C10F32D100 is the complete order code of Schneider’s new-generation ComPacT NSX series автоматические выключатели в литом корпусе. The meaning of each segment is as follows:
| Code Segment | Значение | Description |
| C10 | Frame Size and Breaking Capacity | C10 = NSX100F, frame current 100A, breaking capacity Class F (36kA@415VAC) |
| Ф | Breaking Capacity Class | F = 36kA@415VAC, suitable for standard industrial applications |
| 3 | Number of Poles | 3 = 3-pole (3П3Д, three-phase three-wire system) |
| 2Д | Trip Unit Type | 2D = MicroLogic 2.2 electronic trip unit with display function |
| 100 | Номинальный ток | 100А, adjustable range 90-100A |
- Основные технические параметры
Основные параметры
| Parameter | Value | Description |
| Тип продукта | Molded Case Circuit Breaker (MCCB) | New-generation ComPacT NSX100F |
| Номинальное напряжение | 690VAC/50-60Hz | Maximum operating voltage |
| Номинальный ток (Iu) | 100А | Continuous operating current |
| Максимальная отключающая способность (Ику) | 36kA@415VAC | Ultimate breaking capacity |
| Service Breaking Capacity (Ics) | 36kA@415VAC (100%) | Service breaking capacity |
| Mounting Type | Зафиксированный | Standard mounting, plug-in type optional (C10F32D100P) |
| Protection Category | Category A | Соответствует МЭК 60947-2 стандартный |
MicroLogic 2.2 Trip Unit Parameters
| Функция защиты | Characteristic | Adjustable Range |
| Long-time Delay Protection (л) | Защита от перегрузки, inverse time-lag | 0.8-1.0脳Iu (90-100А) |
| Short-time Delay Protection (С) | Защита от короткого замыкания, definite time-lag | 3-6脳Iu, регулируемый |
| Instantaneous Protection (я) | Short-circuit instantaneous tripping, fixed | 10脳Iu (1000А) |
| Display Function | Current measurement and status indication | Real-time display of three-phase current |
Physical and Electrical Characteristics
| Parameter | Value |
| Power Loss | 14.1Вт |
| Weight | Approximately 2.5kg |
| Compliance Standards | МЭК 60947-2, GB 14048.2 |
| Certifications | CE, CCC, RoHS |
III. Функциональные особенности
- Comprehensive Protection: Provides three-stage protection including long-time delay, short-time delay and instantaneous protection, effectively preventing overload and short-circuit faults.
- Precise Control: Compared with thermal-magnetic trip units (TM series), electronic trip units offer more accurate protection curves and adjustable parameters.
- Status Visualization: MicroLogic 2.2 is equipped with LED display for real-time monitoring of current and fault status.
- Модульная конструкция: Supports a variety of accessories (вспомогательные контакты, alarm contacts, undervoltage release, и т. д.) for flexible installation.
- Environmental Friendly: Schneider Green Signature design, reducing energy consumption and carbon footprint.
- Easy Operation: Ergonomic handle for labor-saving operation; front-mounted accessories reduce wiring time by 40%.
- Сценарии применения
- Industrial Power Distribution Systems: Used as main switch or branch switch to protect motors, transformers and distribution lines.
- Building Electrical Systems: Low-voltage distribution cabinets in commercial buildings and industrial plants.
- Центры управления двигателем (МСС): Protect three-phase motors from locked rotor and overload conditions.
- Data Centers: Power protection for critical loads to ensure power supply continuity.
- New Energy Sector: DC-side protection of photovoltaic inverters and energy storage systems (additional configuration required).
- Product Comparison
Comparison with Trip Units of the Same Series
| Модель | Trip Unit Type | Main Differences | Сценарии применения |
| C10F32D100 | MicroLogic 2.2 | Electronic trip unit with display, three-stage protection | Industrial applications requiring precise protection and monitoring |
| C10F3TM100 | TM100D Thermal-Magnetic Trip | Thermal-magnetic trip unit, two-stage protection, cost-effective | Simple power distribution without precise adjustment requirements |
| C10F33D100 | MicroLogic 3.2 | Added earth fault protection (30-3000мА) |
Comparison with Chint Alternative Models
| Schneider Model | Chint Alternative Model | Similarities | Differences |
| C10F32D100 | NM1-125S/3300 100A | 3-pole, 100А, 36kA breaking capacity | Chint adopts thermal-magnetic trip unit without display; Schneider adopts electronic trip unit with display |
| NM1-125H/3340 100A | 3-pole, 100А, electronic trip unit | Chint has 50kA breaking capacity with slightly different protection functions |
- Selection and Usage Recommendations
- Selection Key Points
Select protection curves according to load types: for motor loads, it is recommended to set short-time delay to 5-6×Iu
Breaking capacity should be greater than the expected short-circuit current of the system
Consider future expansion; rated current should be slightly higher than the actual load current
- Меры предосторожности при установке
Ensure the mounting surface is flat and the tightening torque meets requirements (screw torque 25N·m)
Corresponding cable lugs must be used for terminal connections to avoid heating caused by poor contact
Leave sufficient heat dissipation space around and avoid close installation with heat-generating components
- Рекомендации по техническому обслуживанию
Regular inspection (at least once a year): appearance, tightness status, flexibility of operating mechanism
Check contact condition after short-circuit tripping and replace if necessary
Clean with dry compressed air to avoid moisture and dust accumulation
VII. Troubleshooting Guide
| Fault Phenomenon | Possible Causes | Troubleshooting Steps |
|---|---|---|
| Невозможность закрытия | 1. Undervoltage release without power supply 2. Trip unit malfunction 3. Mechanical lockout | 1. Check control power supply (if equipped) 2. Measure trip unit coil resistance 3. Manually reset the trip mechanism |
| False Tripping | 1. Перегрузка 2. Short circuit 3. Improper trip unit parameter setting | 1. Check load current 2. Check line insulation 3. Reset trip unit parameters |
| No Display After Tripping | 1. Trip unit power supply failure 2. Trip unit damage | 1. Check trip unit power supply 2. Replace the trip unit |