, industrial e-commerce platform www.bestcontactor.com
Regular stock models: EBS53C-50A, EBS103C-100A, EBS203C-200A, EBS403C-400A, и т. д..
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи